Catalog excerpts
Transformer Substations
Open the catalog to page 1PFU House-Type Monoblock Transformer Substations 3 PFS Underground Monoblock Transformer Substations 8 PF House-Type Modular Transformer Substations 10 ORMASET Half-buried Packaged Substations 14 MINIBLOK Outdoor Packaged Substation 15 MINISUB Underground Packaged Substation 18 ORMABAT End-of-line Packaged Substation 21 PF-15 Switching Substation 22 MB Frame-mounted Packaged Substation 23 >
Open the catalog to page 2The PFU Transformer Substations consist of a concrete monoblock-structure enclosure that houses all electrical switchgear fromMV switchgear to LV switchboards, including transformers,control devices and interconnecting equipment for the various elements.The main advantage of these Transformer Substations is thefact that both the construction, assembly and built-in equipmentcan be entirely factory-built, thus ensuring uniform quality andsignificantly minimising any on-site construction and assemblywork. In addition, the careful design of the substations allowsthe substations to be installed...
Open the catalog to page 4CGM switchgear panels inside a PFU substation PFU-5 with 1 transformer and PFU-4 substation >
Open the catalog to page 53280 2380Rear View Levelling Sand 3100MV Panels > 100460Visible Height 2200 For transformers rated above630 kVA, additional ventilation grilles are mounted on the side wall. 32802380Rear View Levelling Sand 3100 > 100460Visible Height MV Panels Transfo.LV switchboards > 2200 2380 > 100460Visible Height Rear View Levelling Sand 44804280MV Panels > 2200
Open the catalog to page 74480 > 100460Visible Height 2380Rear View Levelling Sand4280MV Panels Transfo.LV switchboards > 2200 6080 2380Rear View Levelling Sand5900MV Panels > 100460Visible Height Transfo.LV switchboards > 2200 2380 Tranfo.Transfo.LV switchboards Rear View Levelling Sand 60805900MV Panels > 2200 100460Visible Height
Open the catalog to page 8PFS Transformer Substations feature a monoblock structure andhave been designed for underground installation and can housedifferent electrical power distribution arrangements, makingthem suitable for public distribution and private installationload-centre substations.The underground installation and the easy adaptation of thesubstation area minimise any environmental impact.Depending on the ventilation system, two different versions areavailable: PFS-V (vertical grille ventilation, protruding) and PFS-H (horizontal grille ventilation, non-protruding) > 3040 200+50 29003700Concrete Slaband...
Open the catalog to page 9PF Transformer Substations consist of different prefabricatedconcrete elements that are assembled on-site to create a buildingthat houses all electric switchgear: from the MV switchgear to the low-voltage switchboards, including transformers, controldevices and interconnecting means for the different elements.The modular structure allows Transformer Substations to beeasily transported for installation in hard-to-access areas andpermit any arrangement of the Transformer Substation to beimplemented, including the number of access doors andtransformers required for each application....
Open the catalog to page 11For transformers rated above630 kVA, additional ventilation grilles are mounted on the side wall. For transformers rated above630 kVA, additional ventilation grilles are mounted on the side wall. Rear viewLevelling Sand 24602620 > Visible Height MV panels Transfo.LV switchboards > 2520 2360 100600 Rear viewLevelling sand 4880 MV panels Transfo.LV switchboards > 2460 4720 > 100600Visible height 2620
Open the catalog to page 13The ORMASET is a packaged Transformer Substation that hasbeen designed for half-buried installation, incorporating MV switchgear with SF > 6 as insulation and interrupting medium( CGM/CGC ), a transformer, a LV switchboard as well asinterconnecting and auxiliary devices.Its careful outdoor design, compact size and half-buriedinstallation (visible height 1.5 m) reduces the substation visual impact, making it suitable for both industrial and residential areas. Weight: 7.200 kg (without a transformer) > 34752070 1660 ORMASET (view of LV switchboard access doors) View of the 15008501001660 2350...
Open the catalog to page 15Installation of a MINIBLOK requires digging a trench of thedimensions shown in the figure. The trench foundation should be levelled by a compacted sand layer on which the packaged substation will be placed.Installation operations consist of positioning the packagedsubstation on the dug trench and connecting the MV and LVcables and the outside earthing network. The knockout holesprovided on the enclosure should be drilled so this can be done.After bringing these cables in, the cable service entrancesshould be sealed to prevent water from entering the substation, before the trench is covered....
Open the catalog to page 17CONSTRUCTION CHARACTERISTICS AND TECHNICAL SPECIFICATIONS24kV50kV125 [kV] General Prefabricated enclosure Rated voltage Insulation levelAt power frequency At lightning impulse MV panels Rated protection Impact resistance Class Rated busbar current Rated transformer-off current Rated short-time current (3 s) > peak IEC 61330, RU 1303AIEC 60298, IEC 60298, RU 6407B IP 23D IK 10 10K400 A200 A 16/20 kA 20 kA Switch-fuse combination breaking capacity Transformer LV Switchboard Rated voltage Rated current Rated current at outputs UNE 21428-1, IEC 60076, HD 428, RU 5201D Power No-load secondary...
Open the catalog to page 18MINISUB-V model prevents rainfall and even surface waterfrom entering the enclosure until it reaches an approximate height of 200 mm. In the MINISUB-H model, manholes areavailable that can be coupled to the general rain water sewer to remove water that enters through the grilles, thus preventing it from entering the Transformer Substation.In addition, the use of SF > MINISUB is a compact packaged Transformer Substation thathas been designed by Ormazabal to be used for public MV distribution networks. The substation has been designed for underground installation.Inside the compact concrete...
Open the catalog to page 19CONSTRUCTION CHARACTERISTICS AND TECHNICAL SPECIFICATIONS24kV50kV125 [kV] General Prefabricated enclosure Rated voltage Insulation levelAt power frequency At lightning impulse MV panels Rated protection Impact resistance Class Rated busbar current Rated transformer-off current Rated short-time current (3 s) > peak IEC 61330, RU 1303AIEC 60298, RU 6407B IP 23D IK 10 10K400 A200 A 16/20 kA 20 kA Switch-fuse combination breaking capacity Transformer LV Switchboard Rated voltage Rated current Rated current at outputs UNE 21428-1, IEC 60076, HD 428, RU 5201D Power No-load secondary voltage...
Open the catalog to page 21