1. Catalogs
  2. Opto 22
  3. 1936_OptoEMU
video corpo

1936_OptoEMU

1936_OptoEMU
1 / 11 PagesView full catalog

1936_OptoEMU

Product catalog summary
Overview: The OptoEMU Sensor 3V is an energy monitoring unit designed to track real-time energy usage from various sources, providing detailed data for analysis and cost reduction.
Features: It supports real-time and historical data viewing online, data transmission to SNAP PAC Systems, Modbus/TCP or OPC systems, and SQL databases, with communication over Ethernet or wireless LAN.
Energy Monitoring: The sensor aids businesses in managing energy costs by offering detailed consumption data, treating energy management like other business expenses.
Data Viewing and Integration: Energy data can be securely viewed online and integrated into systems like PAC Control strategies, PAC Display HMIs, and SQL databases.
Connectivity: The sensor connects to metering devices via pulse, Ethernet, serial, and direct connections using current transformers, supporting up to 64 Modbus data items.
Configuration: An easy-to-use utility program is provided for IP address assignment and device configuration, with temporary power cables for initial setup.
Communication: Utilizes standard networks and protocols for data transmission, with security features like WPA2/AES for wireless communication.
Data Storage: The sensor can store data internally if communication is lost, ensuring data delivery once restored.
Mounting and Wiring: The unit should be mounted near the monitored panel or device, powered by a 120/240 VAC connection, with higher voltage setups requiring an auxiliary box.
Specifications: Operates on 100-240 VAC, supports Ethernet and wireless communication, includes a serial port configurable for RS-232 or RS-485, housed in a sturdy metal enclosure with a 30-month warranty.
Technical Specifications: Features a short circuit current of 7 milliamps nominal, minimum off resistance greater than 20 K ohms, and maximum allowable ON resistance of 500 ohms. Provides channel-to-channel isolation for 8 channels and input-to-output isolation of 1500 V AC/DC.
Voltage and Current Inputs: Voltage input range is 0 to 400 VAC RMS, with over-range capability up to 440 volts. Current input range is 0 to 333 mV AC, with over-range capability to 416 mV AC.
OPTOEMU-PT600 Auxiliary Box: Optional accessory for fusible disconnects or powering the sensor from panels with voltage higher than 240 VAC.
Warnings: Electrical wiring must be performed by qualified personnel, and power should be disconnected upstream when servicing to avoid shock hazards.
Opto 22 Products: Offers hardware and software for industrial automation, energy management, and data acquisition, with the OptoEMU Energy Management System providing real-time energy data monitoring.
Quality and Support: Opto 22 guarantees high-quality products made in the USA, with free product support available in English and Spanish, along with online resources and training.
See more

Catalog excerpts

1936_OptoEMU-1

OptoEMU Sensor 3V Energy Monitoring Unit Features Description The OptoEMU Sensor™ Energy Monitoring Unit monitors the electrical energy used in your facility and then delivers that data to online software applications or control systems. The OptoEMU Sensor gives you the detailed, real-time data you need to analyze energy consumption and reduce energy costs. Why Monitor Energy? Traditionally, the cost of energy has been considered an overhead cost. Utility bills show few details about when and how electricity was used, and they arrive long after the energy was consumed. Using Energy Data in Other Systems Energy data from the OptoEMU Sensor can also be sent to other systems for use there. Sensor data can be incorporated in a PAC Control strategy, a PAC Display HMI, and control systems that communicate through Modbus/TCP or OPC. In addition, energy data can be sent to common SQL databases such as MySQL and SQL Server. Using Sensor data in these other systems, you can manage energy usage and costs in detail. For more information on using energy data in other systems, see form 1958, the OptoEMU Sensor Communication Guide. However, new energy pricing structures are changing traditional ways of looking at energy costs. Increasingly, commercial and industrial businesses are finding that they can significantly reduce energy costs by managing energy in the same way as other business costs such as people, assets, and inventory. Energy management represents significant opportunities to improve the bottom line. Connecting to Electrical Devices Reducing energy costs does not require complex or expensive technology; it requires basic information. That information starts with gathering detailed, real-time data through the OptoEMU Sensor. OptoEMU Sensor 3V Energy Monitoring Unit Monitor real-time energy usage from utility meters, electrical panels, subpanels, and equipment View detailed real-time and historical energy usage data online through your chosen software service Send data to a SNAP PAC System, systems using Modbus/TCP or OPC, or SQL databases Communicate over standard 10/100 Mbps Ethernet or wireless LAN (802.11a, b, or g), or both at once Part Numbers Viewing Energy Data Energy monitoring unit for electrical OPTOEMU-SNR-3V panels, machines, and devices, Wired+Wireless™ CBL-PWR-120VUS Temporary power cable accessory for initial IP address configuration, North America Temporary power cable accessory for initial IP address configuration, Europe Auxiliary box for OptoEMU Sensor, with stepdown transformer and fusible disconnect Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected] © 2010–2012 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. DATA SHEET The OptoEMU Sensor sends energy data directly to the service you choose, and you can view the data from any authorized computer or mobile device in accordance with the service you purchase. Real-time and historical energy data gathered by the OptoEMU Sensor is viewed online through a secure software service. You choose the service that’s best for your business. The OptoEMU Sensor can connect to a variety of metering devices that emit pulses. It can connect to Modbus devices over serial or Ethernet. And it can also connect directly to electrical circuits using current transformers (CTs) with a 0.333 VAC secondary.

