1. Catalogs
  2. PONOVO POWER CO., LTD
  3. PSS05i Circuit Breaker Simulator Datasheet_EN_2022 V2

PSS05i Circuit Breaker Simulator Datasheet_EN_2022 V2

PSS05i Circuit Breaker Simulator Datasheet_EN_2022 V2

Product catalog summary
Product Description
PSS05i is a Circuit Breaker Simulator designed to simulate both 3-phase and 1-phase operations. It supports single-tripping coil or double trip coil configurations for Circuit Breakers up to 6-500KV. This simulator can replace real circuit breakers to work with protection relays and automation systems for various simulation applications.
Specifications
- When tripping coils I and II are paralleled, the trip current doubles: 0.25A, 0.5A, 1.0A, 2.0A, 3.0A, 5.0A.
- The input trip/close current must exceed 30% of the setting current.
- Pressing the Breaker Failure Button prevents the Circuit Breaker from tripping. The Trip/Close Current opens after a 1-second delay and recovers after 20 seconds.
- Power Supply: DC220V/0.5A, AC 240V/5A.
Technical Data
- Power Supply: AC 220-240V, 50Hz (current < 0.5A), DC 220V/DC 110V.
- Trip Time Options: 20ms, 30ms, 40ms, 50ms, 60ms, 70ms, 80ms, 90ms, 100ms, 110ms.
- Close Time Options: 40ms, 60ms, 80ms, 100ms, 120ms, 140ms, 160ms, 180ms, 250ms, 500ms.
- Trip/Close Time Error: <±5ms, (error <±20ms at 500ms).
- Trip Current Options: 0.25A, 0.5A, 1.0A, 2.0A, 3.0A, 5.0A.
- Weight: 10kg.
See more

Catalog excerpts

PSS05i Circuit Breaker Simulator Datasheet_EN_2022 V2-1

Product Description PSS05i is the Circuit Breaker Simulator, which can simulate 3-phase and 1-phase operation, single-tripping coil or double trip coil of Circuit Breaker up to 6-500KV level. It can replace the real circuit break to work together with protection relay and automation system to do more simulation applications. Specification Technical Data Power Supply Trip/Close Operation Voltage Trip Time Options Close Time Options Trip/Close Time Error Trip Current Options Trip Current Note Close Current Options Close Current Note Breaker Failure PSS05i AC 220-240V, 50Hz (current<0.5A) DC 220V/ DC 11OV 20ms, 30ms, 40ms, 50ms, 60ms, 7Oms, 80ms, 90ms, 1OOms, 11Oms 40ms, 60ms, 80ms, 100ms, 120ms, 140ms, 160ms, 180ms, 250ms, 500ms <±5ms, (error< ±20ms, at 500ms) 0.25A, 0.5A, 1.0A, 2.0A, 3.0A, 5.0A When tripping coils I and II paralleled, the trip current will be doubling 0.25A, 0.5A, 1.0A, 2.0A, 3.0A, 5.0A When the input trip/close current is more than 30% setting current. Press the Breaker Failure Button, the Circuit Breaker will not trip, Trip/Close Current will be open after 1s delay, and then after 20 seconds, it shall recover. Binary Output Capacity Weig ht El PONOVO POWER CO., LTD. No.139 Jinghai Third Road, BDA, Beijing, China. 100176 Tel:+86 (10) 59089666 Fax:+86(10)59089999 www.ponoco.net [email protected] [email protected]

 Open the catalog to page 1

All PONOVO POWER CO., LTD catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.