1. Catalogs
  2. Regin
  3. TLT...(-420)

TLT...(-420)

TLT...(-420)

TLT...(-420)

Product catalog summary
Overview: The TLT series is a range of high-quality temperature transmitters designed for immersion mounting, offering excellent long-term stability and a wide measurement range. They provide output signals of 0...10 V DC or 4...20 mA and require a supply voltage of 24 V AC or 15...35 V DC. The protection class is IP65.
Functionality: These transmitters use a temperature element to generate a signal proportional to the temperature, which is then converted to an output signal by the built-in electronics. They can adapt to different supply voltages automatically.
Technical Specifications:
  • Power Consumption: 15 mA (0...10 V output signal)
  • Output Load: Max. 1 mA (0...10 V), max. 500 Ω (4...20 mA)
  • Measurement Accuracy: ± 2°C for TLT100(-420), ± 1.5°C for TLT50(-420)
  • Cable Connection: Screw terminals
  • Sensor Type: NTC 10K
  • Immersion Length: 120 mm
  • Pipe Fitting: R 1/2”
  • Protection Class: IP65
  • Weight: 0.25 kg
  • Storage Temperature: -20…+70°C
  • Load Impedance: TLT50 / TLT100 Min. 10 kΩ, TLT50-420 / TLT100-420 Max. 500 Ω
  • Material: Sensor housing - Polycarbonate (PC), Well - Nickel plated brass/copper, Sensor - Nickel plated brass
Models:
  • TLT100: 18...24 V AC or 18...35 V DC, 0...100°C, 0...10 V, 3-wire, Immersion mounting
  • TLT100-420: 11...30 V DC, 0...100°C, 4...20 mA, 2-wire, Immersion mounting
  • TLT50: 18...24 V AC or 18...35 V DC, -30...+50°C, 0...10 V, 3-wire, Immersion mounting
  • TLT50-420: 11...30 V DC, -30...+50°C, 4...20 mA, 2-wire, Immersion mounting
Accessories:
  • DR-30/14: Brass pocket
  • DR-31/14: AISI 304 pocket
Dimensions and Wiring: The document provides detailed measurements in mm and wiring instructions for different models, ensuring proper installation and operation.
See more

Catalog excerpts

TLT...(-420)-1

TLT is a range of high quality temperature transmitters for immersion mounting. Function The transmitters are constructed around a temperature element providing a signal proportional to the temperature. The built-in electronics convert the measurement signal to an output signal 0...10 V DC or 4...20 mA. Supply voltage The transmitters can be powered either with 24 V AC or 18...35 V DC (0...10 V models), or 11...30 V DC (4...20 mA models). The transmitters will automatically adapt to the supply voltage. Immersion well The transmitter is supplied with a nickel plated brass/ copper well with a R 1/2” connection. HEAD Phone: Web: E-Mail: Excellent long-term stability Wide measurement range Output signal 0...10 V DC or 4...20 mA Supply voltage 24 V AC or 15...35 V DC Protection class I

 Open the catalog to page 1
TLT...(-420)-2

Technical data Power consumption Sensor housing HEAD OFFICE SWEDEN E-Mail: [email protected]

 Open the catalog to page 2

All Regin catalogs and technical brochures

  1. FLS…X

    4  Pages

  2. DTV…X

    3  Pages

  3. RCW-M32

    3  Pages

  4. DMD

    3  Pages

  5. HTRT10A(-D)

    3  Pages

  6. CTRTA(-D)

    3  Pages

  7. TTKN

    3  Pages

  8. DTT(H)(C)

    4  Pages

  9. RC-C3H…

    7  Pages

  10. RCC-C3DOCS...

    6  Pages

  11. RC-C3DOC…

    7  Pages

  12. TG-R5/PT100

    1  Page

  13. TG-AH4

    3  Pages

  14. DR-

    3  Pages

  15. TG-R5/PT1000

    1  Page

  16. TG-IH3/...

    3  Pages

  17. TG-KH3/...

    3  Pages

  18. DTV…X

    3  Pages

  19. TG-UH3/...

    2  Pages

  20. ED-TCV

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.