1. Catalogs
  2. PFIFFNER International AG
  3. Inductive voltage transformers EOF

Inductive voltage transformers EOF

Inductive voltage transformers EOF

Inductive voltage transformers EOF

Product catalog summary
General Description: The document describes inductive voltage transformers, specifically the EOF type, designed for outdoor operation in high voltage networks ranging from 24 to 245 kV. These transformers convert high voltage into standardized values for meters and protection devices. The active part is housed in the foot, with high voltage insulation achieved through oil-paper technology using PCB-free mineral oil. The expansion system compensates for oil volume changes due to temperature variations, using a Viton® membrane for 24-72 kV transformers and a stainless steel expansion cell for those above 72 kV.
Design and Construction: The transformers feature corrosion-resistant aluminum alloy housings, which can be color-coated. They are equipped with either porcelain or silicone composite insulators, with various creepage distances available. The hermetically sealed housing protects against atmospheric influences. The terminal box is designed for easy connection, with optional preinstalled cable glands and safety instructions.
Technical Specifications: The document provides detailed technical data for different voltage levels, including withstand voltages, frequency, accuracy class, thermal limiting output, and physical dimensions. The transformers are compliant with IEC/IEEE standards and offer high operating safety with no active parts in the insulator.
Advantages: Key advantages include protection against transient overvoltages and ferroresonance, high operating safety, and optimized design for minimal oil volume. Additional features include color-coated housings, pressure monitoring, and sealable covers for billing purposes.
Installation and Protection: The transformers are designed for easy installation with a generously sized terminal box and excellent moisture protection. The fine-graded bushing ensures optimal electric field distribution and is short-circuit safe.
Global Presence: The document lists contact information for PFIFFNER's global offices, indicating a strong international presence.
See more

Catalog excerpts

Inductive voltage transformers EOF-1

Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 -245) kV Current and voltage - our passion

 Open the catalog to page 1
Inductive voltage transformers EOF-2

General description Voltage transformers type EOF are used in high voltage networks within the 24  –245 kV range. They transform high voltage into standardised values for meters, measuring and protection devices. The active part of the voltage transformer is located in the foot housing. The high voltage insulation is implemented in oil-paper technology. To achieve this, a high quality PCBfree mineral oil is used. The fine graded bushing is inside the insulator. The expansion system is located in the head of the voltage transformer. This unit acts as volume compensation for the oil in case of...

 Open the catalog to page 2
Inductive voltage transformers EOF-3

Design Primary connection Expansion bellows Bellows cover with oil expansion indicator Porcelain or silicone composite insulator Possible options Colour coated housings and flanges Fuses or miniature circuit breakers (MCBs) with or without auxiliary contacts in the terminal box Pressure monitoring with auxiliary contacts Sealable cover on terminals for billing purposes Tan δ terminal for capacitance and di-electric dissipation factor measurement Sealable oil drain valve Primary coil with high voltage insulation Lifting lugs Housing with drainage area Secondary coil Main earth

 Open the catalog to page 3
Inductive voltage transformers EOF-4

* with standard composite silicone insulator, creepage distance 25 mm/kV

 Open the catalog to page 4
Inductive voltage transformers EOF-5

Fine graded bushing Excellent protection against moisture The fine graded bushing is designed to ensure an optimum distribution of the electric field. The inner side of the instrument transformer is protected against moisture by means of special sealing rings. The bushing is fixed in a way, that it is short-circuit-safe and secondary arcs are prevented. All housings are designed with a drain-age area to protect the sealing surfaces of the housings against rain. This significantly reduces crevice corrosion. The housing elements are connected with special stainless steel screws. They are designed...

 Open the catalog to page 5
Inductive voltage transformers EOF-6

PFIFFNER Instr. Transformers Ltd 5042 Hirschthal Switzerland ® +41 (0)62 7392828 PFIFFNER Technologie Ltd 5042 Hirschthal Switzerland ® +41 (0)62 7392828 PFIFFNER Systems Ltd 4303 Kaiseraugst Switzerland ® +41 (0)61 4676111 PFIFFNER Deutschland GmbH 25524 Itzehoe Germany ® +49 (0)48 21408270 PFIFFNER Transformator A.S. 06750 Akyurt/Ankara Turkey ® +90(0)31 28475521 PFIFFNER do Brasil Ltda 88307-740 Itajai Brazil ® +55 (0)47 33481700 MGC Moser-Glaser Ltd 4303 Kaiseraugst Switzerland ® +41 (0)614676111 ALPHA Elektrotechnik Ltd 2560 Nidau Switzerland ® +41 (0)32 3328700 This document has been drawn...

 Open the catalog to page 6

All PFIFFNER International AG catalogs and technical brochures

  1. SP / SK

    2  Pages

  2. Wago

    1  Page

  3. TVS-14

    1  Page

  4. EJGF

    6  Pages

  5. XT 2/4/5

    3  Pages

  6. TSC-PQ

    2  Pages

  7. TSC 1–8

    3  Pages

  8. TP

    3  Pages

  9. TEMBREAK2 T2

    9  Pages

  10. TCH 1

    2  Pages

  11. MG T3

    6  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.