K8DS-PU

K8DS-PU
1 / 12 PagesView full catalog

K8DS-PU

Product catalog summary
Overview: The K8DS-PU is a relay designed for monitoring three-phase power supplies in industrial settings. It detects undervoltage, phase sequence, and phase loss, and is resistant to inverter noise.
Key Features:
  • SPDT output relay with a 5 A capacity at 250 VAC.
  • Supports global power specifications, adjustable via a rotary switch.
  • LED indicators for relay status monitoring.
Specifications:
  • Rated input voltage: 200-240 VAC (K8DS-PU1) and 380-480 VAC (K8DS-PU2).
  • Input load: 1.7 VA (K8DS-PU1) and 2.8 VA (K8DS-PU2).
  • Operating value range: -30% to 25% of rated input voltage.
  • Automatic reset with a 5% fixed reset value.
  • Operating time range: 0.1 to 30 seconds.
  • Power ON lock time: 1 second ±0.5 seconds.
  • Output relay ratings: 5 A at 250 VAC or 30 VDC, with a mechanical life of 10 million operations.
  • Operating temperature: -20 to 60°C; Storage temperature: -25 to 65°C.
  • Standards: EN 60947-5-1, UL 508, CSA C22.2 No.14.
Installation and Operation:
  • Mounts on DIN Track, dimensions: 17.5 × 80 × 74 mm.
  • Supports solid and twisted wires with ferrules.
  • Adjustable undervoltage and operating time settings.
Safety Precautions:
  • Ensure power is off before wiring to prevent shock.
  • Avoid use in explosive or inflammable environments.
  • Adhere to specified torque for terminal screws.
  • Operate within rated load and life count to prevent damage.
Environmental Considerations: Not suitable for outdoor use or environments with extreme conditions like direct sunlight, dust, or corrosive gases.
Installation and Usage Guidelines: Maintain specified temperature and humidity, use correct wiring, and ensure voltage and loads are within specifications. Avoid proximity to high-frequency equipment and install an external switch for quick power-off.
Operating Methods: Use appropriate power supplies, adjust settings with precision tools, and ensure waveform distortion is below 30%. Not suitable for thyristor control without a noise filter.
Mounting and Removal: Can be mounted in any direction but must be secure. Allow space for adjustments and use a screwdriver for settings.
Warranty and Liability: Omron offers a 12-month warranty against defects, limiting liability to the purchase price. The buyer is responsible for product suitability and system safety.
Product Changes and Errors: Specifications may change without notice, and Omron is not responsible for documentation errors.
See more

Catalog excerpts

K8DS-PU-1

omRonThree-phase Undervoltage and Phase-sequence Phase-loss RelayK8DS-PU Ideal for Monitoring 3-phase Power Supplies for Industrial Facilities and Equipment. • Greater resistance to inverter noise. new • Monitor undervoltages, phase sequence, and phase loss in three-phase three-wire circuits with one unit. • One SPDT output relay, 5 A at 250 VAC (resistive load). •World-wide power specifications supported by one unit. (Set with a rotary switch.) •Relay status can be monitored using LED indicator. A Refer to Safety Precautions on page 9. Refer to page 7 for commonly asked questions. Ordering Information List of Models Note: The input range is set with a rotary switch. * The power supply voltage is the same as the rated input voltage.

 Open the catalog to page 1
K8DS-PU-3

Specifications Input frequency •Relationship of Mounting Distance between K8DS-PU Relays and Ambient Temperature (Reference Values) The following diagram shows the relationship between the mounting distances and the ambient temperature. If the relay is used with an ambient temperature that exceeds these values, the temperature of the K8DS may rise and shorten the life of the internal components. DIN Track Distance between products: d

 Open the catalog to page 3
K8DS-PU-4

Connections Terminal Diagram Control Output L1 Relay output 250 VAC, 5 A (resistive load) 30 VDC, 5 A (resistive load) Input Voltages Note: Use the recommended ferrules if you use twisted wires. Power supply AC/DC Timing Charts ●Undervoltage Operation Diagram Operation Table L1 Input L2 L3 Undervoltage set value Item Flashing Alarm indicator Indicators RY_LED Undervoltage t: Operating time (0.1 to 30 s) Phase loss Undervoltage contacts t t1: Power ON lock (1 s) Phase Loss Operation Incorrect phase Phase sequence Correct phase *1 Flashing Flashing Undervoltage alarm indicator Undervoltage relay...

