OCS-260 180…220W DC/AC SINE WAVE INVERTER GENERAL FEATURES: Sine wave output voltage Selectable output frequency: 50/60Hz Adjustable output voltage Output failure alarm Remote inhibit High input-output isolation 3000Vrms Optional railway version EN50155 Fire and smoke: EN45545-2 approved : Startup voltage ≤10.2V. Under-voltage shutdown ≤ 9.1V Specifications are subject to change without notice. These products are not intended for use as critical components in life support or n
Open the catalog to page 1
INPUT Input voltage range Maximum input ripple OUTPUT Nominal output voltage (Vonom) Adjust range Load regulation Line regulation 0.4% @ ΔVin -20…+25% 10% @ ΔVin -30…+25% 1% @ ΔVin -10…+25% for 12V input models 10% @ ΔVin -20…+25% for 12V input models Output frequency Output wave distortion THD Output voltage HF ripple ENVIRONMENTAL Storage temperature Operating temperature (full load) Operating temperature (62.5% load) Natural convection Emissions according SAFETY Safety according to EN60950-1, EN62368-1 Class I OV category II, Pollution degree 2 Input / output isolation: reinforced...
Open the catalog to page 2
OCS-260 180…220W DC/AC ORDERING CODES Input Voltage DC [V] Input voltage range [V] Max. Output Output Input voltage current Current AC [A] [V] [A] Active output power [W] Appar. output power [VA] Output Peak curr. 10ms [A] No load input current [A] OCS–260–70_ _–_ _ T Railway (Optional) B Connector DIN41612H15 D Spring clamp terminals Model number Accessories must be ordered in a separated order line www.premiumpsu.com Powering Your Challenge
Open the catalog to page 3
BLOCKS DIAGRAM DESCRIPTION The OCS-260 consists of sine-wave 120Vac or 230Vac output voltage DC-AC converters. The frequency can be set to 50Hz or 60 Hz, and input and output are galvanically isolated. The OCS-260 inverters consist of two cascaded converters, one DC-DC generating an intermediate output voltage from the input voltage. That intermediate voltage is inverted to supply the output voltage and frequency by means of a second DC/AC converter. The input is protected against reverse polarity by means of fuse and against under-voltage by unit shutdown. The output has protection of...
Open the catalog to page 4
POWER DERATING vs AMBIENT TEMPERATURE INSTALLATION There are two connecting options: spring clamp terminal strip and DIN-41612-H15 connector. The product can be mounted in several ways: On a chassis by means of the 4 corner holes. In EUROCARD racks. For this application there is a standard 10Te front plate accessory NP-9289 With the mounting base NP-9125. This accessory can be mounted on a chassis or in DIN rail adding the clip accessory NP-9135. Make connections as shown in the CONNECTIONS table. The default output frequency is 50Hz. For 60Hz simply actuate the dip-switch as...
Open the catalog to page 5
ACCESSORIES ACCESSORIES Front plate 19’’ subrack (3U 10TE) Screws and LED light guide included Mounting base Screws included Screws included www.premiumpsu.com Powering Your Challenge
Open the catalog to page 6
EU DECLARATION OF CONFORMITY The undersigned, representing the following: Manufacturer: Address: PREMIUM, S. A., C/. Dolors Aleu 19-21, 08908 L’Hospitalet de Llobregat, SPAIN herewith declares that the product: Type: Models: is in conformity with the provisions of the following EU directive(s): 2014/35/EU Electromagnetic compatibility Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS) and that standards and/or technical specifications referenced overleaf have been applied: EN 60950: 2005 Safety (Information technology equipment) Safety....
Open the catalog to page 7
ANNEXE Applicable values for the different sections of the norm EN50155: 2017 4.3.1 Working altitude Ambient temperature Switch-on extended operating temp. Rapid temperature variations Shocks and vibrations load load load load < 100% < 100% (Without connectors handling) <50% <50% (Without Connectors handling) ST1 H1 According EN61373:2010 Category 1 class B Test Radiated emissions Conducted emissions Limits 40dB(µV/m) Qpk at 10m 47dB(µV/m) Qpk at 10m Do not apply Internal freq. < 108MHz 79dB(µV) Qpk, 66dB(µV) Av 73dB(µV) Qpk, 60dB(µV) Av Input Output Signal PE Input L to L Input L to PE...