1. Catalogs
  2. Regin
  3. TG-UH3/...

TG-UH3/...

TG-UH3/...

TG-UH3/...

Product catalog summary
Overview: The TG-UH3 is an outdoor sensor designed for air temperature measurement, featuring a sealed housing with IP65 protection, easy access to connections, and a replaceable cable gland. It is equipped with a large mounting plate for stable installation.
Application: This sensor is versatile and can be used in various environments due to its different sensor element models.
Function: The sensor is suitable for all environments and is easy to install, even on uneven surfaces, thanks to its large contact surface on the mounting bracket. The terminal block for connecting to a controller is located under a removable cover.
Technical Specifications:
  • Protection Class: IP65
  • Temperature Range: -50 to +70 °C
  • Cable Gland: M16
  • Dimensions: 78 x 51 x 104 mm
  • Weight: 0.09 kg
Material: Both the housing and base are made of Polycarbonate (PC).
Models and Sensor Elements:
  • TG-UH3/PT100: PT100, 100 Ω at 0°C
  • TG-UH3/PT1000: PT1000, 1000 Ω at 0°C
  • TG-UH3/NTC1.8: NTC 1.8, 1800 Ω at 25°C
  • TG-UH3/NTC2.2: NTC 2.2, 2252 Ω at 25°C
  • TG-UH3/NTC10-01: NTC 10, 10 kΩ at 25°C
  • TG-UH3/NTC10-02: NTC 10, 10 kΩ at 25°C
  • TG-UH3/NTC10-03: NTC 10, 10 kΩ at 25°C
  • TG-UH3/NTC20: NTC 20, 20 kΩ at 25°C
  • TG-UH3/Ni1000-01: Ni1000, 1000 Ω at 0°C
  • TG-UH3/NI1000-02: Ni1000, 1000 Ω at 0°C
Documentation: All documentation is available for download at www.regincontrols.com.
See more

Catalog excerpts

TG-UH3/...-1

TG-UH3/... Outdoor sensor with housing Outdoor sensor for air temperature measurement. , n , ,, . . , Ini.r ✓ Sealed housing with IP65 ✓ Easy access to connection ✓ Replaceable cable gland ✓ Large mounting plate for easy, stable mounting The sensor measures the outdoor air temperature. It can be used for a wide range of applications since there are models with different sensor elements. The outdoor sensor is suitable for all environments. A large contact surface on the mounting bracket makes the sensor easy to mount also on uneven surfaces. The terminal block for connecting the analog input to a controller is located under the cover. The cover is easily removed from the base with a twist. The sensor is designed so that the seal remains in the cover at all times and the cable gland is replaceable. HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 1
TG-UH3/...-2

Technical data All documentation can be downloaded from www.regincontrols.com. HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 2

All Regin catalogs and technical brochures

  1. FLS…X

    4  Pages

  2. DTV…X

    3  Pages

  3. RCW-M32

    3  Pages

  4. DMD

    3  Pages

  5. HTRT10A(-D)

    3  Pages

  6. CTRTA(-D)

    3  Pages

  7. TTKN

    3  Pages

  8. DTT(H)(C)

    4  Pages

  9. RC-C3H…

    7  Pages

  10. RCC-C3DOCS...

    6  Pages

  11. RC-C3DOC…

    7  Pages

  12. TG-R5/PT100

    1  Page

  13. TG-AH4

    3  Pages

  14. DR-

    3  Pages

  15. TG-R5/PT1000

    1  Page

  16. TG-IH3/...

    3  Pages

  17. TG-KH3/...

    3  Pages

  18. DTV…X

    3  Pages

  19. TLT...(-420)

    3  Pages

  20. ED-TCV

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.