Medium Voltage Switchgearand Switches Medium Voltage Switchgear up to 17.5 kV,Air-insulated, metal-clad, withdrawable technique >

Open the catalog to page 1
Medium voltage switchgear up to 17.5Kv - 3

Drawer unit delivery programme/equipment Delivery programme vacuum circuit-breaker drawer unit 34Equipment for vacuum circuit-breaker drawer unit 35 Delivery programme vacuum load-break switch drawer unit 36Equipment for vacuum load-break switchdrawer unit 37Delivery programme disconnecting link drawer unit 38 Equipment for disconnecting link drawer unit 39 Delivery programme vacuum contactor drawer unit 40Equipment for vacuum contactor drawer unit 41Delivery programme earthing switch 42 Earthing switch, type EDL 42 Earthing switch type DES 42Equipment for earthing switch 43 Installation in...

Open the catalog to page 3
Medium voltage switchgear up to 17.5Kv - 4

AMC ( A ir-insulated M etal C lad) panels are type-tested, air-insulated, metal-clad units which can be assembled side-by-side.Ormazabal AMC switchgear assemblies satisfy the international requirements for air-insulated metal-clad switchgear assemblies.Switchgear in withdrawable techniqueFour metal-clad compartments Drawer units with vacuum circuit-breaker Drawer units with vacuum load-break switch Drawer units with vacuum contactor Standard current and voltage transformers All standard types of protection and control systems can be usedSuitable for combined protection and control systems,...

Open the catalog to page 4
Medium voltage switchgear up to 17.5Kv - 6

Configuration of the cable connection compartment Configuration of the busbar compartment The cable connection compartment offers a multitude of standard and customer option equipment with:Current and voltage transformersՕVoltage transformers with primary fuses Earthing switch ՕSurge arrestor Three-phase medium voltage capacitor ՕHRC fuse baseDepending on the panel version up to three cable systems per phase can be connected in AMC6 panels and up to six cable systems per phase in AMC9 panels. The panel floor is sheet-metal. In the bus sectionaliser panel versions, the compartment contains...

Open the catalog to page 6
Medium voltage switchgear up to 17.5Kv - 7

Cable installation The medium voltage cables can be installed from the front of the panel. The cable connection compartment is easily accessible and has a separate compartment door. After the drawer unit has been removed out of the panel, the front cross-spar of the panel and the plate between the drawer unit compartment and cable connection compartment can be removed with a few movements, for additional ease of installation of cables in the cable connection compartment.The maximum cable cross-sections that can be attached at the cable connections at the panels are as follows: AMC6 =...

Open the catalog to page 7
Medium voltage switchgear up to 17.5Kv - 8

rearmountedfrontmounted A-drawer unit compartment B-busbar compartmentC-cable connection compartmentD-low voltage compartment Low voltage compartment door (front cover) Low voltage compartment door (application-specific)Door closingCapacitive voltage detection system (optional) Low voltage compartment door handlesDrawer unit compartment doorOperation opening for manual winding up of spring accumulatorManual operation of switch Viewing window - switch indicatorsManual operation of switchSlide for the operation opening Operation opening for drawer unitDrawer unit compartment door...

Open the catalog to page 8
Medium voltage switchgear up to 17.5Kv - 9

Example : AMC6-12/1250-630/25-L Example : NVL2F-12/25/1250-150C Panel width:6 = 650 mm9 = 900 mm Rated voltage:7 = 7.2 kV12 = 12 kV17= 17.5 kV Rated busbar current:630 A1250 A2500 A Type of equipment:VL= Vacuum circuit-breakerVLT= Vacuum load-break switchVS= Vacuum contactor TB= Disconnecting link Type of insulating enclosure:2, 3 Rated voltage:7= 7.2 kV12 = 12 kV 17= 17.5 kV Rated short-circuit breaking current > 4) Rated current of outgoing busbar:200 A630 A1250 A2500 A > 3) :20 = 20 kA25 = 25 kA31 = 31.5 kA Rated current:200 A630 A1250 A 2500 A > 4) Rated short-time withstand current:20...

