Model C2363A-0-0 Teleterm M3e
8Pages

{{requestButtons}}

Catalog excerpts

Model C2363A-0-0 Teleterm M3e - 1

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. DATASHEET • 12 Configurable Inputs and Outputs • Wide choice of communications options • ISaGRAF 61131-3 Programmable • Internet Ready Comms options • SD Card Logging • Low power operation • 10/100 Ethernet option FEATURES • Integral Real-Time Clock with Battery Backup 12 Inputs and/or Outputs (Analog or Digital) Programmable for a wide range of applications. Wide operating temperature range SD Memory Card Slot for off-line data logging. Compact size for tight spaces On-board temperature sensor and voltage monitor Convenient DIN Rail mounting OVERVIEW The TELETERM M3 series is a state-of-the-art RTU range designed to expand the possibilities of remote monitoring and control by providing a cost effective platform with a wide range of features. Communications options include Ethernet, GSM, 3G UMTS (NextG Australia), CDMA, licence-free Radio in a number frequency bands, Conet Industrial LAN for use over existing plant cabling, and RS232 and RS485 serial. The TELETERM M3 comes with 12 universal I/O that can be configured for analogue or digital input or output according to your needs. The on board RS232/485 port can be used to acquire data from other third party devices using either the Modbus protocol, or by downloading a custom software protocol “plug-in”. This feature allows a wide variety of third party devices to be supported. The low power consumption of the Teleterm M3 makes it suitable for use in solar powered and battery powered applications. The Teleterm M3 series can also be programmed in ISaGraf, an industry standard programming environment for all five IEC61131-3 programming languages, providing the ability to do local control, and custom logic. The Teleterm M3 also incorporates an SD memory card slot to support local data logging. Typical applications for the M3 include: • Energy Management and Remote Meter Reading. Environmental Monitoring Remote Site Monitoring Utilities monitoring Remote inventory monitoring Traffic Management Remote Digital Advertising Sign management Transport/Cargo Monitoring Vending machines Stay in touch – Take control with the Teleterm M3 Series from Omniflex. Copyright Omniflex ♦ Subject to change without notice

Open the catalog to page 1
Model C2363A-0-0 Teleterm M3e - 2

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. General Layout Optional 10/100 Ethernet Port USB Serial Port RS232 Serial Port RS232/485 Serial Port Diagnostic Lights (LEDs) SD Card Eject Button I/O Terminals microSD Memory Card Mechanical Dimensions 109,5 Height including serial cable Copyright Omniflex ♦ Subject to change without notice

Open the catalog to page 2
Model C2363A-0-0 Teleterm M3e - 3

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. Communication Functions by Model Product Name Order Code GSM/ 2.4GHz 868MHz 920MHz +1 10/100 RS232/ 3G RS232 EGSM/ 63mW 315mW 1W RS232/ Notes 12 I/O EtherRS485 UMTS Port GPRS Radio Radio Radio 485 net Port Port Port Port Port Port Port NOTES: 1. The M3G version is available in a number of options to conform to different GSM based networks. Please ensure that the correct unit is specified for your application. 2. The EGSM/GPRS port is a quad band device operating on...

Open the catalog to page 3
Model C2363A-0-0 Teleterm M3e - 4

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. Input/Output Configurable Options The M3 is equipped with 12 versatile input/output points (I/O points or IOP’s). Each I/O point can be individually configured from the options given in the following table: I/O Point Digital Input Analogue Input Digital Output Analogue Output Note 1: See the “Specifications” section of this document for detailed specifications of each I/O point option. Note 2: All 0-30V analogue inputs have increased resolution over the range 0-6V (equivalent to...

Open the catalog to page 4
Model C2363A-0-0 Teleterm M3e - 5

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. SPECIFICATIONS COMMON TO ALL MODELS Input/Outputs All M3 RTU’s have 12 Input/Output Points (IOP configurable in software as analogue or digital, inputs or outputs. 0-30Vdc (software configurable to smaller ranges such as 1-5Volts) (See the table above for a matrix of available functions on each I/O Point.) < 0.15% of reading +6mV from 0 to 5.5V < 0.15% of reading +30mV from 5.5 to 30V 6mV from 0 to 5.5 Volts nominal (10 bits) 33mV from 5.5 to 30Volts nominal (10 bits) As a...

Open the catalog to page 5
Model C2363A-0-0 Teleterm M3e - 6

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. Type Asynchronous serial port Supports the following protocols as standard: • Conet/s • Modbus ASCII (Master or Slave) • Modbus RTU (Master or Slave). Baud Rate Maximum cable length Communication Standard Selected by the wiring to the DB9 connector Do not connect Rx Data (In) Tx Data (Out) Do not connect Ground Do not connect RTS (Out) CTS (In) Do not connect Rx Data + (In) Rx Data – (In) Do not connect Tx Data+ (Out) Ground Vcc Do not connect Do not connect Tx Data – (Out)...

Open the catalog to page 6
Model C2363A-0-0 Teleterm M3e - 7

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. Number of messages Network Port Only limited by the installed User program. (Consult factory for application advice). HSDPA (UMTS) mobile network Network Bands Remote Programming and Configuration Network compatibility Compatible with Telstra NextG(Australia) Remote mounted antenna connected via SMA connector on M3G. SMS’s can be sent and received by the user program. The Teleterm M3U allows remote dial-in for the purpose of configuration and program changes remotely....

Open the catalog to page 7
Model C2363A-0-0 Teleterm M3e - 8

TELETERM M3 Series Programmable RTU’s Model C2362A and C2363A Teleterm RTU’s with integrated communication ports. Operating Band Throughput Data Rate Special Radio Licence Requirements None. (operates in licence-free ISM band) 10 Frequency Hopping Sequences Transmit Power Outdoor Range (Line of Sight) Up to 10 km with dipole Up to 30 km with hi-gain antenna Receiver Sensitivity RPSMA Connector for external antenna Ordering Information ORDER CODE Teleterm M3G Programmable RTU with integral GSM/GPRS modem. Teleterm M3G Programmable RTU with 3G HSDPA/UMTS integral 3G HSDPA/UMTS modem (Telstra...

Open the catalog to page 8

All Omniflex catalogs and technical brochures