Catalog excerpts
Focus on Medium Voltage Medium Voltage Switchgear Primary Distribution Gas insulated, single busbar cubicle range
Open the catalog to page 1The quality of the products designed, manufactured and installed by Ormazabal is backed by the implementation and certification of a quality management system, based on the international standard ISO 9001:2000. Our commitment to the environment is reaffirmed with the implementation and certification of an environmental management system as laid down in international standard ISO 14001. In view of the constant evolution in standards and design, the characteristics of the elements contained in this catalogue are subject to change without prior notification. These characteristics, as well as...
Open the catalog to page 2Medium Voltage Switchgear Primary Distribution Gas insulated, single busbar cubicle range. Quality of the electrical supply 7 Main functional elements 14 Connection between cubicles 19
Open the catalog to page 3Gas insulated, simple busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution General description The CPG.0 range of Ormazabal's CPG system is made up of a full assembly of modular cubicles of up to 24 kV / 2500 A and up to 36 kV / 1250 A, GIS type, with SF6 insulation, for the configuration of different primary distribution electrical diagrams. Types of functional units: • Circuit-breaker CPG.0-V • Busbar coupling CPG.0-C • Disconnector CPG.0-S • Fuse protection CPG.0-F • Busbar rise CPG.0-RB The installation of elements that allow to...
Open the catalog to page 4Gas insulated, single busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution Construction characteristics The CPG.0 cubicles present an architecture divided into independent compartments: D B • (A) Switch compartment. • (B) Busbar compartment. • (C) Cable compartment. • (D) Control compartment. • (E) Operation interface Its structure is made up of a metal frame with a mechanical rigidity that preserves the shape of the assembly under normal service conditions. The frame, together with the rest of non-live metal parts of the cubicle, is...
Open the catalog to page 5Gas insulated, simple busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution The cable compartment, which allows frontal access to the medium voltage cables, is located in the lower part of the cubicle and has a cover that is interlocked with the earthing circuit. The external cone-type bushings allow the installation of toroidal-core current transformers on them. This compartment can be supplied ready to withstand an internal arc in terminals of 25 kA / 1 s, in compliance with the criteria of standard IEC 62271-200. The base can house the...
Open the catalog to page 6Gas insulated, single busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution IP rating IP rating of IP65 for the tank and IP3X for the cubicle assembly. Monitoring Monitoring compensated by the gas pressure temperature inside the tank, including potential-free contact. Voltage presence/absence indicator Permanent indication (multi-LED) and optional contacts for remote indication and/or use of electromagnetic interlocks. Full insulation of the entire power circuit Including the cable terminations, all of which is shielded, earthed and...
Open the catalog to page 7Gas insulated, simple busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution Circuit-breaker cubicle Fuse protection cubicle Disconnector cubicle Busbar coupling cubicle Busbar rise cubicle TECHNICAL CHARACTERISTICS Rated voltage outgoing line between phases and phase-to-earth isolating distance Rated current Short-time power frequency withstand voltage (1 min) Lightning impulse withstand voltage between phases and phase-to-earth isolating distance Rated short-time withstand current Rated peak value withstand current Rated short-circuit...
Open the catalog to page 8Gas insulated, single busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution CPG.0-V Circuit-breaker cubicle Includes a vacuum circuit-breaker and a three position disconnector in series with it. Both components are located inside the switch compartment. ELECTRICAL CHARACTERISTICS Rated voltage Rated busbar current Rated outgoing line current Rated short-time withstand current * With forced ventilation SF6 pressure gauge with potential-free contact Busbar Current transformers Voltage transformers Three-position disconnector Optional Motor...
Open the catalog to page 9Gas insulated, simple busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution CPG.0-S Disconnector cubicle Includes a three-position disconnector without load breaking capacity. ELECTRICAL CHARACTERISTICS Rated voltage Rated busbar current Rated outgoing line current Rated short-time withstand current SF6 pressure gauge with potential-free contact Busbar Current transformers Voltage transformers Three-position disconnector Optional Motor driving mechanism (disconnector) Interlocks* Voltage presence detector Auxiliary contact Cable compartment...
Open the catalog to page 10Gas insulated, single busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution CPG.0-F Fuse protection cubicle It has a three-position switch-disconnector (closed/open/earthing), including fuse protection. The fuses are housed in sealed fuse holders, which in turn are inside the switch compartment, reinforcing the level of insulation. The three-pole opening switch with combined actuation by fuse blow is optionally motorisable. ELECTRICAL CHARACTERISTICS Rated voltage Rated busbar current Rated outgoing line current Rated short-time withstand...
Open the catalog to page 11Gas insulated, simple busbar cubicle range Up to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear Primary Distribution CPG.0-C Busbar coupling cubicle It includes a vacuum circuit-breaker with two three-position disconnectors in series with it, one upstream and the other downstream from the circuit-breaker. These elements are located inside the switch compartments. ELECTRICAL CHARACTERISTICS Rated voltage Rated busbar current Rated outgoing line current Rated short-time withstand current SF6 pressure gauge with potential-free contact Busbar Current transformers Voltage transformers...
Open the catalog to page 12