Introduction
The document discusses the new generation of Electronic Power Factor (PF) Corrector Systems developed by Karmet Group Companies, focusing on improving operating efficiency and reducing energy costs by minimizing reactive energy consumption.

Specifications
The systems utilize thyristor-controlled modules for fast and efficient reactive energy correction. Key features include:
  • 32-step capacitive and 2-step inductive sensitivity correction.
  • Zero current switching for increased capacitor life.
  • Modular architecture for easy installation and scalability.
  • Remote communication and monitoring capabilities.

Procedures
The systems operate by independently controlling each phase, allowing for optimal handling of unbalanced loads. The response time for load changes is 20 milliseconds, significantly reducing the risk of overloading and network losses.

Norms and Standards
The systems are designed to work with both monophase and three-phase systems, with operating voltages of 220/230 VAC and 380/400 VAC, respectively. They comply with standard operating frequencies of 50Hz and offer a correction tolerance of ±2% VAR.

Recommendations
For optimal performance, it is recommended to use these systems in parallel with classical compensation systems, especially in environments with fast-changing loads. The use of harmonic filters is advised to suppress system harmonics and prevent electrical noise.

Key Data and Analysis
Tables and screen shots in the document illustrate the significant reduction in reactive power and the stabilization of active power when the electronic compensation system is active. The systems are shown to reduce kVA values by over 25%, enhancing generator efficiency and reducing energy consumption.

Conclusion
The EKM and EKT series offer a reliable and efficient solution for power factor correction, addressing the limitations of conventional systems and providing significant energy savings and improved network performance.
See more

Catalog excerpts

Electronic pf Corrector-1

EKM-EKT SERIES RELIABLE SOLUTIONS in POWER ELECTRONICS Power Management Instruments PMI / GESS / KARMET GROUP COMPANIES ELECTRONIC PF CORRECTOR SYSTEMS

 Open the catalog to page 1
Electronic pf Corrector-2

2 NEW GENERATION ELECTRONIC THYRISTOR CONTROLLED PF CORRECTOR SYSTEMS ELECTRONIC PF CORRECTOR SYSTEMS Improved operating efficiency is crucial and topical subject around the world. Reduction of energy costs is regarded worldwide as one of the crucial challenges to all branches of the industry. Reactive energy is chiefly regarded as one of the causes for the consumption of unusable energy and that is why reducing reactive energy usage has traditionally been one of the simplest ways to conserve energy. Today, Conventional Compensation Systems are the most common solution providers to eliminate...

 Open the catalog to page 2
Electronic pf Corrector-3

3 Screen Shot 1: Capacitor Activation with Contactor Screen Shot 2: Capacitor Activation with Thyristor As can be observed in Tables 1 and 2, while the active total power is steady (61 kW – 65 kW), total active and reactive power drops significantly to prevent the overloading at mains and transformers. Table 1: Electronic Compensation System is OFF Table 2: Electronic Compensation System is ON COMPARISION MECHANICAL COMPENSATION • Each phase controlled independently enabling the device to handle unbalanced loads at optimum level. • Response time is 20 msec. for fast changing loads • Increased...

 Open the catalog to page 3
Electronic pf Corrector-4

4 Separate Correction of Each Phase (EKM) – Capaciti ve an d Inducti ve Correction with 20 msec . Correction Spee d (EKM-EKT) Load unbalances among phases are perfectly eliminated with separate correction of each phase. The number of activated capacitors is limited to the actual requirement at each phase. Capacitive reactive load correction is also maintained at each phase with a similar logic. Added reactor to sixth arm can also be set in motion via thyristor module if inductive kvar is needed. Lon ger Component Life with Zero Current Switchin g Zero current switching of thyristor diode modules...

 Open the catalog to page 4
Electronic pf Corrector-5

5 ELECTRONIC PF CORRECTOR SYSTEMS MONOPHASE ELECTRONIC COMPENSATION Line1 L1 Current Module Control PCB Current Module Line2 L2 Control PCB Current Module Control PCB Load L1 Load L2 Load L3 Capacitive Block Inductive Block Electronic Swiching Capacitive Block Inductive Block Electronic Swiching Capacitive Block Inductive Block Line3 Electronic Swiching L3 Line1 L1 Line2 L2 Line3 L3 Electronic Swiching & Capacitive Block Current Transformer Control PCB Load L1 Load L2 Load L3 THREEPHASE ELECTRONIC COMPENSATION EKM MODULE 360 kVAR ELECTRONIC PF CORRECTOR MODULE (EKKM) UNIQUE SOLUTION for ELECTRIC...

 Open the catalog to page 5
Electronic pf Corrector-6

6 As demonstrated below, while the active power remains stable (81 kW-83 kW), the kVA value diminishes by more than 25% (116 kVA – 84 kVA). Such a significant difference can be explained by as follows; 1. Additional Power Capacity: Generator’s consumed power for reactive energy (over 25%) can be used for active energy (pf corrected from 0.7), so that it will be possible to have more loads with the same generator set. 2. Energy Saving: Since the reactive power is eliminated, the current at mains will decrease at the same rate, which will bring savings on energy usage. 3. More efficient Operation...

 Open the catalog to page 6
Electronic pf Corrector-7

7 • Each phase controlled separately to enable the system to handle unbalanced loads at optimum level. • Response time is 20 msec. for fast changing loads • Increased capacitor life with zero current switching • 32 step capacitive and 2 step inductive sensitivity correction with binary logic • No current harmonics with harmonic filters at each of 5 arms • Semiconductor switching increases reliability • Periodic test of capacitors and semiconductors to give prior failure detection • Remote communication and monitoring with RS 485 • Modular construction and easy service • Parallel operation with...

 Open the catalog to page 7
Electronic pf Corrector-8

Power Management Instruments Group Companies Ortadoðu Elektronik Sanayi Ltd. ªti. Karmet Makina Elektronik Tasarým A.S. PMI Elektrik Sistemleri Dis Tic. Ltd. Sti Sales & Marketing Perpa Elektrokent A Blok Kat:12 No:1767 Okmeydani / ISTANBUL / TURKEY Tel: +90 212 320 35 95 / +90 212 320 35 96 Fax: +90 212 320 35 97 E-mail: [email protected] Manufacturing Plant and R&D Modern Keresteciler Sanayi Sitesi 1. Cad. 23. Sok. No:14 Saray / Kazan / ANKARA / TURKEY www.pmienergy.com Design by: ARTVENTURE www.ar PMI-2011 V.04-EN tventuredesign.com PMI/GESS/KARMET reserves the right to make alterations on...

 Open the catalog to page 8

All PMI/OES Group catalogs and technical brochures

  1. Inverters

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.