Terrain Firetrap
12Pages

{{requestButtons}}

Catalog excerpts

Terrain Firetrap - 1

Terrain Firetrap Fire protection for above ground drainage systems

Open the catalog to page 1
Terrain Firetrap - 2

The best fire rating available for the drainage stack As part of the on-going development of Terrain drainage systems, we have developed a comprehensive range of passive fire protection products for use with Terrain PVC soil and waste, Terrain Fuze and Terrain dB12. These products will enable secure specification of Terrain drainage systems with the confidence of conforming to the requirements of Part B Building Regulations. In addition all products comply with BS 476 Part 20 and BS EN 1366-3. The Terrain Firetrap range comprises: Terrain Firetrap Sleeves • Ideal for Terrain Fuze stacks •...

Open the catalog to page 2
Terrain Firetrap - 3

Firetrap Sleeves Firetrap Collars for Terrain PVC, Terrain FUZE and Terrain dB12 Construction Details and Fire Rating Installation of Firetrap Sleeves Installation of Firetrap Collars for Terrain PVC, Terrain FUZE and Terrain dB12 Standards and Certification Pages 4-5 Pages 6-7 Page 8 Page 9 Page 10 Page 11

Open the catalog to page 3
Terrain Firetrap - 4

Firetrap Sleeves The Terrain Firetrap Sleeve is a cost effective product for the fire stopping of pipe penetrations whilst maintaining similar thermal and acoustic properties as standard mineral fibre insulation. Terrain Firetrap Sleeve was developed with ease of installation in mind. The sleeve can be quickly and simply fitted onto the pipe and slid into the penetration ensuring that there are no air gaps around the sleeves by filling with mortar or mastic. In a fire situation the sleeve expands to fill the available space (15mm max) between the pipe and the penetration and will crush and...

Open the catalog to page 4
Terrain Firetrap - 6

Firetrap Collars - for Terrain PVC soil and waste, Terrain FUZE and Terrain dB12 Terrain Firetrap Collars have been specifically designed to re-instate the fire resistance of a wall or floor which has been penetrated by services such as Terrain PVC, Terrain FUZE or Terrain dB12 Manufactured in steel, each fire collar contains an internal lining of intumescent graphite impregnated organic polymer. Anchoring hooks are also supplied. The collars will seal pipes from 50mm to 315mm diameter and can be face fixed or set into a wall or ceiling structure. They are suitable for use on concrete,...

Open the catalog to page 6
Terrain Firetrap - 7

Fire Rating Collars will seal

Open the catalog to page 7
Terrain Firetrap - 8

Construction Details Fire protection for vertical Terrain Drainage Pipework in a NON fire rated duct Note: Metal brackets to be installed to support pipework accordingly Firesleeve scolloped out locally for 50mm pipe entry to sit flush on floor if required Plasterboard Terrain FUZE Terrain insulated Firetrap Fire Sleeve 4 hour rating top and bottom of slab Note: Insulation may be required to meet standard building requirements and regulations Basin WC Maximum allowable gap around fire sleeve to be 15mm all round. Above this must be filled with Firestop compound or concrete Fire rated wall...

Open the catalog to page 8
Terrain Firetrap - 9

Installation - Firetrap Sleeves To maintain the fire rated compartment between floor levels where Terrain drainage penetrates the slab, an insulated fire sleeve should be installed. The fire sleeve should be installed through the entire slab penetration. Where possible a maximum of 25mm of sleeve can be left protruding out of the slab both at floor level and the underside of the slab. If, due to low level connections at slab level, this method is not possible then two alternative methods can be used; 1. Maintain the 25mm protrusion but scollop out the sleeve locally to accommodate the low...

Open the catalog to page 9
Terrain Firetrap - 10

Installation - Firetrap Collars for Terrain PVC, Terrain FUZE and Terrain dB12 1. How to install the fire collar Drill a hole through the wall/floor using a corer and crown bit in required size. Install the plastic pipe. Seal the gap between the hole and the pipe. If a wide gap exists, the space must be sealed using fire-proof mortar or alternatively, an intumescent sealing agent. Close off the remaining gap to ensure a seal is formed against smoke and gas A sealing effect is achieved with the expansion of the intumescent material during the fire which completely seals the plastic pipes....

Open the catalog to page 10
Terrain Firetrap - 11

Standards and Certification Steps must be taken that comply with the provisions of the National certificates issued for the product when a fire-proof seal is made for the passage of pipes using fire-proof intumescent collars. Terrain recommends referring to the product’s certificates to verify the limitations with regards to the size of the opening, type and thickness of the wall or floor and the maximum diameter of the pipes. Local Fire Regulations should always be consulted in accordance with Building Regulations Part B. Firetrap Sleeves for Terrain FUZE Firetrap Collars for Terrain FUZE...

Open the catalog to page 11
Terrain Firetrap - 12

TERRAIN FIRETRAP FSC Mixed Sources Product group from wsll-nMnigod furwti and otnor controlled nu»> Cert no. SA-C0C-W1754 www.fic.arg 01 Ml Forest Stewardship Covnd Polypipe Building Services New Hythe Business Park College Road Aylesford Kent ME20 7PJ United Kingdom Tel: +44 (0)1622 795200 Fax: +44 (0)1622 716796 commercialenquiries@polypipe.com www.polypipe.com/commercial-building-services

Open the catalog to page 12