1. Catalogs
  2. Regin
  3. TG-IH3/...

TG-IH3/...

TG-IH3/...

TG-IH3/...

Product catalog summary
Overview: The TG-IH3 immersion sensor is designed for temperature measurement in heating or cooling applications. It features a sealed housing with IP65 protection and is available in various lengths to suit different applications.
Specifications: The sensor has a protection class of IP65, a time constant of 18 seconds, and a measuring temperature range from -20 to +120 °C. The probe diameter is 5 mm, and it has a pressure rating of PN25. The external dimensions are 78 x 156 x 104 mm, and it weighs 0.17 kg including packaging. The housing and base are made of polycarbonate, while the probe is made of stainless steel (EU1.4301/SUS304).
Models: Various models are available with different sensor elements and insertion lengths, including PT100, PT1000, NTC20, Ni1000, and NTC10-01. Each model has specific nominal resistance and insertion length.
Installation: The sensor requires a well for installation, which is not included. Users must mount a well on the pipe and secure the sensor with a locking screw. The terminal block for connecting to a controller is accessible under a removable cover.
Accessories: Accessories include mounting clips and wells of various lengths made from stainless steel or acid-proof stainless steel.
Documentation: Additional documentation is available for download from the manufacturer's website.
See more

Catalog excerpts

TG-IH3/...-1

TG-IH3/...Immersion sensor with housing t*J ✓ Sealed housing with IP65 ✓ Easy access to connection ✓ Replaceable cable gland Immersion sensor for temperature measurement in heating- or cooling applications. Available in different lengths. The immersion sensor measures the temperature in water pipes. It can be used for a wide range of applications, since there are models with different sensor elements and different insertion lengths. Needs to be installed in a well. The immersion sensor is suitable for all environments. A well is not delivered with the product. The user needs to mount a well on the pipe where temperature are wished to be measured, and then assemble the sensor in the well and secure the sensor with the locking screw. The terminal block for connecting the analog input to a controller is located under the cover. The cover is easily removed from the base with a twist. The sensor is designed so that the seal remains in the cover at all times and the cable gland is replaceable. HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 1
TG-IH3/...-2

Technical data HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 2
TG-IH3/...-3

L1 = 108, for 90 mm insertion length L2 = 98, for 90 mm insertion length All documentation can be downloaded from www.regincontrols.com. HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 3

All Regin catalogs and technical brochures

  1. FLS…X

    4  Pages

  2. DTV…X

    3  Pages

  3. RCW-M32

    3  Pages

  4. DMD

    3  Pages

  5. HTRT10A(-D)

    3  Pages

  6. CTRTA(-D)

    3  Pages

  7. TTKN

    3  Pages

  8. DTT(H)(C)

    4  Pages

  9. RC-C3H…

    7  Pages

  10. RCC-C3DOCS...

    6  Pages

  11. RC-C3DOC…

    7  Pages

  12. TG-R5/PT100

    1  Page

  13. TG-AH4

    3  Pages

  14. DR-

    3  Pages

  15. TG-R5/PT1000

    1  Page

  16. TG-KH3/...

    3  Pages

  17. DTV…X

    3  Pages

  18. TLT...(-420)

    3  Pages

  19. TG-UH3/...

    2  Pages

  20. ED-TCV

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.