RDW1(DW45) Seriesv
14Pages

{{requestButtons}}

Catalog excerpts

RDW1(DW45) Seriesv - 1

RDW1 Series circuit breaker is mainly used in rated service current up to 6300A of distribution networks to distribute electric energy and protect lines. • AC rated current: 630-6300A; • Short-circuit breaking capacity: 80kA-120kA; • Rated working voltage below AC690V; • Both the 3 poles and 4 poles are available; • Two types:Draw-out type and fixed type: • Equipped with many types of intelligent controllers with different functions; • Standards: IEC60947-2. GB14048.2. Operation Conditions • When the ambient air temperature is -5°C to +40°C. the mean value is no greater than +35"C within 24 hours. • Altitude: not higher than 2000m for the installation site. • When the ambient air temperature is +40°C. the relative humidity of the air shall not be higher than 50%; a higher relative humidity is allowed at a lower temperature; for example, for the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature averaged in that month +20°C. and special measures shall be taken for the condensation occasionally produced due to temperature change. • Pollution grade: Class 3. • The installation category of the breaker's main circuit is IV and the control circuit and auxiliary circuit being III. • The circuit breaker should be installed according to the manual.The vertical tilt angle should not exceed 5°. • If the air circuit breaker is installed in a small compartment of the switch board, the protection grade is up to IP40.

Open the catalog to page 1
RDW1(DW45) Seriesv - 2

Provide Professional Low-Voltage Distribution Solutions a. Intelligent controller types: H type (communication type), M type (standard type), L type (economic type), 2M type (high immunity type) and 2H type (high immunity communication type): b.lt have overload long time-delay, short circuit short time-delay and short circuit instantaneous functions; c.single-phase earthing fault protection; d. Display function: setting current display, action current display and each phase voltage display (the voltage display should be informed when ordering); e.Alarm function: overload alarm; f.Self...

Open the catalog to page 2
RDW1(DW45) Seriesv - 3

Intelligent Frame Type Universal Breaker ^ RDW1(DW45) Seriesv Main Technical Parameters Note:The capacity-reducing factor is 0.9 for above 2500A.The 4000A of 6000A is not reducing capacity.

Open the catalog to page 3
RDW1(DW45) Seriesv - 4

Provide Professional Low-Voltage Distribution Solutions Energy storage handle Energy storage indication Panel Inlet and outlet device Position indicator Shake hand knob

Open the catalog to page 4
RDW1(DW45) Seriesv - 5

RDW1(DW45) Seriesv Connection Terminals Circuit breaker have total 47 terminals.The connection diagram refer to Pic.A, Pic.B and Pic.C. #1, #2 AC AC working power supply inputflnput from DC power module U1 and U2 in AC current) #25, #26 connect with neutral pole or input from current transformer. Note: • If the F, X, M voltage of control power is different, it need connect with different power supply. #35 can be connected with power supply directlyfautomatic energy storage), also can be connected with NC button firstly, then for power supply (manual energy storage). • #6-#7 NC contact...

Open the catalog to page 5
RDW1(DW45) Seriesv - 6

Provide Professional Low-Voltage Distribution Solutions RDW1(DW45) Seriesv • Other connection of intelligent controller #1 #2 AC working power supply input (Input from DC power module U1 and U2 in AC current) #12 overload alarm #14 Instantaneous short time-delay output #15 long time-delay output #16 earthing fault output #19 public line output #20 self-checking output #21 tripping output #25, #26 connect with neutral pole or input from current transformer Power (transformer r~J~|— Relay coil —--NO contact (8> - Indicator light Relay connection diagram 1)The controller output drives relay J...

Open the catalog to page 6
RDW1(DW45) Seriesv - 7

RDW1(DW45) Seriesv Note: • If the F, X, M voltage of control power is different, it need connect with different power supply. • #35 can be connected with power supply directly(automatic energy storage), also can be connected with NC button firstly, then for power supply (manual energy storage). • #6-#7 NC contact output (user provide accessories) • User provide additional accessories, o When the controller working power supply is DC current, it need add DC power module.(#1 and #2 terminals cannot be connected with AC power supply).The secondary diagram refer to picture (DC110V or 220V input...

Open the catalog to page 7
RDW1(DW45) Seriesv - 8

wide Professional Low-Voltage Distribution Solutions Note: • If the F, X, M voltage of control power is different, it need connect with different power supply. • #35 can be connected with power supply directly(automatic energy storage), also can be connected with NC button firstly, then for power supply (manual energy storage). • #6-#7 NC contact output (user provide accessories) • User provide additional accessories. When the controller working power supply is DC current, it need add DC power module.(#1 and #2 terminals cannot be connected with AC power supply).The secondary diagram refer...

Open the catalog to page 8
RDW1(DW45) Seriesv - 9

RDW1(DW45) Seriesv Overall And Mounting Dimensions (mm) • Fixed type circuit breaker mounting and overall dimensions (RDW1-3200) • Draw-out circuit breaker mounting and overall dimensions (RDW1-2000)

Open the catalog to page 9
RDW1(DW45) Seriesv - 10

rofessional Low-Voltage Distribution Solutions RDW1(DW45) Seriesv Overall And Mounting Dimensions (mm) • Draw-out circuit breaker mounting and overall dimensions (RDW1-3200) HofBOfMl ccrooctOn • Draw-out circuit breaker mounting and overall dimensions (RDW1-4000, 5000/3Poles)

Open the catalog to page 10
RDW1(DW45) Seriesv - 11

RDW1(DW45) Seriesv Overall And Mounting Dimensions (mm) • Draw-out circuit breaker mounting and overall dimensions (RDW1-4000, 5000A/4P) Note: From panel center to circuit breaker center is 206.5 • Draw-out circuit breaker mounting and overall dimensions (RDW1-6300, 6300A/4ln=4000A, 5000A) Note: From panel center to circuit breaker center is 189(3P), 246.5(4P)

Open the catalog to page 11
RDW1(DW45) Seriesv - 12

rofessional Low-Voltage Distribution Solutions RDW1(DW45) Seriesv Overall And Mounting Dimensions (mm) • Draw-out circuit breaker mounting and overall dimensions (RDW1-6300 ln=6300A) Note: From panel center to circuit breaker center is 246.5 • Draw-out circuit breaker mounting and overall dimensions (RDW1-6300/4 ln=6300A) Note: From panel center to circuit breaker center is 304

Open the catalog to page 12