MV Switchgear for Primary Distribution CPG.1 - 1

MV Switchgear Primary Distribution CPG.1 Single and double busbar gas-insulated cubicles Up to 36 kV CPG System

Open the catalog to page 1
MV Switchgear for Primary Distribution CPG.1 - 2

DESCRIPTION Ormazabal’s CPG System includes the CPG.1 range of GIS Primary Distribution modular cubicles, with Single and Double Busbar, and SF6 insulated. Designed mainly to ensure people’s safety and reliability of service, the CPG.1 range contributes to improving electrical distribution in Medium Voltage networks up to 36 kV. Highly automated manufactured processes, the performance of routine tests across the various phases of the assembly procedure and the use of the most innovative manufacturing techniques assuree the highest level of quality in Ormazabal’s products. STANDArDs IEC...

Open the catalog to page 2
MV Switchgear for Primary Distribution CPG.1 - 3

types of cubicles SINGLE BUSBAR CPG.1- V1 (Circuit-breaker Cubicle) CPG.1- S1 (Disconnector Cubicle) CPG.1- F1 (Fused Protection Cubicle) CPG.1- C (Longitudinal Busbar Coupling Cubicle) DOUBLE BUSBAR CPG.1- V2 (Circuit-breaker Cubicle) CPG.1- S2 (Disconnector Cubicle) CPG.1- F2 (Fused Protection Cubicle) CPG.1- CL (Longitudinal Busbar Coupling Cubicle) CPG.1- CT (Transversal Busbar Coupling Cubicle)

Open the catalog to page 3
MV Switchgear for Primary Distribution CPG.1 - 4

Intern AL ARC Both as a whole and in their various MV compartments, CPG.1 cubicles are designed to withstand an internal arc of 31,5 KA / 1s, in line with the 5 criteria of Appendix A of standard IEC 62271-200 (clase IAC-AFL). TECHNICAL CHARACTERISTICS 24 kV 36 kV Rated current [A] General Busbar Up to 2000 Up to 2000 Outgoing lines 630 / 1250 / 1600 / 2000* 630 / 1250 / 1600 / 2000* Lightning impulse [kV] Between phases and phase-to-earth 125 170 Isolating distance 145 195 Power frequency 1 min [kV] Between phases and phase-to-earth 50 70 Isolating distances 60 80 Rated short-circuit...

Open the catalog to page 4
MV Switchgear for Primary Distribution CPG.1 - 5

• Protected against harsh environmental conditions (dust, pollution, humidity, salinity, etc.), protected against indirect contacts and long service life provided by its gas insulation, with its gas isulation, with the breaking and connection components housed in separated stainless steel swichgear compartments, totally sealed for life. • Internal arc withstand, accredited by means of tests conducted in accordance with the criteria of standard IEC 62271200. • IP rating: IP65 for the tank, and IP3X for the cubicle assembly. • Temperature-compensated monitoring of the gas pressure inside each...

Open the catalog to page 5
MV Switchgear for Primary Distribution CPG.1 - 6

CA·311·GB·0905 TECHNICAL-COMMERCIAL DEPARTMENT Tel.: +34 94 431 87 31 Fax: +34 94 431 87 32 www.ormazabal.com In view of the constant evolution in standards and design, the characteristics of the elements contained in this catalogue are subject to change without prior notification. These characteristics, as well as the availability of components, are subject to confirmation by Ormazabal’s Technical - Commercial Department. ..Transformer Substations up to 36 kV xxMedium Voltage Applications for Renewable Energy ..Medium Voltage Secondary Distribution Switchgear xxCGMCOSMOS System xxCGM.3...

Open the catalog to page 6

All Ormazabal catalogs and technical brochures

  1. CA-500

    44 Pages

  2. CA-209

    4 Pages

  3. CA-112

    40 Pages

  4. CA-343

    6 Pages

  5. CA-110

    40 Pages

  6. CA-326

    6 Pages

  7. CA-505

    32 Pages

  8. CA-109

    36 Pages

  9. CA-502

    40 Pages

  10. CA-121

    8 Pages

  11. CA-100

    40 Pages

  12. ormaSET

    2 Pages

  13. miniSUB

    24 Pages

  14. AMC

    32 Pages

  15. GAE

    36 Pages

  16. CPG.0

    20 Pages

  17. CPG.1

    20 Pages

  18. CFI

    2 Pages