Water Treatment and Water Disinfection 2016 - 156 Pages

Add to MyDirectIndustry favorites
Water Treatment and Water Disinfection 2016

Catalog excerpts

Water treatment and water disinfection

 Open the catalog to page 1

ProMinent GmbH Technical changes reserved. All previous catalogues and price lists are superseded with the release of this product catalogue. You can view our general terms and conditions on our homepage.

 Open the catalog to page 2

Product Catalogue Volume 4 1.0.1www.prominent.com Product Catalogue Volume 4 Water Treatment and Water Disinfection A clear case of disinfection Hygienically pure water is one of the greatest challenges of our time. With ProMaqua® products and systems - combined with our many years of practical experience - we have developed application-based solutions for a range of different industries. They are characterised by their outstanding handling of natural resources, minimal operating costs and maximum efficiency. Chapter 1 offers UV systems for the gentle and chemical-free disinfection of...

 Open the catalog to page 3

New Products Water Treatment and Water Disinfection New Products Water Treatment and Water Disinfection 1.0.1www.prominent.com UV Systems Dulcodes LP Flow up to 523 m³/h P_PMA_DS_0028 A world first – the Dulcodes LP: precise lamp dimming in seconds – even with rapidly changing flows and temperature conditions Our patented Vario-Flux high-output lamps with active temperature management are used in the Dulcodes LP. Thanks to the unique combination of electronic ballast technology and the Vario-Flux lamps, they can be dimmed quickly and precisely over a broad range of up to 50% of the nominal...

 Open the catalog to page 5

Water treatment and water disinfection page 1.1 General Notes on UV Treatment 1-1 1.1.1 Applications of Dulcodes UV Systems 1-1 1.1.2 Description of Dulcodes UV Systems 1-2 1.2 Performance Overview of Dulcodes UV Systems 1-4 1.2.1 Notes on Planning and Designing an UV System 1-5 1.3 Questionnaire for Designing an UV System 1-6 1.4 UV System Dulcodes LP Stainless Steel 1-7 1.5 UV System Dulcodes LP-PE Plastic 1-9 1.9 Accessories for Dulcodes UV Systems 1-17 Ozone Systems OZONFILT® 2-1 2.1 Ozone In Water Treatment 2-1 2.2 Performance Overview of Ozone Systems 2-2 2.3 Questionnaire on the...

 Open the catalog to page 7

Contents Water treatment and water disinfection 3.8 PE/PP Storage Tank and Equipment Construction PE Storage Tank With General WHG Approval 5.2.1 Our standard equipped storage tanks and collecting pans with approval marks 5.2.2 Accessories Meeting The Requirements Of WHG § 19 and VAwS (Directive On Systems For Storage And Handling Of Water-Endangering Substances) 5.2.3 Other Accessories PP/PE Storage Tanks, Custom-built Polymer Batching and Metering Systems Ultromat® 6.1 Electrolysis Systems CHLORINSITU® Performance Overview Questionnaire on the Design of an Electrolysis System Electrolysis...

 Open the catalog to page 8

Water treatment and water disinfection page 7.6 Ultrafiltration System Dulcoclean® UF 7-10 7.6.1 Ultrafiltration Systems Dulcoclean® UF 7-10 7.7 Reverse Osmosis System Dulcosmose® 7-11 7.7.1 Reverse Osmosis System Dulcosmose® ecoPRO 7-11 7.7.2 Reverse Osmosis System Dulcosmose® TW 7-14 7.7.3 Reverse Osmosis System Dulcosmose® BW 7-16 7.7.4 Reverse Osmosis System Dulcosmose® SW 7-18 8 Gravity Filter INTERFILT® SK 8-1 8.1 Sand Filter INTERFILT® SK 8-1

 Open the catalog to page 9

UV Systems Dulcodes 1.0.1Product Catalogue 2016 General Notes on UV Treatment 1UV Systems Dulcodes Disinfection is a key stage in modern water treatment. UV disinfection is used to an ever increasing extent, as a safe, chemical-free and reliable disinfection process. Extensive research projects and numerous trouble-free operational systems prove the safety and reliability of UV disinfection. With UV disinfection, the water to be disinfected is irradiated with ultraviolet light, which involves a purely physical, chemical-free process for water disinfection. UV-C radiation in particular, with...

 Open the catalog to page 11

UV Systems Dulcodes Description of Dulcodes UV Systems Dulcodes UV disinfection systems essentially consist of: ࡯ ࡯ ࡯ ࡯ ࡯ High-quality reactor made of stainless steel (DIN 1.4404) or UV-resistant plastic Lamp protection tubes made of high-quality quartz, easily removable for cleaning purposes Lamps with an exceptionally high UV output in the 254 nm range Highly selective UV sensors with good long-term and temperature stability UV system controllers and modern electronic ballasts fitted in a control cabinet The special features of our Dulcodes UV disinfection systems are: ࡯ Uniform UV dose...

 Open the catalog to page 12

UV Systems Dulcodes Dulcodes UV Controllers Compact controller Compact unit for the control of all functions of the UV system. The control can be selected for single lamp systems of the Dulcodes LP product range. The display alternately shows the current UV-intensity, the operating hours and the number of lamp activations. The compact controller informs the operator if values fall below freely programmable safety and warning thresholds. Different functions, such as start rinsing, interval rinsing, stagnation rinsing and post-burning time can be freely set on demand. The control has the...

 Open the catalog to page 13

1.2 Performance Overview of Dulcodes UV Systems ProMinent offers a wide range of UV systems for the most diverse applications. The following overview shows the capacity and main applications of our standard systems: Type LP: Low-pressure systems Type MP: Medium-pressure systems ProMinent provides all the advice needed for the safe operation of a Dulcodes UV system: ■ Evaluation of the situation on site by trained, expert field sales staff. ■ We can measure all key water parameters required for optimum system design in our water laboratory. ■ Project planning of the system. ■ Commissioning...

 Open the catalog to page 14

Notes on Planning and Designing an UV System ࡯ The system should always be designed for the maximum water flow. ࡯ The system should always be designed for the worst anticipated UV transmission. ࡯ Fireproof sampling cocks for microbiological tests should be provided upstream and downstream of UV disinfection systems. ࡯ A manual shut-off valve should be provided before the UV system to isolate the system for maintenance work. ࡯ With potable water disinfection and similar applications, an electrically-controlled shut-off valve should be provided downstream of the UV disinfection system, which...