Digital Relay Test Kit
Open the catalog to page 1PW636i-F Digital Relay Test Kit PW636i-F (6×32A, 4×300V, 8 fiber optic ports) is the new generation of PW series relay test set which can be used both as a conventional relay test kit and IEC61850/IEC61869 testing tools. Other test works, such as transducer, energy meter, indication meter, etc., can also be done easily. It's the ideal test device for all power utilities, power plants, relay manufactures, panel manufactures, research institutes, universities, testing companies, etc. Product Features • In-built monitoring and recording • Large output power • High accuracy • Support GOOSE/SV (IEC61850/IEC61869)...
Open the catalog to page 2PW636i-F Digital Relay Test Kit Application PW636i-F is not only has current and voltage outputs for all kinds of conventional relay testings, but also has 8 switchable optical fiber/Ethernet ports to support digital relay protection tests based on IEC61850/IEC61869. It can send and receive SV, simulate MU to send SV to relay which the dispersion is better than ±80ns, receive SV, realizing self-loop test. It can publish and subscribe GOOSE message, many different kinds control/block messages, simulate the abnormal message (jitter, frame loss, flying spot, wrong sequence, data anomalies, packet...
Open the catalog to page 3PW636i-F Digital Relay Test Kit PW636i-F Panels PW636i-F is designed with fuse on the mains supply and electronic protection for overload on the current (open circuit) or voltage outputs (short circuit), with immediate isolation of the output and alarm indication. Also diagnostic message for the setting of wrong data, mistakes on the input etc. There’s also electronic protection in case of counterfeed of voltage output, if any incorrectness happens, the alarm light shall flash. And Overheat LED indicator shall flash for protection against over-temperature, on all outputs. ▪ Front Panel GPS Antenna...
Open the catalog to page 4Binary input group 1 Binary output group 2 Test functions according to IEEE relay code 32 Directio n a 1 Power Relay 27/27N U nd e rvoltage Relay 68 Blocking or "out of step" Relay
Open the catalog to page 5PowerTest For PW636i-F Digital Relay Test Kit Software PowerTest For PW636i-F is specially designed for PW636i-F digital relay test kit. The application equipment includes intelligent equipment (merging unit, protection relays and intelligent terminals, etc.) and power system automatic equipment based on IEC61850/IEC61869 functions. PowerTest For PW636i-F is a relay test software that includes different test packages, the Basic package, Protection package, Advanced package, Special package, IEC61850 package, New Modules, which packages includes different testing module, that can be used for all...
Open the catalog to page 6❖ 12 voltage and 12 current sources available for test relay ❖ Amplitude and phase angle of voltage and current sources can be controlled independently ❖ Test can be in manual or auto mode QuickTest (VL-L, 3I) ❖ Easy to control the phase-phase voltage, 3V0 (zero sequence voltage) and 3 currents ❖ Amplitude, phase angle and frequency of current sources and phase-phase voltage, zero sequence voltage can be controlled independently ❖ Test can be in manual or auto mode QuickTest (Sequence) ❖ Easy to control the sequence components (positive sequence, negative sequence and zero sequence) for voltage...
Open the catalog to page 7❖ Easy to test impedance relay with constant voltage ❖ Set the fault impedance and fault voltage, obtain the amplitude and phase angle of each phase voltage and current according to the fault type ❖ Can manually or automatic search the relay operation value QuickTest (Z, Zs Const) ❖ Easy to test impedance relay with constant system impedance ❖ Set the fault impedance and system impedance, obtain the amplitude and phase angle of each phase voltage and current according to the fault type ❖ Can manually or automatic search the relay operation value Time ❖ Time module is used to test trip delay time...
Open the catalog to page 8❖ Can generate harmonics for all voltage and current outputs ❖ Can check the 2nd /3rd / 4th /5th harmonic restraint of current differential ❖ Can check the harmonic measurement of the relay up to 31st harmonic ❖ Can set the harmonic for each channel ❖ Can check different types of line protection system, including over current, distance, etc. ❖ Can check the whole relay system, including auto-reclosing and circuit breaker simulate ❖ Can set different fault type ❖ Can do end-to-end test with GPS control > Protection Package In protection package, there are more testing modules for relay's characteristics...
Open the catalog to page 9❖ Can test impedance relay with R-X setting in different ways ❖ Input impedance characteristic to Z plain ❖ Associate the characteristic with relay settings ❖ Select test point directly on Z plain or in setting box Distance (Z-Phi) ■ Can test impedance relay with Z-Phi setting in different ways ❖ Input impedance characteristic to Z plain ❖ Associate the characteristic with relay settings ❖ Select test point directly on Z plain or in setting box Directional ❖ Can test maximum trip angle and two boundary angles (Lead and lag angles) ❖ Can set angle define, V lead I or I lead V ❖ Can set fault type,...
Open the catalog to page 10Time Inversed Current ❖ Used to test time inversed current relay ❖ Can test normal current relay with or without time delay ❖ Can test directional current relay with or without time delay ❖ Can test the inversed current relay with user defined curve ❖ Can import the IEC and IEEE standard curve ❖ Used to test time inversed voltage relay ❖ Include testing directional, time definite and with time delay voltage relay ❖ Can simulate three phase, phase-earth fault, and phase-phase fault ❖ Can test frequency protection relay, such as over frequency, under frequency, df/dt trip, df/dt blocking ❖ Including...
Open the catalog to page 11In the advanced package, the centralization testing the RX Characteristic Sweep, testing for distance relay, Advanced Differential, TransPlay, Synchronization, etc. Advanced Differential (6I) ❖ Can search the percentage restraint curve, harmonic restraint, trip time ❖ Can automatic to calculate the matching factor via the transformer parameter and CT/PT parameter ❖ Can test single phase, phase-phase, three-phase fault ❖ Can search the characteristic boundary of the impedance relay ❖ Can find the boundary at different angles
Open the catalog to page 1214 Pages
7 Pages
10 Pages
2 Pages
22 Pages
21 Pages