gpONDVDPCT200Portable CT/PT Testing System il^DNOVD 200 Portable CT/PT Testing System
Open the catalog to page 1PCT200 Portable CT/PT Testing System PCT200 Portable CT/PT Testing System is a test equipment specially designed for current transformer and voltage transformer characteristic tests. PCT200 Portable series has two models, the standard PCT200X and the higher accuracy PCT200AX. Each model has 2 optional power supply type-external power supply type (PCT200X, PCT200AX) and large-capacity lithium battery supply type (PCT200X-B, PCT200AX-B). With built-in testing software in its local 7inch touch screen, all test items can be completed after pressing Excel the Run generating Excel andfinalize PDF automatically...
Open the catalog to page 2• Secondary loop time constant (Ts) • Transient dimensioning factor (Ktd) • Peak value of instantaneous error (£A) • Rated symmetrical short-circuit current factor (Kssc) • Rated equivalent limiting secondary e.m.f. (Eal) • Winding resistance • Knee point • Composite error • Current injection • Ratio error and phase displacement • Accuracy limit factor (ALF) • Instrument security factor (FS) PCT200 portable series can test various CT, including Steady-state CT, which include protection CT, measurement CT and metrology-grade CT; Transient CT, which include TPS, TPX, TPY, TPZ grade; Transmission...
Open the catalog to page 3PCT200 Portable CT/PT Testing System Wiring connection of various CT testing Transmission line CT test CT test in the star connection transformer CT test in the star connection transformer CT test in Delta connection transformer CT test in Delta connection transformer Burden test / Current injection test Test CT with multiple taps
Open the catalog to page 4PCT200 Portable CT/PT Testing System Following PT tests can be done • Polarity • Winding resistance • Knee point Voltage injection test • Voltage injection • Wiring connection Single phase PT test-polarity and ratio Three phase PT test-polarity and ratio Single phase PT test-resistance and excitation Three phase PT test- resistance and excitation PCT200 Portable CT/PT Testing System Test Principle Load test output and measurement parameters Input low voltage signal on the secondary side of CT & measurements Calculate all relevant parameters of CT and its accuracy at different current
Open the catalog to page 5PCT200 portable CT/PT testing system is professional CT/PT test set which adopts new principle launched by PONOVO. The new principle is the "voltage method" test principle used for the transformation ratio, and the "DC method" test principle for the excitation characteristics which is more advanced than the conventional "frequency conversion method". The "voltage method" test principle is the AC voltage of 0~130V output to the secondary side of transformer. By using high-precision voltage acquisition circuit to collect and analyze the voltage induced by the primary side, then calculate the actual...
Open the catalog to page 6PCT200 Portable CT/PT Testing System PCT200 Portable Series Panels The front panel and right panel of PCT200 Portable Series are same, the top panel of external power supply type and battery type are different. PCT200 Portable Series Front Panel 7-inch touch screen Test wiring diagram PCT200 Portable Series Right Panel Ethernet port, connect with PC DB9 port, connect with ATB02
Open the catalog to page 7PCT200 Portable CT/PT Testing System PCT200 Portable Series Top Panel- external power supply type S1, S2 input port S1, S2 output port USB port for report export / software upgrade Power supply switch Grounding port Power supply connector PCT200 Portable Series Top Panel- battery type USB port for report export / software upgrade Ethernet Port for connect with PC DB9 port for connect with ATB02 Power button Grounding port Charger connection port
Open the catalog to page 8PCT200 Portable CT/PT Testing System PCT200 Portable CT/PT Testing System Software PCT200 portable CT/PT testing system software is a smart comprehensive automated testing software. It adopts the built-in touch screen, which makes the human-computer interaction more friendly. Test report can be saved for a long time, also can be exported through the U disk at any time and edited. When using PCT200, the tester only needs to wire tester and transformer, input the nameplate of the transformer then press Run button, really realizing “one-key test". After the test is completed, the tester will generate...
Open the catalog to page 9PCT200 Portable CT/PT Testing System CT Analyzer – Mobile phone and Tablet control PCT200 portable CT/PT testing system also supports Mobile phone control and Tablet control. The connection between test set and mobile phone/tablet by Bluetooth. The function is same with local software. PCT200 controlled by Mobile phone PCT200 Portable CT/PT Testing System Main interface Test results Test process Excitation curve
Open the catalog to page 10PCT200 Portable CT/PT Testing System CT Analyzer – PC software (optional) PCT200 portable CT/PT testing system also supports PC control. The connection between test set and PC by WIFI or Ethernet cable. The function is same with local software. And supports the ATB02 as well. Main interface Result page
Open the catalog to page 11PCT200 Portable CT/PT Testing System PCT200 Portable CT/PT Testing System Specification s Application Output voltage PCT200X Test M/P/TP type CT and PT 0-130V Output voltage range Output current range 0~5Arms (15 Apeak) Output power 0~500VArms Turn ratio range Ratio measurement Test M/P/TP type CT and PT Test M/P/TP type CT and PT Test M/P/TP type CT and PT 0-130V 0-120V 0-130V 0-5Arms (15A peak) Output voltage range 0-120V Output current 0~5Arms (15 Apeak) 0~5Arms (15 Apeak) 0.0001VA~500VA (1500VA peak) Output current range 0-5Arms Output power 0~500VArms 1-100000~500VArms (15A peak) 30000:1...
Open the catalog to page 12PCT200 Portable CT/PT Testing System Winding resistance (primary & secondary) Range Accuracy Resolution Turn ratio Accuracy Resolution Burden Burden range CT Burden resolution Others Temperature Compensation Burden test Nominal & operating Accuracy limit factor (ALF) Instrument security factor (FS) Remanence factor (Kr) Secondary loop time constant (Ts) Saturated inductance (Ls) 0.02%rg. + 0.03%rd. Typ. Output voltage range 0.05%rg. + 0.05%rd. Gur. Output current range 0.1mΩ Output power Turn ratio range Ratio measurement 0-5Arms (15A peak) 0.1mΩ(1500VA peak) 0.1mΩ 0.0001VA~500VA 1-10000 30000:1...
Open the catalog to page 1315 Pages
7 Pages
10 Pages
2 Pages
22 Pages
21 Pages