Product catalog summary
Overview: The document details R. STAHL safety barriers, specifically Series 9001, 9002, and 9004, which connect intrinsically safe circuits with non-intrinsically safe circuits. These barriers are essential for limiting electrical energy in hazardous areas using Zener diodes, resistors, and fuses.
Specifications: Available in single and dual-channel versions, these barriers occupy only 12 mm of space and are designed for installation in Zone 2 and Division 2 areas. They feature a uniform exchangeable fuse, reducing inventory needs.
Functionality: Safety barriers limit power supply to prevent ignition through sparks or hot surfaces. They include Zener diodes for voltage limitation, resistors for current limitation, and fuses for protection. Some models have additional function blocks like electronic current limitations and amplifiers.
Installation and Grounding: The barriers can be mounted on a 35 mm DIN rail for grounding or grounded individually using the PA terminal. Accessories are available for various mounting options.
Selection Criteria: Selection involves functional and safety considerations, including electrical requirements, voltage polarity, and signal type. Safety criteria focus on maximum voltage, current, power, capacitance, and inductance to ensure compatibility with intrinsically safe apparatus.
Interconnection: When interconnecting barriers, consider potential current and voltage additions. The document provides guidelines for safe interconnection, referencing standards like EN 60079-11 and EN 60079-25.
Maintenance: The barriers feature an exchangeable back-up fuse, allowing easy replacement without dismounting, minimizing the need for spare parts.
Applications: Applications include use with transmitters, converters, sensors, and detection systems, compatible with HART and other protocols.
Analog Output Safety Barriers: Used for i/p converters with field circuits grounded or floating. Operating voltage ranges from +20 V to +35 V, with a current of 0 to 22 mA. Safety values include a maximum voltage Uo up to 28 V, current Io up to 121 mA, and power Po up to 770 mW.
Digital Input Safety Barriers: Suitable for driving relays or digital inputs with field circuits grounded. Operating voltage from +20 V to +35 V, with a current of 40 mA. Safety values include a maximum voltage Uo up to 25.2 V, current Io up to 60 mA, and power Po up to 378 mW.
Digital Output Safety Barriers: Used for solenoid valves and LEDs with field circuits grounded or floating. Operating voltage from +20 V to +35 V, with specific open circuit output voltages. Safety values include a maximum voltage Uo up to 25.2 V, current Io up to 121 mA, and power Po up to 760 mW.
Thermocouples and AC-Sensors: For thermocouples and AC-sensors with floating field circuits. Maximum end-to-end resistance of 2 x 82.1 Ω. Safety values include a maximum voltage Uo of 9.3 V and current Io of 300 mA.
Pt100 Connections: For 2-wire, 3-wire, and 4-wire Pt100 connections with floating field circuits. Operating voltage of 1.4 V, with specific measurement ranges. Safety values include a maximum voltage Uo up to 10.9 V and current Io up to 450 mA.
Strain Gauge Load Cells: For 350 Ω or 700 Ω load cells with 6-wire connections. Operating voltage up to ±16 V, with specific voltage and current for load cells. Safety values include a maximum voltage Uo up to 19.9 V and current Io up to 330 mA.
Vibration Sensors: For use with Bentley Nevada or Metrix displacement sensors. Operating voltage of -24 V with an end-to-end resistance of 358 Ω. Safety values include a maximum voltage Uo of 26 V and current Io of 138 mA.
Conclusion: The document provides detailed specifications and safety parameters for various safety barriers, ensuring safe operation in hazardous and safe areas. Each barrier is tailored for specific applications, with defined nominal and safety values to guide installation and usage.
See more

Catalog excerpts

Safety Barriers-1

2 Safety Barriers Safety Barriers Series 9001, 9002, 9004 ● Complete product range for all standard applications ● Flexible and space saving single and dual channel versions on 12 mm only ● Reduced inventory due to uniform exchangeable fuse ● Installation in Zone 2 and Division 2 possible 09964E00 Safety barriers are used to connect intrinsically safe (Ex i) circuits with non-intrinsically safe circuits. The barriers limit the electrical energy towards the hazardous area by means of a combination of Zener diodes, resistors and fuses. Safety barriers featuring an extremely broad application area. 2/1 Automation 18.11.2009

 Open the catalog to page 1
Safety Barriers-2

2 Safety Barriers Series 9001, 9002, 9004 Advantages at a Glance: If single or dual channel, the safety barriers offer a low cost and space saving solution on 12 mm foot print. The transparent cover offers sufficient space for labeling. 04102E00 Snapping-on mounts the barrier mechanically, it simultaneously establishes the PE connection. Therefore only one common PE connection is needed per DIN rail. Time and energy-intensive wiring is dispensed with, however, manual wiring is still an installation option. Even if other rails are used, adapters guarantee that the safety barriers possess a high...

 Open the catalog to page 2
Safety Barriers-3

2 Safety Barriers Series 9001, 9002, 9004 Introduction Application Safety barriers are used as economical interfaces without galvanic isolation between intrinsically safe and non-intrinsically safe circuits. They protect circuits (i. e. cable and apparatus) in hazardous locations. Safety barriers are so-called associated apparatus: Since they also contain non-intrinsically circuits they must either be installed in the safe area or if certified in Zone 2 / Division 2. The combination with an further type of explosion protection (e.g. flame proof enclosure) enables the installation in Zone 1. Hazardous...

