1. Catalogs
  2. Onda
  3. REMOTE CONDENSERS CLV

REMOTE CONDENSERS CLV

REMOTE CONDENSERS CLV
1 / 24 PagesView full catalog

REMOTE CONDENSERS CLV

Product catalog summary
Specifications:
The document details remote condensers featuring copper pipes and aluminum fins with high-efficiency pyramidal corrugation. The frame is made from galvanized steel, painted in RAL9016, ensuring durability and noise reduction. Standard fan motors operate at 400V - 3F - 50Hz, with options for 60Hz, and are protected with IP54. Capacities are tested under specific conditions using refrigerant R404a, with a standard design pressure of 30 bar, and options for 45 bar. Performance adjustments are possible using coefficients for temperature differences, ambient temperature, refrigerant type, and altitude.
External Frame:
The frame is constructed from galvanized steel and features high-type fan cowls for optimal performance and minimal noise.
Fan Motors:
Standard fans operate at 400V - 3F - 50Hz, with 60Hz options available. They have an external rotor, IP54 protection, and are highly efficient. Motors and fans are balanced both statically and dynamically.
Declared Capacities:
Capacities are tested according to ENV327, with ambient temperature at +25°C, condensation temperature at +40°C, and using refrigerant R404a.
Testing:
All coils undergo testing with dry air and are degreased. Standard design pressure is 30 bar, with options for 45 bar available.
Performance Parameters:
Various coefficients (K2, K3, K4, K5) are provided for adjusting performance based on temperature differences, ambient temperature, refrigerant type, and altitude.
Options:
Several options are available, including fan motor wiring configurations, speed regulators, inverters, EC fans, safety switches, and additional pressure sensors. Specific configurations like vertical air flow kits, anti-vibration supports, anti-hail protection, and special frame colors are also offered.
Quick Selection:
Condensers can be selected based on compressor type, cooling capacity, and working conditions using provided parameters and coefficients.
Procedures:
The adiabatic system includes a three-way electrical valve managed by fan control, which pressurizes the system when temperature or pressure limits are reached. The system automatically empties after each cycle, with piping and nozzles made from AISI material. The pump group provides a maximum pressure of 10 BAR for efficient water nebulization.
Standards and Recommendations:
The standard working pressure is 2.5 BAR, and the minimum required water pressure is 1.5 BAR. It is recommended to use hydrophilic fins to limit corrosion, and the water's pH should be maintained between 6.5 and 8.2. For operations exceeding 200 hours per year, water softening is advised, with hardness not exceeding 10°F.
System Components:
The adiabatic system PD is fully assembled and includes a water distribution system, plastic panels, and trays for water collection. The system is designed to drain completely after each cycle, ensuring maximum efficiency with minimal water flow. The UV disinfection system for water sanitization is available as an option.
Performance Data:
The document provides detailed performance data for various models of remote condensers, including fan numbers, capacity, air flow, power consumption, and nominal current. The data is based on specific standards (ENV327, EN13487, ISO 3744) and includes notes on dimensions and weight.
Options and Compatibility:
Various options are available for the systems, and compatibility with local installation rules should be checked. The document includes a list of available options and notes on specific configurations.
See more

Catalog excerpts

REMOTE CONDENSERS CLV-3

3 Advanced Heat Exchangers Heat Exchange Finned Coils Batterie di scambio termico _All finned coils of remote condensers are produced with copper pipes and aluminium fins with high efficiency pyramidal corrugation _The frame of finned coils is produced in galvanized steel with thickness suitable to weight of heat exchanger. _All pipes are expanded on aluminium counter-endplates to avoid any contact between copper pipes and steel frame and therefore any possible pipe damage. _Endplate holes corresponding to header nipples are larger to avoid that vibrations and dilatations can damage pipes. _Tutte...

 Open the catalog to page 3
REMOTE CONDENSERS CLV-4

Quick Selection / Selezione rapida Condensers can be selected if you know type of compressor, cooling capacity and working conditions according to following scheme and parameters. La selezione del condensatore può essere effettuata conoscendo la tipologia di compressore, la potenza frigorifera e le condizioni di lavoro secondo lo schema e i parametri indicati di seguito. Compressor Type / Tipo di compressore K1 Air Temperature Difference / Differenza di temperatura aria T ambient - T condensation / T ambiente - T condensazione K2 Air Temperature Ambient / Temperatura aria ambiente T amb. °C Altitude...

 Open the catalog to page 4
REMOTE CONDENSERS CLV-5

5 Advanced Heat Exchangers Option / Opzioni PLEASE CHECK PAGE 8 TO KNOW THE AVAILABILITY OF THE OPTIONS CODE CODICE CONSULTARE PAGINA 8 PER CONOSCERE LA DISPONIBILITÀ DELLE OPZIONI Cablaggio elettroventilatori Quadro elettrico Fans with wiring in terminal box Fans with wiring in electrical box including switches and thermal protection for each fan and general switch. Speed Regulator “by step” Fans with wiring in electrical box including speed regulator “by step”. This system lets you keep steady condensation pressure stopping not necessary fans of the condensers. You can set the speed regulator...

