Buffering with electrolytic capacitors instead of lead batteries Buffering of 48V loads Minimum hold-up time 0.1s at 20A and 0.2s at 10A Longer hold-up time at lower loads Clear status indication by status LED and signaling terminals Quick-connect spring-clamp terminals 3 Year warranty The buffer unit is a supplementary device for regulated DC48V power supplies. It buffers load currents during typical mains faults and load peaks. Rated voltage Voltage range Output voltage Working principle In times when the power DC supply provides sufficient Discharge voltages, the buffer unit stores energy in integrated electrolytic capacitors. In case of mains voltage fault, this energy is released again in a regulated process. Bridges mains faults without interruption Statistic show that 80% of DC all mains fault lasts less Buffer Unit than 0.2s. These mains faults are completely bridged by the buffer unit. This increases the reliability of the system as a whole. Extended hold-up time Buffer mode select with jumper Charging current Charging time Input current Power dissipation Temperature range Dimensions standby mode standby mode operational WxHxD Once mains power fails or DC is switched off, the buffer Buffer Unit unit will continue to provide the load current for a defined period of time. Process data can be saved and processes can be terminated before the DC power switches off. Controlled restarts are subsequently possible. 3. ORDER NUMBERS Buffer Unit Accessory Output current Hold-up time Easy to handle, expandable and maintanance-free The buffer unit does not require Power Buffer any control wiring. It can be AC Supply Unit(s) added parallel to the load circuit at any given point. Buffer units DC can be switched in parallel to increase the output ampacity or the hold-up time. 4. MARKINGS 48V, 20A, 100ms Wall mounting bracket Side mounting bracket Mating connector, Part of derlivery May 2013 / Rev. 1.2 / DS-UF20.481-EN All parameters are specified at 48V, 10A, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0
Open the catalog to page 1May 2013 / Rev. 1.2 / DS-UF20.481-EN All parameters are specified at 48V, 10A, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0
Open the catalog to page 2INSTALLATION NOTES Mounting Orientation: The power terminal shall be located on top of the unit. Cooling Convection cooled, no forced air cooling required. Do not obstruct air flow! Installation clearances: Recommended installation clearances: 40mm on top of the unit, 20mm on the bottom of the unit, 0mm (or 15mm in case the adjacent device is a heat source) on the left and right side of the unit Intended use This buffer unit has been designed for use in panel board installations or other building-in applications where a suitable mechanical enclosure shall be provided to fulfil local requirements....
Open the catalog to page 35. STANDBY MODE Input voltage Voltage range Input current Power dissipation Status lamp Active signal Ready signal DC 48V 48-56Vdc 40mA 1.9W permanent on high ohmic low ohmic Charging mode Charging mode 32s / 25s flashes 1.25Hz high ohmic high ohmic 6. CHARGING MODE Input current Charging time Status lamp Active signal Ready signal 1) Initial charging is the first charge after voltage is applied to the buffer unit. 2) Re-charging is the charging of the internal capacitors after voltage interruptions shorter than 2minutes. Fig. 6-1 Buffer charging time, 48V Charge May 2013 / Rev. 1.2 / DS-UF20.481-EN...
Open the catalog to page 47. BUFFER MODE Rated output current Current limitation Output voltage Ripple and noise voltage Hold-up time Activation threshold Status lamp Active signal Ready signal Electronically limited Jumper in position “45V fixed” Jumper in position “Vin –2V” 5A, 20Hz to 20MHz, 50Ohm 10A, 20Hz to 20MHz, 50Ohm 20A, 20Hz to 20MHz, 50Ohm may increase below –10°C min. 0.1s 45V, 20A typ. 0.15s 45V, 20A min. 13.4s 45V, 0.1A typ. 21s 45V, 0.1A To increase buffer current or extend hold-up time any given number of buffer units can be put in parallel typ. 45V Jumper in position “45V fixed” Buffering starts if terminal...
Open the catalog to page 5May 2013 / Rev. 1.2 / DS-UF20.481-EN All parameters are specified at 48V, 10A, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0
Open the catalog to page 68. FUNCTIONAL DIAGRAM Fig. 8-1 Functional diagram Status lamp Buffer Capacitor Charger & Inrush Limiter Safety and OverVoltage Protection ReversePolarity Protection Buffer Capacitor Shut-Down Buffer Capacitor Discharger Buffer Capacitor Chassis Ground Input / Output Voltage Monitor Back-up Level Selector Ready Monitor Active Monitor 9. FRONT SIDE AND USER ELEMENTS Fig. 9-1 I/O Power Port Quick-connect spring-clamp terminals, + Positive terminal - Negative terminal Chassis Ground to bond the housing Back-up threshold jumper 1-2: Variable mode Unit switches to buffer mode when terminal voltage...
