RDW2-1600 series
13Pages

{{requestButtons}}

Catalog excerpts

RDW2-1600 series - 1

series Intelligent type universal circuit breaker Appliance RDW2-1600 Intelligent type Air circuit breaker, is mainly applied to power distribution network of rated operational voltage up to 690V, rated current from 200A to 1600A. It used to distribute power and protect circui and power-supply equipment against damages of overload, under-voltage, short-circuit, single-phase grounding(leakage) this kind fault. And circuit breaker has Intelligent protection functions, accurated selective protection function, and it can rise power-supply reliability to aviod unneccessary power interruption. And it also has common communication port to connect with fieldbus conveniently and realizes the remote function to meet the requirements of control center and automatic system. The corresponding leakage transformer and intelligent controller can realize leakage protection. This protection has isolation functions, the sign is . This productio which rated operational current below 630A, is also can be used to power-distribution network of AC50(60)Hz, 400V for protecting Motor against overload, short-circuit, phase-loss, under-voltage and grounding fault this kinds fault. Under normal condition, it also can be used to transfer circuit unfrequently and start motor unfrequently. This production conforms to standard of GB14048.1-2012, GB14048.2-2008, GB14048.4-2010. Rated current Poles(3P,4P) Frame size rated current C for Drawout type(Non for Fixed type), H for insulation switch Design code Air circuit breaker Company code 2.1.1 Use type: Main circuit: A type(non-selective type), B type(selective type), and AC-3 (operate motor directly) Auxiliary circuit: AC-15,DC-13 2.1.2 Installation type: Fixed type, Drawout type 2.1.3 Transmission type: Motor, Handle 2.1.4 Poles: 3P,4P 2.1.5 Release type: Intelligent controller, shunt release,,under-voltage instantaneous(or delay) release 2.1.6 Intelligent controller type 2L type: economic type(basic function) 3M type: normal type(basic function+Intelligent function) 3H type: advanced type(basic function+Intelligent function+communication port)

Open the catalog to page 1
RDW2-1600 series - 2

series Intelligent type universal circuit breaker Normal operation conditon and installation condition 3.1 Temperature: no more than +40ºC, no less than -5ºC, and average day temperature no more than +35ºC. Notice: when the temperature requirment exceed the above range, it should be consulted with Manufacture. 3.2 Atitude: Installation location altitude should no more than 2000m. 3.3 Humidity: when the temperature at +40ºC, it no more 50%. The higher humidity is acceptd at the lower temperature., like 90% humidity is accepted under +20ºC. The condensetion should be taken care when the...

Open the catalog to page 2
RDW2-1600 series - 3

series Intelligent type universal circuit breaker 4.5.3 Instelligent controller long-time delay overcurent protection inverse time-lag action feature is, (T for long-time delay, 1.5I is setting time, I is long-time delay setting current,T is long-time delay action time), action time see Table 4, return factor no less than 0.9, return current is 0.9 T . Table 4 Current setting value Action time Release class Note: Above is power-distribution and motor-protection setting time, generator setting value should consult with company. 4.5.4 Intelligent controller short-time delay characteristic...

Open the catalog to page 3
RDW2-1600 series - 4

series Intelligent type universal circuit breaker Fig 1 overcurrent release protection feature curve Fig 2 Grounding fault protection feature curve 4.5.7 Residual current protection is realized by external leakage current transformer to detect the residual current signal. Action feature is delay type, conforms to Tabel 7.(Not including controller inherent action time 20ms.) Rated residual action current :3A,10A,20A,30A Rated residual no-action current Minimum :

Open the catalog to page 4
RDW2-1600 series - 5

series Intelligent type universal circuit breaker Table 7 Ultimate no drive time residual current 4.5.8 Grounding or residual current protection type Grounding or residual current protection is a protection for equipment because the equipment has leakage current to earth. According to leakage current, it is divied into Grounding protection and residual current protection. Grounding protection is protected by controller according to 3-phases and neutral current vector sum. According to poles, it has 3PT, 4PT,(3P+N)T, three type protection mode.(see Fig 3.) Residual current protection is...

Open the catalog to page 5
RDW2-1600 series - 6

series Intelligent type universal circuit breaker 4.6 Voltage and consumption of Shunt release, Undervoltage release, motor operational mechanism, energy release (closing) electromagnetic, Intelligent controller, see Table 8 Table 8 AC(50Hz) Item Shunt release Undervoltage release Closing electromagnet Motor operational mechanism Intelligent controller voltage Note:1. Controller operational voltage is DC24V, their transformer or power module side can provide voltage AC380V,220V(50Hz) or DC220V,110V 2.Shunt release reliable action voltage range is 70%~110%, closing electromagnet and...

Open the catalog to page 6
RDW2-1600 series - 7

series Intelligent type universal circuit breaker Intelligent controller function Table 10 Controller model no. Overload longtime delay protection Short-circuit shorttime delay protection Short-circuit instantaneous delay protection Grounding fault protection Current imbalance protection Residual current protection Function test Fault memory Signal contact output Thermal memory Self-inspection MCU woring indication Current Histogram display Current meter Making,breaking and Over limit tripping Load monitor Fault state indication and value display Physical quantity measurement Communication...

Open the catalog to page 7
RDW2-1600 series - 8

series Intelligent type universal circuit breaker Phase separator Horizontal connection Vertical connection Vertical connection Busbar thickness Max Outside buttom dimension and installation dimension Fig 4 RDW2-200A-1600A fixed type circuit breaker Phase separator Connect separate Horizontal connection

Open the catalog to page 8
RDW2-1600 series - 9

series Intelligent type universal circuit breaker Phase separator Horizontal connection Connect separate Vertical connection Vertical connection Busbar thickness(mm) Max Outside buttom dimension and installation dimension Fig 4 RDW2-200A~1600A drawout type circuit breaker Frame door and Installation dimension Center line Center line Install plate Install plate Basic line Drawout type Basic line to right side installation hole center to right side installation hole center Fixed type Fig 6 RDW1-1600/3P,4P door frame and installation size

Open the catalog to page 9