 Open the catalog to page 4
K8DS-PU-5

•Indicators Item * This indicator uses the input across L2 and L3 as the internal power supply. It will not light unless there is an input across L2 and L3. •Setting Knobs Item Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with insulating sleeve for the terminal connection. The length of the exposed current-carrying part inserted into the terminal must be 8 mm or less to maintain dielectric strength after connection. For 2.5 mm2 or For ferrules with smaller solid wires an insulation sleeve. Recommended ferrules Phoenix Contact • Al 1,5-8BK (for AWG16) • Al 1-8RD (for...

 Open the catalog to page 5
K8DS-PU-6

Setting Methods •Undervoltage Undervoltage is set using the undervoltage knob (UNDER). The undervoltage can be set to between -30% and 25% of the rated input. Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.) Use this as a guide to set the voltage. The rated input depends on the model and the rotary switch setting. Example: K8DS-PU1 with Rotary Switch Set to 200 V The rated input voltage is 200 VAC and the setting range is 140 to 250 V. •Operating Time The operating time is set using the...

 Open the catalog to page 6
K8DS-PU-7

Checking Operation How to Measure the Operating Time Undervoltage Change the input value quickly from 120% to 70% of the set value and measure the time required for the Relay to operate. Operating Time Adjust the slide resistor so that the voltage applied to the K8DS terminals is 80% of the set value when the auxiliary relay in connection diagram 2 operates. Close the switch and use a cycle counter to measure the operating time. Undervoltage Gradually reduce the input from 120% of the set value. The input will equal the operating value when the input goes below the set value and the alarm indicator...

 Open the catalog to page 7
K8DS-PU-8

Load-side Phase Loss In principle, phase loss cannot be detected on the load side because the K8DS-PU measures three-phase voltage to determine phase loss. Motor Load Phase Loss during Operation Motor load phase loss cannot be detected during operation. It can be used to detect phase loss at startup. Normally, threephase motors will continue to rotate even if one phase is open. The three-phase voltage will be induced at the motor terminals. The diagram shows voltage induction at the motor terminals when phase R has been lost with a load applied to a three-phase motor. The horizontal axis shows...

 Open the catalog to page 8
K8DS-PU-9

Safety Precautions Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/. Warning Indications There is a risk of minor electrical shock, fire, or device failure. Do not allow any pieces of metal, conductors, or cutting chips that occur during the installation process to enter the product. Explosions may cause minor injuries. Do not use the product in locations with inflammable or explosive gases. There is a risk of minor electrical shock, fire, or device failure. Do not disassemble, modify, repair, or touch the inside of the product. Loose...

 Open the catalog to page 9
K8DS-PU-10

Precautions for Safe Use 1. Do not use or store the product in the following locations. • Locations subject to water or oil • Outdoor locations or under direct sunlight • Locations subject to dust or corrosive gases (particularly sulfurizing gases, ammonia, etc.) • Locations subject to rapid temperature changes 5. To reduce the error in the setting knob, always turn the setting knob from the minimum setting toward the maximum setting. 6. Phase loss is detected only when the power supply to the motor is turned ON. Phase loss during motor operation is not detected. 7. Phase loss can be detected...

 Open the catalog to page 10
K8DS-PU-11

Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR...