Open the catalog to page 710. OPERATING DIAGRAM Fig. 10-1 Operating diagram V Mains Fig. 10-2 Signals schematic Hold-up Time Power Supply t Optocoupler high ohmic Optocoupler high ohmic Charging Mode Buffer Mode 11. ACTIVE AND READY SIGNAL, INHIBIT INPUT Active signal (Pin 7) Signal voltage Signal current Voltage drop across opto-coupler Leakage current Isolation Ready signal (Pin 8) Signal voltage Signal current Voltage drop across opto-coupler Leakage current Isolation Inhibit input (Pin 9) Signal voltage Signal current Shut-down threshold Isolation low ohmic while buffer capacitors are discharging 60Vdc 6mA 1.2V /...
Open the catalog to page 812. TERMINALS AND WIRING Power terminal Type Solid wire Stranded wire AWG Ferrules Pull-out force Wire stripping length Bi-stable, quick-connect spring clamp terminals. IP20 Finger-safe construction. Suitable for field- and factory installation. Shipped in open position. 0.5-6mm2 0.5-4mm2 20-10AWG Allowed, but not required 10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (according to UL486E) 10mm / 0.4inch Fig. 12-1 Connecting a wire Use appropriate copper cables, that are designed for an operating temperature of 60°C Follow national installation codes and regulations! Ensure that all strands of a...
Open the catalog to page 918 Pages
18 Pages
28 Pages
29 Pages
21 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
4 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
23 Pages
2 Pages
20 Pages
2 Pages
2 Pages
2 Pages
20 Pages
23 Pages
2 Pages
2 Pages
2 Pages
2 Pages
23 Pages
23 Pages
22 Pages
19 Pages
17 Pages
17 Pages
19 Pages
19 Pages
19 Pages
20 Pages
20 Pages
20 Pages
20 Pages
20 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
3 Pages
2 Pages
2 Pages
3 Pages
11 Pages
2 Pages
9 Pages
8 Pages
9 Pages
23 Pages
23 Pages
24 Pages
21 Pages
23 Pages
28 Pages
28 Pages
23 Pages
23 Pages
23 Pages
23 Pages
22 Pages
27 Pages
27 Pages
28 Pages
28 Pages
25 Pages
25 Pages
25 Pages
26 Pages
26 Pages
26 Pages
27 Pages
22 Pages
26 Pages
21 Pages
26 Pages
26 Pages
25 Pages
19 Pages
23 Pages
23 Pages
23 Pages
23 Pages
23 Pages
23 Pages
23 Pages
23 Pages
21 Pages
21 Pages
14 Pages
22 Pages
22 Pages
21 Pages
21 Pages
20 Pages
21 Pages
19 Pages
19 Pages
20 Pages
20 Pages
20 Pages
19 Pages
20 Pages
20 Pages
20 Pages
21 Pages
26 Pages
26 Pages
27 Pages
22 Pages
22 Pages
23 Pages
21 Pages
22 Pages
22 Pages
21 Pages
20 Pages
27 Pages
28 Pages
31 Pages
9 Pages
9 Pages
9 Pages
9 Pages
27 Pages
27 Pages
17 Pages
18 Pages
2 Pages
2 Pages
2 Pages
2 Pages
32 Pages
35 Pages
26 Pages
28 Pages
27 Pages
27 Pages
25 Pages
31 Pages
9 Pages
2 Pages
7 Pages
17 Pages
17 Pages
4 Pages
4 Pages
4 Pages
4 Pages
4 Pages
2 Pages
2 Pages
2 Pages
2 Pages
2 Pages
4 Pages
2 Pages
23 Pages
23 Pages
23 Pages
22 Pages
21 Pages
19 Pages
26 Pages
5 Pages
1 Page
25 Pages
25 Pages
19 Pages
28 Pages
25 Pages
25 Pages
25 Pages
25 Pages
22 Pages
21 Pages
28 Pages
34 Pages