Catalog excerpts
aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding ENGINEERING YOUR SUCCESS.
Open the catalog to page 1Page 2 / Catalog OEM-1, Couplings Couplings Table of Contents Introduction to Parker Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 System Couplings 5400 Series Self-Sealing Steel Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 5500 Series Self-Sealing Brass Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5700 Series One-Shot™ Brass Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 FD57 Series Stub Kit Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Open the catalog to page 2Catalog OEM-1, Couplings / Page 3 Introduction to Parker Couplings Parker Hannifin has the broadest coupling product offering in the market. Whether it's quick connect, self-sealing upon disconnection, or brass or steel construction, Parker has what you need. With applications ranging from room air-conditioners to cryogenic pumps, Parker has the product you are looking for. This complete line approach allows Parker to develop value-added assemblies that will reduce SKUs and increase production throughput. Combine this with the outstanding services Parker offers and anything is possible. The...
Open the catalog to page 3Page 4 / Catalog OEM-1, Couplings Parker’s 5400 self-sealing steel couplings are used in fluid-transfer applications for easy maintenance on refrigeration and air conditioning systems. The couplings also allow for pre-charging of units for easy installation. Applications can include marine refrigeration and air conditioning systems, along with cryogenic units. Applications ■ General fluid-transfer applications ■ Marine refrigerant and air conditioning systems ■ Cryogenic systems Base Product Part Number ■ 5400-S2 Male coupling half ■ 5400-S5 Female coupling half Features and Benefits ■...
Open the catalog to page 4Catalog OEM-1, Couplings / Page 5 Performance Data
Open the catalog to page 5Page 6 / Catalog OEM-1, Couplings 5401-S17 Male Half — Braze Tubing Adapter with Jam Nut Part Number
Open the catalog to page 6Catalog OEM-1, Couplings / Page 7 Part Number
Open the catalog to page 7Page 8 / Catalog OEM-1, Couplings * Specify O.D. Tubing size of adapter required in 16th of an inch. Example: -4 coupling with 3/8" O.D. tubing = 6/16 or -6. Part number is then 202208-6-4B. ** Item Number 10 is furnished with the O-ring, Item Number 9. However, Item Number 9 can be purchased separately. Maximum Bulkhead Thickness Recommended Torque Values
Open the catalog to page 8Catalog OEM-1, Couplings / Page 9 Step 1 After tubing or hose has been connected to adapters** (1) and (12), install adapter O-rings (2) and (11)* on adapters. Be sure O-rings are not twisted. Step 2 Generously lubricate adapter O-rings (2) and (11) with the system lubricant to prevent them from scuffing and tearing when coupling body is threaded on adapter. Step 3 Adapter to S2 male coupling half connection. A. Lubricate poppet face with system lubricant. Insert poppet valve assembly (3) into body (4). Tighten body (4) on adapter (1). B. After body and adapter make metal-to-metal contact,...
Open the catalog to page 9Page 10 / Catalog OEM-1, Couplings 5500 Series Self-Sealing Brass Coupling Parker’s 5500 self-sealing brass couplings allow for pre-charging of AC and heat pump systems. The couplings provide for easy maintenance and installation on refrigeration and air conditioning systems. Applications can also include marine refrigeration and air conditioning systems, split refrigeration, and portable cooling solutions. Application ■■Portable split-system air conditioners ■■Split refrigeration systems ■■Marine refrigeration systems ■■Refrigerated dry cleaning systems ■■Beverage systems ■■Compatible with...
Open the catalog to page 10Catalog OEM-1, Couplings / Page 11 When disconnected, spring-loaded valve assemblies in the male and female coupling halves are sealed to prevent refrigerant loss and the inclusion of air or foreign materials. A spring in the male coupling half presses the bonded poppet against sealing surface “A” of the coupling body. Likewise, a spring in the female coupling half presses the sleeve against sealing surface “B” of the stem valve head. An O-ring on the female sleeve prevents leakage between the sleeve and coupling body. Partially Connected Female Coupling Half Female Coupling Half Male...
Open the catalog to page 11Page 12 / Catalog OEM-1, Couplings 5500 SERIES SELF-SEALING BRASS COUPLINGS Protective metal cap/plug not available for -06 coupling body size. + Due to the numerous manufacturers of refrigerant oils and continuous changes of additives, compatibility cannot be guaranteed Contact Parker for compatibility of refrigerant oils not listed.
Open the catalog to page 12Catalog OEM-1, Couplings / Page 13 Liquid Line Pressure Drop vs. Mass Flow A Refrigerant Mass Flow (Kg/Hr) Refrigerant Mass Flow (Lbs/Hr) Suction Line Pressure Drop vs. Mass Flow A Refrigerant Mass Flow (Kg/Hr) Refrigerant Mass Flow (Lbs/Hr)
Open the catalog to page 13Page 14 / Catalog OEM-1, Couplings * Dash size = copper connection size x 16
Open the catalog to page 14Catalog OEM-1, Couplings / Page 15 "B" in the part number denotes a plastic plug. "S" in the part number denotes a steel plug. + Dimension is across hex flats. Dash size = copper connection size x 16
Open the catalog to page 15Page 16 / Catalog OEM-1, Couplings Copper Connection * Dash size = copper connection size x 16 ** "B" in the part number denotes a plastic cap. "S" in the part number denotes a steel cap. + Dimension is across hex flats.
Open the catalog to page 16Catalog OEM-1, Couplings / Page 17 Coupling Body Size Inch (Dash Size*) mm Part Number Dimensions - Inches (mm) Length Diameter * Dash size = coupling body size x 16 Mounting Flange (Steel) Coupling Body Size * Dash size = coupling body size x 16
Open the catalog to page 17Page 18 / Catalog OEM-1, Couplings Coupling Body Size Product Type 5502 = Male Coupling Half 5505 = Female Coupling Half Copper Connection Size Bulkhead Mount InstallationApplicable for sizes -08, -12, and -16 Bulkhead Set-upPanel or Bulkhead Coupling Half with Marker Union Nut II Screwdriver Wrench Step 1 Drill holes in bulkhead or panel to accommodate 5502 coupling half and flange mounting screws. Remove dust cap before positioning on bulkhead. Mount male coupling in half by sliding flange over end of coupling (before brazing tubing) and attaching to bulkhead with self tapping sheet metal...
Open the catalog to page 18All Parker Refrigeration & Air Conditioning catalogs and technical brochures
-
ZoomLock MAX