1. Catalogs
  2. Powerbox
  3. ENI100 Series

ENI100 Series

ENI100 Series

ENI100 Series

Product catalog summary
Specifications:
- Input: Nominal range 100-240VAC, voltage range 90-264VAC, frequency 50/60Hz, inrush current max 50A peak, input current 2A, crimped terminal connector, 3-wire 0.5m cable, leakage current <100µA, isolation class I.
- Output: Power up to 96W continuous, 12VDC version limited to 80% power at 100-120VAC, voltage preset non-adjustable, tolerance 5%, ripple and noise typ. 1% p-p max, efficiency 87-90% at 230VAC full load, hold up time 35ms, start up time <2s, line regulation 1% max, load regulation 2% max, overcurrent protection approx 125%, constant current limiting, overtemperature and overvoltage protection, transient response 4ms max, temperature coefficient typ. 0.04%/°C, 0.5mm2 output cable, crimped terminal connector.

Environmental:
- Operating temperature 0°C to +40°C, 70°C with derating, storage temperature –40°C to +75°C, humidity 5% to 95% non-condensing, derating requires mounting on a metal plate 500x500mm, RoHS compliant.

General:
- Switching frequency 40-80kHz, max weight 400g, MTBF >270,000 hours at 25°C, lifetime prediction min 80,000 hours at 25°C, 230VAC at 70% load.

Standards:
- IP54 protection, fulfills IEC 60950-1, designed to meet UL508, EMC standards IEC60601-1-2, IEC61204-3, EN55011 class B, harmonic emissions IEC61000-3-2, voltage flicker IEC61000-3-3, ESD susceptibility IEC61000-4-2, radiated susceptibility IEC61000-4-3, EFT/Burst IEC61000-4-4, surge IEC61000-4-5, conducted susceptibility IEC61000-4-6, magnetic field IEC61000-4-8, dips and interruptions IEC61000-4-11.

Derating Curve:
- Requires mounting to a heat sink (500x500x2mm) for optimal performance.

Powerbox Output:
- Part No ENI 100 5135: 12VDC, 8A, 96W
- Part No ENI 100 5138: 24VDC, 4A, 96W
- Output load percentages and input voltage derating curve provided.
See more

Catalog excerpts

ENI100 Series-1

Input Nominal input range 100-240VAC. Voltage range 90-264VAC, see derating curve. Inrush current Max 50A peak, cold start. Input connector Crimped terminal. Isolation class Class I, double isolation between input and output. Power consumption Zero load Approx 0,3 Watts at 110 VAC input. Output Power Up to 96W, continuous at 100-240VAC input, see table. 12VDC version limited to 80% output power at input voltage 100-120 VAC. Voltage See table. Factory preset non adjustable. Ripple and noise Typ. 1% p-p max (20MHz BW). 5% at <110VAC input. Efficiency 87-90% @ 230VAC full load. Line regulation 1% max full load. 5% at <100VAC input. Load regulation 2% max @ 230VAC, 10-90% load change at output terminal. Overcurrent protection Approx 125%, auto recovery. Current limiting charact. Constant current. Overtemp. protection Yes, auto recovery. Overvoltage protection Yes. Transient response 4ms max. Temperature coefficient Typ. 0.04%/°C of Uo. Output cable 0.5mm2, length 0.7m. Output cable polarisationCable identificaiton ”1” = PLUS Cable identification ”2” = MINUS Output connector Crimped terminal. Environmental Operating temperature 0°C to +40°C, 70°C with derating. Storage temperature -40°C to +75°C. mounted on a metal plate or wall of minimum size 500x500mm thickness min 2mm. If used without equal cooling the output power shall be derated to 80% for the 24V version and 70% for the 12V version. RoHS Unit complies with RoHS. POWERBOX ndustrial Line ENI100 Series 100W Single Output Potted AC/DC Power Supply Dimensions See drawing. MTBF >270,000 hours at 25°C ambient temperature, 50 years power on. Lifetime prediction Min 80,000 hours at 25°C, 230VAC at 70% load. Standards IP protection Designed to meet IP54. Safety standards Fulfills IEC 60950-1. Designed to meet UL508. Safety markings TBD. CB certificate according to EN60950-1, ESD susceptibility IEC61000-4-2, ±6kV contact discharge, Surge IEC61000-4-5, ±2kV common mode, ±1kV differential mode. Conducted susceptibility IEC61000-4-6, 3V/m. Dips and interruptions IEC61000-4-11, 30% 500ms, 60% 100ms, 95% 5sec. Performance criteria A A1 B. * at 100-160 VAC nominal input voltage performance criteria B Powerbox Output Continuous Continuous Part No Voltage Output Current1) Output Power1) Attached to a metal plate 500x500 mm thickness min 2mm.

 Open the catalog to page 1
ENI100 Series-2

POWERBOX Industrial Line ENI100 Series 100W Single Output Potted AC/DC Power Supply

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.