RC-C3DOC…-1

RC-C3DOC...Pre-programmed room controller with display and communication RC-C3DOC... is a complete pre-programmed room controller from the Regio Midi series intended to control heating, cooling and CO2 in a zone control system. ✓ Communication via RS485 (Modbus, BACnet or EXOline) ✓ Quick and simple configuration via Application Tool ✓ Input for occupancy detector, window contact, condensation sensor, CO2 detector or changeover function ✓ Supply air temperature limitation The Regio controllers are suitable for use in buildings requiring optimum comfort and reduced energy consumption, such as offices, schools, shopping centres, airports, hotels and hospitals etc. RC-C3DOC... is a room controller in the Regio series. It has display and communication via RS485 (Modbus, BACnet or EXOline) for systems integration. The controller has a built-in room temperature sensor. An external sensor for room temperature, change-over or supply air temperature limitation can also be connected (PT1000). There is also an input for CO2 sensors. RC-C3DOC... can control 0...10 V DC valve actuators and/or 24 V AC thermal actuators or On/Off actuators with spring return and dampers. HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 1
RC-C3DOC…-2

RC-C3DOC... can be connected to a central SCADA system via RS485 (EXOline, BACnet or Modbus) and configured for a specific application using the free configuration software Application Tool. The modular design, featuring a separate bottom plate for wiring, makes the entire Regio range of controllers easy to install and commission. The bottom plate can be put into place before the electronics are installed. Mounting takes place directly on the wall or on an electrical connection box. The display has the following indications: The buttons on the controller enables easy setting of parameter values...

 Open the catalog to page 2
RC-C3DOC…-3

Off: Heating and cooling are disconnected. However, frost protection is still active (factory setting (FS))=8°C). This mode is activated if a window is opened. Unoccupied: The room in which the controller is placed is not used for a extended time period, such as during holidays or long weekends. Both heating and cooling are kept within a temperature interval with configurable min/ max temperatures (FS min=15°C, max=30°C). Stand-by: The room is in an energy saving mode and is not used at the moment. This can, for instance, be during nights, weekends and evenings. The controller stands by to change...

 Open the catalog to page 3
RC-C3DOC…-4

Change-over function RC-C3DOC… has an input for change-over that automatically resets output UO1 to operate with heating or cooling function. The input can be connected to sensors of type PT1000, with the sensor mounted so that it senses the temperature of the coil supply pipe. As long as the heating valve is more than 20 % open, or each time a valve exercise takes place, the difference between the media and room temperature is calculated. The control mode is then changed based on the temperature difference. Optionally, a potential-free contact can be used. When the contact is open, the controller...

 Open the catalog to page 4
RC-C3DOC…-5

Technical data HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 5
RC-C3DOC…-6

Setpoint settings via Application Tool HEAD OFFICE SWEDEN E-mail: [email protected]

 Open the catalog to page 6
RC-C3DOC…-7

Output for 0...10 V valve actuator/damper actuator alt. thermal actuator alt. On/Off actuators, heating or cooling (FS). Input for external sensor, alt. change-over sensor, alt. supply air temperature limitation sensor Input for CO2 sensor, 0...10 V DC, alt. air speed Input for occupancy detector, alt. window switch, alt. digital change-over Input for condensation sensor KG-A/1 alt. window switch alt. digital change-over Analogue ground Application examples Heating/Cooling/VAV Temperature sensors Modbus TCP/IP EXOline BACnet Presence detector Window switch Documentation All documentation can...

 Open the catalog to page 7

All Regin catalogs and technical brochures

  1. FLS…X

    4  Pages

  2. DTV…X

    3  Pages

  3. RCW-M32

    3  Pages

  4. DMD

    3  Pages

  5. HTRT10A(-D)

    3  Pages

  6. CTRTA(-D)

    3  Pages

  7. TTKN

    3  Pages

  8. DTT(H)(C)

    4  Pages

  9. RC-C3H…

    7  Pages

  10. RCC-C3DOCS...

    6  Pages

  11. TG-R5/PT100

    1  Page

  12. TG-AH4

    3  Pages

  13. DR-

    3  Pages

  14. TG-R5/PT1000

    1  Page

  15. TG-IH3/...

    3  Pages

  16. TG-KH3/...

    3  Pages

  17. DTV…X

    3  Pages

  18. TLT...(-420)

    3  Pages

  19. TG-UH3/...

    2  Pages

  20. ED-TCV

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.