 Open the catalog to page 1
1936_OptoEMU-2

OptoEMU Sensor 3V Energy Monitoring Unit DATA SHEET OptoEMU Sensor 3V Energy Monitoring Unit Connecting to pulse, serial, and Ethernet inputs Connecting directly to a panel The Sensor can monitor energy devices in all ways, simultaneously: • Pulse—The Sensor can monitor up to four electrical devices that emit a pulse output, such as a utility meter or submeter. • Ethernet—The Sensor monitors Modbus/TCP energy devices that connect over an Ethernet network. • Serial—The Sensor monitors Modbus energy devices that connect over a serial network. The serial interface on the unit is software configurable...

 Open the catalog to page 2
1936_OptoEMU-3

OptoEMU Sensor 3V Energy Monitoring Unit A temporary power cable accessory is available, if needed, for assigning the IP address before installation. (See “Part Numbers” on page 1.) Data Storage The OptoEMU Sensor can store data internally. If communication with the software service is lost, the unit stores data for delivery when communication is restored. The OptoEMU Sensor communicates with these services over a standard 10/100 Mbps Ethernet network or over an 802.11a, b, or g wireless LAN (local area network). With wired Ethernet network interfaces plus an independent wireless interface, the...

 Open the catalog to page 3
1936_OptoEMU-4

OptoEMU Sensor 3V Energy Monitoring Unit Wiring for Pulsed Inputs Pulsing Meter with KY pulsing output Use with either two-wire KY (Form A) or three-wire KYZ (Form C) pulsing devices. Junction box with fuses DATA SHEET Contact your utility company if connections are not immediately apparent. Follow wiring instructions in the OptoEMU Sensor User’s Guide, form #1932. Junction box with fuses Pulsing Meter with KYZ pulsing output NOTE: If this equipment is used in a manner not specified by Opto 22, the protection provided by the equipment may be impaired. OptoEMU Sensor 3V Energy Monitoring Unit...

 Open the catalog to page 4
1936_OptoEMU-5

OptoEMU Sensor 3V Energy Monitoring Unit Wiring for Serial Ports RS-232 and RS-485 Pinouts Signal Direction Signal Direction RS-485 2-Wire Serial device Middle of link Serial device End of link RS-485 4-Wire Serial device Middle of link RX – RX + COM TX/RX – TX/RX + Serial device End of link TX – TX + COM RX – RX + OptoEMU Sensor 3V Energy Monitoring Unit DATA SHEET Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected] ©...

 Open the catalog to page 5

All Opto 22 catalogs and technical brochures

  1. 0491_PB

    4  Pages

  2. 1240_SNAP

    6  Pages

  3. 1556_SNAP

    18  Pages

  4. 1184_SNAP

    5  Pages

  5. B3000-B

    4  Pages

  6. 1990_OptoEMU

    8  Pages

  7. 0859_Solid

    23  Pages

  8. 1120_SNAP

    13  Pages

  9. 1065_SNAP

    42  Pages

  10. 1684_SNAP

    7  Pages

  11. 1594_SNAP_

    16  Pages

  12. 1165

    14  Pages

Archived catalogs

  1. 1780_PAC

    2  Pages

  2. 1699_PAC

    9  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.