1. Catalogs
  2. Raycap
  3. Lightning and Overvoltage Protection with Integrated Fuse ProTec T1SF 1+0

Lightning and Overvoltage Protection with Integrated Fuse ProTec T1SF 1+0

Lightning and Overvoltage Protection with Integrated Fuse ProTec T1SF 1+0

Lightning and Overvoltage Protection with Integrated Fuse ProTec T1SF 1+0

Product catalog summary
Overview: The ProTec T1SF 1+0 is a lightning and overvoltage protection device with an integrated fuse, designed for use in main distribution boards. It is suitable for TN-S, TN-C, and TT network systems, providing protection in L-PE, N-PE (only TN-S), L-PEN, and L-N modes. The device complies with IEC 61643-11:2011 and EN 61643-11:2012+A11:2018 standards.
Technical Specifications:
  • Nominal AC Voltage: 240 V
  • Maximum Continuous Operating Voltage: 275 V
  • Nominal Discharge Current: 25 kA
  • Maximum Discharge Current: 65 kA
  • Impulse Discharge Current: 25 kA
  • Voltage Protection Level: 1500 V
  • Response Time: < 100 ns
  • Short-Circuit Current Rating: 75 kA
  • Operating Temperature Range: -40 ºF to +185 ºF (-40 ºC to +85 ºC)
  • Degree of Protection: IP 20
Mechanical & Environmental Features:
  • Housing Material: Thermoplastic, UL 94 V-0
  • Mounting: 35 mm DIN Rail, EN 60715
  • Operating Humidity: 5% to 95%
  • Altitude: Up to 6562 ft (2000 m)
Order Information:
  • Order Code: 275
  • Product Variants: ProTec T1SF-xxx-1+0, ProTec T1SF-xxx-1+0-R (with remote contacts), ProTec T1SF-xxx-P (plug)
  • Standard Order Quantity: 7 Units for main device, 6 Units for spare plug
Dimensions & Packaging:
  • Single Unit Weight: 0.727 pounds (330 grams) for ProTec T1SF-xxx-1+0, 0.736 pounds (334 grams) for ProTec T1SF-xxx-1+0-R
  • Packaging Dimensions: 4.3 × 4.5 × 13.8 inches (109 × 115 × 352 mm)
See more

Catalog excerpts

Lightning and Overvoltage Protection with Integrated Fuse ProTec T1SF 1+0-1

DATA SHEET Lightning and Overvoltage Protection with Integrated Fuse Main Distribution Boards TN-S, TN-C, TT (only L-N) L-PE, N-PE (only TN-S), L-PEN, L-N Class I+II / Type 1+2 Pluggable Design IEC 61643-11:2011 EN 61643-11: 2012+A11:2018 Location of Use: Network Systems: Mode of Protection: IEC/EN Category: Housing: Compliance: Class I •  Class II •   ype 1 •   ype 2  T T E CURREN Technical Data ProTec T1SF-xxx-1+0(-R) IEC Electrical Nominal AC Voltage (50/60Hz) Maximum Continuous Operating Voltage (AC) Nominal Discharge Current (8/20 µs) Maximum Discharge Current (8/20 µs) Impulse Discharge Current (10/350 µs) Specific Energy Voltage Protection Level Response Time Overcurrent Protection Short-Circuit Current Rating (AC) Follow Current Interrupt Rating (AC) Additional Electrical Parameters (Tests performed within Raycap testing laboratory only) Residual Voltage at 5 kA (8/20 μs) Mechanical & Environmental Operating Temperature Range Permissible Operating Humidity Terminal Screw Torque Conductor Cross Section (max) 39.9 Ibf·in [4.5 Nm] 2 AWG (Solid, Stranded) / 4 AWG (Flexible) 35 mm2 (Solid, Stranded) / 25 mm2 (Flexible) Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0 Thermal Protection Operating State / Fault Indication Green Flag / Not Green Flag RC Conductor Cross Section (max) Order Code ProTec T1SF

 Open the catalog to page 1
Lightning and Overvoltage Protection with Integrated Fuse ProTec T1SF 1+0-2

Line Conductor Terminal Neutral Conductor Terminal Remote Contacts Terminal (Optional) Thermal Disconnector Integrated Surge Adapted Backup Fuse Complete Unit Dimensions & Packaging ProTec T1SF-xxx-1+0 Single Unit Weight pounds [grams] ProTec T1SF-xxx-1+0-R Single Unit Weight pounds [grams] Single Unit DIN 43880 Dimension Packaging Dimensions (H x W x L) Standard Order Quantity Plug Internal Configuration Spare Plug inches [mm] Dimensions & Packaging ProTec T1SF-xxx-P Single Unit Weight pounds [grams] Single Unit DIN 43880 Dimension Packaging Dimensions (H x W x L) Standard Order Quantity

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.