Main Features:
  • High reliability with smooth, real-time output waveform without high harmonic distortion.
  • Accurate waveform representation at lower currents.
  • Capability to playback up to 6 channels of current/voltage at high speed with an output signal frequency of 500kHz.
  • Transient characteristic with drop/rise time less than 3µs.
  • Supports testing of traveling wave fault location at two sites using GPS synchronization.
  • Fault playback capability with support for COMTRADE file playback and waveform editing, with a sample rate up to 10MHz, ranging from 80ms to 50s.
Specifications:
  • Voltage Source:
    • Range: 3x0-60Vrms continuous output, 3x60-100Vrms for 5 seconds, 3x150Vpeak for 50ms.
    • Power: 6VA@60V, 10VA@100V.
    • Accuracy: 0.1V≤U<5V: ≤1%±2mV; 5V≤U<100V: <0.5%.
    • Frequency: 0Hz-350kHz (±3dB).
    • Step response: 2us.
    • Channel synchronization: ≤0.2us.
  • Current Source:
    • Range: 3x0-5Arms continuous output, 3x5-10Arms for 5 seconds, 3x15Apeak for 50ms.
    • Power: 60VA@5-10A.
    • Accuracy: 0.1A≤I<0.5A: ≤1%±1mA; 0.5A≤I<10A: <0.5%.
    • Frequency: 0Hz-500kHz (±3dB).
    • Step response: 3us.
    • Channel synchronization: ≤0.2us.
  • Power Supply:
    • Nominal input voltage: 110-220Vac.
    • Nominal frequency: 50/60Hz.
  • Environmental Conditions:
    • Operation temperature: -10~45°C.
    • Storage temperature: -25~70°C.
    • Relative humidity: 5-95% non-condensing.
  • Others:
    • GPS External accessory: PGPS02i.
    • Dimensions: 448mmx266mmx500mm.
    • Weight: 17kg.
Additional Information:
  • COMTRADE Waveform and GPS Synchronization Output are supported.
See more

Catalog excerpts

PH041i Travelling Wave Fault Location Test Kit brochure_EN_2023 V1-1

PDIMDVD PH04i Travelling Wave Fault Location Test Kit Main Feature • High reliability • The output waveform is smooth and real-time without high harmonic • Accurate waveform at lower current • Max 6 channels of current/voltage can be played back at high speed with output signal frequency 500kHz • Transient characteristic: drop/rise time less than 3^s • Support to test traveling wave fault location at two sites by GPS synchronization. • Fault playback Support to playback COMTRADE file and edit waveform Support sample rate upto 10MHz, from 80ms to 50s

 Open the catalog to page 1
PH041i Travelling Wave Fault Location Test Kit brochure_EN_2023 V1-2

Voltage source Range 3x0-60Vrms, continues output Current source Range 3x0-5Arms, continues output Power supply Nominal input voltage 110-220Vac Binary Binary input 1 Environmental conditions Operation temperature -10~45°C Relative humidity 5-95% non-condensing Others GPS External accessory PGPS02i 3 PONOVO POWER CO., LTD. No.139 Jinghai Third Road, BDA, Beijing, China. 100176 Tel : +86(10) 59089666 Fax: +86(10)59089999 www.ponovo.net [email protected] [email protected]

 Open the catalog to page 2