S40A Protection Relay Test Set - 2

S40A Protection Relay Test Set S40A is a type of 3‐phase protection relay test set, with 3×40A, 3×300V, and a local control system. It is a portable and economic secondary injection tester, and easy to use. This 3‐phase protection relay testing set can apply to the testing not only on operating value and operating time of AC/DC relays, but also on complex voltage blocking directional over‐current, zero sequence over‐current, low‐frequency load shedding and other protection functions of low voltage line micro‐processor based protection and whole group transmission of high voltage line...

Open the catalog to page 2
S40A Protection Relay Test Set - 3

S40A Protection Relay Test Set S40A Panels  Front Panel Short‐cut key for test module ‐ Manual, Ramp, Distance, Time, others and df/dt LED indication‐Overheat, Overload, Ia/Ib/Ic distortion, High power LCD display Trip A, Trip B, Trip C, Reclose indicator Coarse regulation knob USB port Start button Stop button Fine regulation knob Function keys ‐ AC/DC, 200mA, High Power, Menu  Top Panel Current outputs‐3x40A, 1x200mA(low grade) Binary input‐ Trip A, Trip B, Trip C, Reclose Binary

Open the catalog to page 3
S40A Protection Relay Test Set - 4

S40A Protection Relay Test Set  Rear Panel Ventilation Power switch Mains supply connector S40A Local Relay Test Set Software S40A is a type of relay tester controlled by SCM. Colored LCD with local control system makes S40A portable, and easy to use. There are Manual (AC Relays and DC Relays) test modules, Ramp test module, Distance module, Time (AC Time and DC Time) test modules, df/dt(Frequency relays) module, which can test pick‐up value and operating time of AC/DC relays, voltage blocking directional overcurrent, zero sequence overcurrent, frequency function etc. Report Set and View,...

Open the catalog to page 4
S40A Protection Relay Test Set - 5

❖ Can output 3 AC voltages and 3 AC current or 3 DC voltages and 1 DC current ❖ Can manually control amplitude, phase and frequency of AC values and amplitude of DC values by step size ❖ Current range can be 3 phase AC 0-40A, DC 0-10A or 1 phase AC/DC 0-200mA > Distance module ❖ Can make the test of setting value check and recloser time of distance relay ❖ Provide three modes of zero-sequence compensating coefficient, KL, Kr and Kx, Z0/Z1. ❖ Can set transient fault and permanent fault ❖ Fault type includes A-E, B-E, C-E, A-B, B-C, C-A, A-B-C short-circuit ❖ Direction includes forward...

Open the catalog to page 5
S40A Protection Relay Test Set - 6

Nature Fault Type Directional Multiple |Z| Phi Current Mode Magnitude Angle Fault Time Trip Timel 0.512s Reclose Time 1.009s Trip Time2 0.115s ❖ Provide two states ❖ When it enters into the second state, then starts timing ❖ When it get the binary input Ta, Tb, Tc, then get the test of AC and DC relay operating time > df/dt test module (Frequency relays) ❖ Can make the fixed-point test for operating frequency, delay time, df/dt value, voltage blocking value and current blocking value of frequency relay

Open the catalog to page 6
S40A Protection Relay Test Set - 7

❖ After finishing the testing, there is Others key for save on the lower right of LCD. ❖ Press it to save reports in local ❖ Max 21 reports can be saved locally ❖ Report view is results and names of the selected test items will be displayed on the lower of LCD. ❖ There is the USB port to connect with PC to import report from the test set and review. Empty Empty Empty Empty Empty Empty Empty Ramp Empty Empty Empty Empty Empty Empty Empty Empty Empty Empty ❖ Voltage Output Low means max voltage output 100V, Voltage Output High means max voltage output 300V

Open the catalog to page 7
S40A Protection Relay Test Set - 8

S40A Protection Relay Test Set S40A Protection Relay Test Set Specifications Voltage generators Setting range 3‐phase ac(L‐N) 3×0~300V 1‐phase ac(L‐L) 1×0~600V dc (L‐N) 3×0~300V Phase Angle range 0°~+360° Accuracy 0.2° Resolution 0.1° Power 3‐phase ac(L‐N) 3×85VA at 300V 1‐phase ac(L‐L) 1×170VA at 600V (two generators in series) dc (L‐N) 3×100W at ±300 V Accuracy <0.16% rd.+0.04% rg. guar. <0.08% rd.+0.02% rg. typ. Ranges 300V Resolution 10mV Distortion 0.1% Voltage range 24V, 110V, 220V Power 110W at 220V, 55W at 110V, 12W at 24V Binary inputs Number 4 Input characteristics 0~250Vdc or...

Open the catalog to page 8
S40A Protection Relay Test Set - 9

Professional Solution Provider For The Power World Since 2001, Ponovo Power has been focusing on providing professional solutions to over 5000 clients in the fields of intelligent testing and power quality control in China and aboard 9 PONOVO POWER CO., LTD. No.139 Jinghai Third Road, BDA, Beijing, China. 100176 Tel : +86 (10) 59089666 Fax: +86 (10) 59089999 www.ponovo.net info@relaytest.com support@relaytest.com