 Open the catalog to page 11

All OMRON catalogs and technical brochures

  1. NX1P

    41  Pages

  2. J7KCA

    18  Pages

  3. CX-Drive

    80  Pages

Archived catalogs

  1. D4F

    8  Pages

  2. D4GS-N

    11  Pages

  3. E4E2

    5  Pages

  4. G9SE Series

    20  Pages

  5. NT series

    18  Pages

  6. Code Reader/OCR

    24  Pages

  7. CompoNet

    28  Pages

  8. E9NC-T

    2  Pages

  9. ZW Series

    24  Pages

  10. ZS Series

    32  Pages

  11. ZG2

    16  Pages

  12. FZ4 Series

    42  Pages

  13. VC-DL100

    6  Pages

  14. MS4800

    40  Pages

  15. CP1E

    12  Pages

  16. CP1

    12  Pages

  17. E5AC-T

    8  Pages

  18. E2EF

    8  Pages

  19. VT-X700

    6  Pages

  20. Sysmac Catalog

    410  Pages

  21. G5 Series

    59  Pages

  22. E3T Series

    6  Pages

  23. E3T Data Sheet

    26  Pages

  24. E3ZM-C

    14  Pages

  25. E3S-CL

    9  Pages

  26. E3S-A

    21  Pages

  27. E3S-R

    11  Pages

  28. E3S-GS3E4

    3  Pages

  29. D5A

    8  Pages

  30. D5F

    5  Pages

  31. SC

    5  Pages

  32. VB

    5  Pages

  33. NL

    8  Pages

  34. E6A2-C

    5  Pages

  35. E6B2-C

    5  Pages

  36. E6D-C

    5  Pages

  37. E6F-C

    5  Pages

  38. E6H-C

    5  Pages

  39. E4C-UDA

    5  Pages

  40. E4A-3K

    9  Pages

  41. E4B

    12  Pages

  42. G7J

    10  Pages

  43. G7Z

    9  Pages

  44. G4Q

    6  Pages

  45. MMK

    14  Pages

  46. MM

    17  Pages

  47. MK-S(X)

    12  Pages

  48. MK-S

    9  Pages

  49. G2AK

    7  Pages

  50. G2A-434

    7  Pages

  51. G2A

    9  Pages

  52. G7T

    7  Pages

  53. G2R-[]-S

    11  Pages

  54. LY

    14  Pages

  55. NE0A-SCPU01

    6  Pages

  56. E3NC-L/-S

    16  Pages

  57. MY

    35  Pages

  58. V680S Series

    68  Pages

  59. V680 series

    68  Pages

  60. TL-L

    5  Pages

  61. GLS

    3  Pages

  62. F92A

    4  Pages

  63. XS2

    29  Pages

  64. XS5

    25  Pages

  65. APR-S

    6  Pages

  66. SAO

    13  Pages

  67. SE

    15  Pages

  68. K2CM

    16  Pages

  69. K8AK-TH

    12  Pages

  70. K8AK-LS

    12  Pages

  71. K8AK-TS/PT

    12  Pages

  72. K8DS-PZ

    12  Pages

  73. K8AK-PW

    12  Pages

  74. K8DS-PA

    12  Pages

  75. K8AK-PA

    12  Pages

  76. K8DS-PM

    12  Pages

  77. K8AK-PM

    16  Pages

  78. K8DS-PH

    12  Pages

  79. K8AK-PH

    12  Pages

  80. K8AK-VW

    12  Pages

  81. K8AK-VS

    12  Pages

  82. K8AK-AW

    16  Pages

  83. K8AK-AS

    12  Pages

  84. G9SA-300-SC

    9  Pages

  85. WS02-CFSC1-E

    3  Pages

  86. DST1 Series

    5  Pages

  87. G9SA

    16  Pages

  88. G9SB

    10  Pages

  89. G9SX-LM

    28  Pages

  90. G9SX/G9SX-GS

    49  Pages

  91. G9SX-SM/LM

    9  Pages

  92. G9SX-SM

    24  Pages

  93. G9SP

    28  Pages

  94. NX-SL/SI/SO

    20  Pages

  95. Vision Systems

    20  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.