Open the catalog to page 9
Medium voltage switchgear up to 17.5Kv - 10

Interlocking system Operation at the panel The interlocking of panel components according to VDE0671 part 200 respectively IEC62271-200 and optional additional interlocking features of type AMC panels, in connection with the metal-clad panel design, form a safe system and also assist the operator in performance of his operations. To ensure quick and reliable operation of the panel, the operating and display elements are positioned for clear viewing and for clear association. Capacitive voltage detection systems for the outgoing cables and/or main busbars can be equipped as options. The...

Open the catalog to page 10
Medium voltage switchgear up to 17.5Kv - 11

Rated voltage U > r [kV] 7.2 12 17.5 Rated frequency f > r Hz 50/60 50/60 50/60Rated lightning impulse withstand voltage U > p kV 60 75 95Rated power-frequency withstand voltage U > d kV 20 28 38Rated normal current I > r ss 630 630 630A for busbarsOptionalA 1250 1250 1250A 2500 2500 2000 Rated normal current I > r 1) A 630 630 630A for outgoing busbarsOptional 1250 1250 1250A 2500 2500 2000 Rated short-time withstand current I > k 20 20 20kA with t > k = 3sOptionalkA 25 25 25kA 31.5 31.5 31.5 Rated peak withstand current I > P 50 50 50kA at f > r = 50 HzkA 62.5 62.5 62.5kA 80 80 80Ambient...

Open the catalog to page 11
Medium voltage switchgear up to 17.5Kv - 12

Panel ranges/equipment Panel types > 1) Rated voltage U > r [kV] 7.2 12 17.5 > AMC6-12/630-630/20-L Օ > AMC6-12/1250-630/20-L Օ > AMC6-12/1250-1250/20-L Օ > AMC6-12/2500-630/20-L Օ > AMC6-12/2500-1250/20-L Օ > AMC6-12/630-630/25-L Օ > AMC6-12/1250-630/25-L Օ > AMC6-12/1250-1250/25-L Օ > AMC6-12/2500-630/25-L Օ > 3P2MP1 AMC6-12/2500-1250/25-L Օ > AMC6-12/630-630/31-L Օ > AMC6-12/1250-630/31-L Օ > AMC6-12/1250-1250/31-L Օ > AMC6-12/2500-630/31-L Օ > AMC6-12/2500-1250/31-L Օ > AMC9-12/630-630/20-L Օ > AMC9-12/1250-630/20-L Օ > AMC9-12/1250-1250/20-L Օ > AMC9-12/2500-630/20-L Օ >...

Open the catalog to page 12
Medium voltage switchgear up to 17.5Kv - 14

Panel types > 1) Rated voltage U > r [kV] 7.2 12 17.5 > AMC6-12/630-630/20-K Օ > AMC6-12/1250-630/20-K Օ > AMC6-12/2500-630/20-K Օ > AMC6-12/630-630/25-K Օ > AMC6-12/1250-630/25-K Օ > AMC6-12/2500-630/25-K Օ > AMC6-17/630-630/20-K > AMC6-17/1250-630/20-K Օ > AMC6-17/2000-630/20-K > AMC6-17/630-630/25-K Օ > AMC6-17/1250-630/25-K > AMC6-17/2000-630/25-K Օ > 1)Key to type references → > page9. Configuration example for panel type ...-K Other equipment options → page15. > Rated voltage U > r [kV] 7.2 12 17.5 Rated normal current I > r 630 630 630 foroutgoing busbarsA Panel height Standard incl....

Open the catalog to page 14

All Ormazabal catalogs and technical brochures

  1. CA-500

    44 Pages

  2. CA-209

    4 Pages

  3. CA-112

    40 Pages

  4. CA-343

    6 Pages

  5. CA-110

    40 Pages

  6. CA-326

    6 Pages

  7. CA-505

    32 Pages

  8. CA-109

    36 Pages

  9. CA-502

    40 Pages

  10. CA-121

    8 Pages

  11. CA-100

    40 Pages

  12. ormaSET

    2 Pages

  13. miniSUB

    24 Pages

  14. AMC

    32 Pages

  15. GAE

    36 Pages

  16. CPG.0

    20 Pages

  17. CPG.1

    20 Pages

  18. CFI

    2 Pages