1. Catalogs
  2. Pepperl+Fuchs SE
  3. Unicom Com Unit for PROFIBUS DP/DP-V1

Unicom Com Unit for PROFIBUS DP/DP-V1
1 /3Pages

Unicom Com Unit for PROFIBUS DP/DP-V1

Unicom Com Unit for PROFIBUS DP/DP-V1
1 /3Pages

Catalog excerpts

Unicom Com Unit for PROFIBUS DP/DP-V1-1

Unicom Com Unit for PROFIBUS DP/DP-V1FB8209H0908.3 ■ Interface between the I/O modules and the PCS/PLC ■ Com unit for 80 analog or 184 digital channels ■ Installation in suitable enclosures in Zone 1 ■ HART communication via PROFIBUS DP V1 or service bus ■ Non-volatile memory for configuration and parameter settings ■ Self configuration in redundant systems ■ Outputs drive to safe state in case of failures Unicom Com Unit for PROFIBUS DP/DP-V1 The PROFIBUS com unit forms the interface between the I/O modules on the backplane and the process control system. It supports all single width and dual width I/O modules. Thereby signals from NAMUR sensors, mechanical contacts, high-power solenoid drivers, power relays, sounders, and alarm LEDs are transported to the higher-level bus system. The com unit can be easily configured via DTM and supports redundancy as well as HART. Configuration in Run (CiR) enables configuration of a running system without a PROFIBUS restart, even in non-redundant systems. Release date: 2025-10-31 Date of issue: 2025-10-31 Filename: 70106285_eng.pdf Technical Data Slots Rated voltage Ur 5 V DC , only in connection with the power supplies FB92** Fieldbus connection Fieldbus type PROFIBUS DP/DP-V1 Refer to "General Notes Relating to Pepperl+Fuchs Product Information". Pepperl+Fuchs Group www.pepperl-fuchs.com [email protected] [email protected]

 Open the catalog to page 1
Unicom Com Unit for PROFIBUS DP/DP-V1-2

LED indication LED green (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active LED red (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation Release date: 2025-10-31 Date of issue: 2025-10-31 Filename: 70106285_eng.pdf Directive conformity Electromagnetic compatibility Directive 2014/30/EU Electromagnetic compatibility Degree of protection Fieldbus standard Environmental test Shock resistance Vibration resistance Damaging...

 Open the catalog to page 2
Unicom Com Unit for PROFIBUS DP/DP-V1-3

Unicom Com Unit for PROFIBUS DP/DP-V1 Technical Data Data for application in connection with hazardous areas EU-type examination certificate Directive conformity Directive 2014/34/EU International approvals ATEX approval IECEx approval General information System information The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have...

 Open the catalog to page 3
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.