 Open the catalog to page 5
REMOTE CONDENSERS CLV-6

Option / Opzioni PLEASE CHECK PAGE __ TO KNOW THE AVAILABILITY OF THE OPTIONS CODE CODICE Kit supporti per flusso aria verticale Kit supports for vertical air flow The unit are standard always shipped and packed in vertical configuration with horizzontal air flow. In case of vertical air flow is necessary to add the option “SV” kit supports for vertical air flow. Is always necessary specify in the order the unit with correct air flow direction ( V = vertical air flow ; H = horizzontal air flow ) because the circuitation of the units is realized to be drainable in the specifical configuration....

 Open the catalog to page 6
REMOTE CONDENSERS CLV-7

7 Advanced Heat Exchangers Adiabatic system / Sistemi adiabatici Nozzle dimension and quantity are selected to get the correct water flow and the best distribution on the finned block. Dimensione e numero di ugelli sono ottimizzati e calcolati per ottenere la corretta portata d’acqua e la miglior distribuzione possibile sul pacco alettato. La pressione minima dell’acqua richiesta è di 2,5 bar. Minimum required water pressure is 2,5 bar. Le elettrovalvole di carico e scarico vengono gestite dal controllo dei ventilatori (nel caso venga selezionato uno dei quadri elettrici + regolazione disponibili),...

 Open the catalog to page 7
REMOTE CONDENSERS CLV-8

The adiabatic system PD is supplied completely assembled and ready to be used. Il sistema adiabatico PD viene fornito completamente montato e pronto all’uso. The structure PD is integrated in the unit and constituted by a water distribution system completely openable, the plastic panels and the trays for water collection and discharge. La struttura PD è integrata nella macchina ed è composta da un sistema di distribuzione dell’acqua completamente ispezionabile, dai pannelli in materiale plastico, dalle vasche di raccolta e scarico acqua. The water distribution system is designed to drain completely...

 Open the catalog to page 8
REMOTE CONDENSERS CLV-9

Condensatori remoti CLV ORDER CODE CODICI DI ORDINAZIONE 9 Advanced Heat Exchangers Fans connection / Collegamento ventilatori D=∆ Y= Number of poles / Numero di poli X = 6S M=6 L=8 Coil type / tipo batteria Number of fans / Numero di ventole ( 1÷8 ) Diameter of fans / Diametro ventilatori 80 = Ø 800mm 91 = Ø 910mm Type / Esecuzione CLV = V shape Single row fans Esecuzione a V Singola fila di ventole

 Open the catalog to page 9
REMOTE CONDENSERS CLV-10

Fan number Numero ventilatori

 Open the catalog to page 10
REMOTE CONDENSERS CLV-11

Advanced Heat Exchangers Fan number Numero ventilatori

 Open the catalog to page 11
REMOTE CONDENSERS CLV-12

Fan number Numero ventilatori Notes / Note (a) Capacity calculation based on ENV327 / Rese calcolate secondo ENV327 (b) Nominal data / Dati nominal (c) According EN13487 / ISO 3744 / In accordo EN13487 / ISO 3744 (d) Diameter valid for CE30 version for CE45 version please contact our technical office / Diametri validi per versione CE30, per versioni CE45 contattare il nostro ufficio tecnico (e) Dimension and weight refer to the standard execution and don’t include any option. Contact Onda for specifical drawing and weight Dimensioni e peso sono riferiti all’esecuzione standard priva di accessori....

 Open the catalog to page 12
REMOTE CONDENSERS CLV-13

13 Advanced Heat Exchangers Notes The dimensions of above drawing are only preliminary and must be always reconfirmed by our Tech. Dept. Note: Le quote d’ingombro sono indicative e vanno sempre confermate dal nostro ufficio tecnico

 Open the catalog to page 13
REMOTE CONDENSERS CLV-14

Fan number Numero ventilatori

 Open the catalog to page 14
REMOTE CONDENSERS CLV-15

Advanced Heat Exchangers Fan number Numero ventilatori

 Open the catalog to page 15
REMOTE CONDENSERS CLV-16

Fan number Numero ventilatori Notes / Note (a) Capacity calculation based on ENV327 / Rese calcolate secondo ENV327 (b) Nominal data / Dati nominal (c) According EN13487 / ISO 3744 / In accordo EN13487 / ISO 3744 (d) Diameter valid for CE30 version for CE45 version please contact our technical office / Diametri validi per versione CE30, per versioni CE45 contattare il nostro ufficio tecnico (e) Dimension and weight refer to the standard execution and don’t include any option. Contact Onda for specifical drawing and weight Dimensioni e peso sono riferiti all’esecuzione standard priva di accessori....

 Open the catalog to page 16
REMOTE CONDENSERS CLV-17

17 Advanced Heat Exchangers Notes The dimensions of above drawing are only preliminary and must be always reconfirmed by our Tech. Dept. Note: Le quote d’ingombro sono indicative e vanno sempre confermate dal nostro ufficio tecnico

 Open the catalog to page 17
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.