 Open the catalog to page 3
Safety Barriers-4

2 Safety Barriers Series 9001, 9002, 9004 Selection Criteria - Function and Safety Selection of safety barriers is generally carried out in two steps: • Functional consideration • Safety consideration 1. Functional consideration Safety barriers are first selected according to their electrical requirements. It is therefore necessary to know the electrical data of the connected apparatus. Further selection criteria: • Polarity of the voltage at the safety barrier UN (+, -, ~) in reference to ¿/PA • Voltage UN • Max. permissible voltage drop across the barrier, caused by the line resistance RL and...

 Open the catalog to page 4
Safety Barriers-5

2 Safety Barriers Series 9001, 9002, 9004 Selection Criteria - Function and Safety 2. Safety consideration The safe maximum values of an individual safety barrier (single- or dual-channel) are determined by the certification: • Maximum voltage Uo • Maximum current Io • Maximum power Po • Maximum permissible capacity Co • Maximum permissible inductance Lo It is to be tested however, if the permissible safe maximum values of the intrinsically safe apparatus (field apparatus in the hazardous area) are maintained by the selected safety barrier. 09938E02 Interconnection of Safety Barriers If several...

 Open the catalog to page 5
Safety Barriers-6

2 Safety Barriers Series 9001, 9002, 9004 Interconnection of Safety Barriers Addition possibilities Example: I = current addition U = voltage addition When interconnecting two safety barriers for alternating potential I + U results, thus a current addition as well as a voltage addition is to be taken into consideration. Polarity - + ~ - I U I and U + U I I and U ~ I and U I and U I and U The EN 60079-11, table A.1 contains the permissible value pairs / combinations of permissible maximum safe values for: • Voltage Uo • Current Io • External capacitance Co The following procedure is to be applied:...

 Open the catalog to page 6
Safety Barriers-7

2 Safety Barriers Series 9001, 9002, 9004 Installation and Grounding R. STAHL safety barriers Series 9001, 9002 and 9004 excel due to an especially simple mounting mechanism. They snap on to a 35 mm DIN rail (NS35/15 to EN 50 022) directly without a mounting attachment. At the same time a conducting connection between ¿ / PA of the barrier and the rail, is established. Grounding several barriers is achieved by connecting the rail with the potential equalisation / grounding system (collective ground). The safety barriers can alternatively be grounded individually as well by using the ¿ / PA terminal...

 Open the catalog to page 7
Safety Barriers-8

2 Safety Barriers Series 9001, 9002, 9004 Exchangeable Back-up Fuse All safety barriers Series 9001, 9002 and 9004 have an exchangeable back-up fuse. Dual-channel safety barriers have a back-up fuse per channel. This fuse backs up the internal, non-accessible fuse. A protective circuit prevents tripping of both fuses at the same time. It is thus ensured that the safety barrier is protected against destruction resulting from reverse polarity of the operating voltage or excessively high operation voltages. Two advantages are essential for maintenance and repair: • in case of overload the safety...

 Open the catalog to page 8
Safety Barriers-9

2 Safety Barriers Series 9001, 9002, 9004 Overview application Safety Barrieres Symbol Application 2-, 3-wire transmitter INTRINSPAK Type 9002/13-280-110-001 9001/51-280-091-141 06861E00 2-wire transmitter HART 9002/13-280-110-001 9001/51-280-091-141 06329E00 4-wire transmitter, current source Field circuit floating 9002/34-280-000-001 4-wire transmitter HART Field circuit floating 9002/34-280-000-001 07648E00 07649E00 i/p converter, control valve, indicator Field circuit grounded 9001/01-280-110-101 9002/13-280-110-001 07650E00 i/p converter, HART control valve Field circuit grounded 9001/01-280-110-101...

 Open the catalog to page 9
Safety Barriers-10

Safety Barriers Series 9001, 9002, 9004 Overview application Safety Barrieres Thermocouple, mV signals Field circuit floating 9002/77-093-300-001 06332E00 Resistance thermometer (RTD), Potentiometer Pt100, 2-wire connection Field circuit floating Pt100, 3-wire connection Field circuit floating Pt100, 4-wire connection Field circuit floating 9002/22-032-300-111 9002/22-032-300-111 9002/22-032-300-111 9002/77-093-040-001 06331E00 Strain gauge load cells 350 O or 700 O 6-wire ± 7.5 V (15 V) Field circuit floating 9002/10-187-270-001 9002/10-187-020-001 9002/77-093-040-001 350 O 6-wire + 10 V Field...

 Open the catalog to page 10

All R. STAHL AG catalogs and technical brochures

  1. CATALOGUE 2018

    1094  Pages

  2. Ex-Poster

    1  Page

  3. AK00_III

    12  Pages

  4. EN/IEC 61439

    4  Pages

  5. Focus customer

    24  Pages

  6. SERIES 200

    8  Pages

  7. HMI Oil and Gas

    20  Pages

  8. HMI Overview

    36  Pages

  9. SolConeX

    12  Pages

  10. GUBox

    4  Pages

  11. EXLUX 6001

    4  Pages

  12. AK00_III

    5  Pages

  13. IS1+Remote I/O

    16  Pages

  14. Lighting

    16  Pages

  15. Stahl - Catalog

    1306  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.