Series Gateways ODOT-S4E2 User Manual Modbus RTU to Modbus TCP/IP Protocol Converter Sichuan Odot Automation System Co., Ltd. 2017-12 Copyright©2017 All rights reserved by odot

Open the catalog to page 1
ODOT-S4E2 - 2

Revision records: Ownership information Without the consent of the copyright owner, the whole or part of this document do not be republished as paper or electronic document. Disclaimer This document is only used to assist readers for using products.The company is not responsible for loss or mistake because of using this dodument. The text and product described in this document is constantly developing and improving. Sichuan Odot Automation System Co., Ltd. has the right to modify this document without notifying users.

Open the catalog to page 2
ODOT-S4E2 - 4

1 Description 1.1 Function This product, developed by Sichuan Zero Automation System Co., Ltd., is a Modbus RTU to Modbus TCP/IP protocol converter based on market demand and years of experience. All the Modbus RTU/ASCII slave devices with RS485/RS422/RS232 interface can connect to Modbus TCP/IP network and communicate with TCP clients. Realize high speed data transmission by connecting the low speed serial device to the high-speed Ethernet.This protocol converter has two type working mode , "transparent transmission" and "mapping" , which can achieve the maximum system compatibility. 1.2...

Open the catalog to page 4
ODOT-S4E2 - 5

through network port. ♦ RS485 surge protection, internal terminal resistance and bias circuit enhance stability. ♦The packet sending interval can be adjusted freely, and the use is more flexible. ♦ Self diagnostic, slave devices status live monitoring. ♦ One push to rest button, restore factory setting. ♦ 35mm standard guide rail. ♦ EMC comply EN 55022:2010 & EN55024:2010 international standard. To make the product works better,please operate it in the range of preference parameter. All the related technical parameters are shown in ’’Table 1”. Table 1

Open the catalog to page 5
ODOT-S4E2 - 6

Ethernet parameter Working mode Transparent transmission mode, address mapping mode,Modbus TCP protocol Number of TCP connection Max. 5 Serial parameter Number of serial Serial communication RTU mode & ASCII mode mode Baud rate Checking mode Mapping mode protocol Function code Modbus buffer 3xxxx 区(input register):2048 Word 4xxxx 区(hold register

Open the catalog to page 6
ODOT-S4E2 - 7

supply: 9-36 W)C ling Temperature: -*0-85''-i*y. 5-55%RH (non-condensing) 2.2 Status in LED indicators description Power t stales I transmit status I receive status ,1 transmit slatuS ,1 revive status There are total 6 LED status indicators.The symbol definition and status indicators are shown in "Table 2”.

Open the catalog to page 7
ODOT-S4E2 - 8

2.3 Terminals definition Device wiring adoptslOPin 3.81mm gap Plug-in terminals, the terminal definition of RS485 interface are shown in "table 3”.

Open the catalog to page 8
ODOT-S4E2 - 10

2.4. Reset switch Click the reset button by the paper clips. When all lights flash once,it means successful reset and the technical parameters of the gateway are as follows:

Open the catalog to page 10
ODOT-S4E2 - 12

Serial Gateway ODOT-S2E2 Poww supply: 9-36 VDC Operating Temperature: -M-85C Humidity: 5-3S16RH (non-orwidonsing) Symbol description PWR Power status ctH EttieT"®1 status m ****££ RX’ 1#50,,a! transmitslaluS Va ^ive status 3 HOW TO USE THE PROTOCOL CONVERTER 3.1. The description of protocol converter 3.1.1. Serial working mode There are two types of working modes : Master mode and slave mode. When the serial port works in master mode, the serial port can connect up to 31 Modbus RTU/ASCII slave devices without relaying.This mode is mainly used for data communication between Modbus TCP master...

Open the catalog to page 12
ODOT-S4E2 - 13

slaves. When the serial port works in slave mode,the serial port can connect to a Modbus RTU/ASCII master device. This mode can be applied as follows: (1) Data Communication Between Modbus TCP Client and Modbus RTU/ASCII Master Station. (2) Data communication between Modbus RTU/ASCII masters. (3) Modbus TCP client and a Modbus RTU/ASCII master communicate with a Modbus RTU/ASCII slave at the same time. 3.1.2.Gateway working mode There are two types of working modes: transparent mode and mapping mode .When "Transparent" mode is in a factory setting without data cache nor editing the address...

Open the catalog to page 13
ODOT-S4E2 - 14

equipment working condition, 263 points in total. Access to the "system diagnostic” area can obtain the slave station's information and used to setting the disconnection alarm. The distribution of the data storage area and the scope of the address coding are shown in table 5. 3.1.4 System diagnostic area The diagnosis system is divided into two parts. The first part: The address 0x2000-0x200F is in total of 16 word that is 256 bits as the "slave station error indicator area”. The number 1-247 are respectively corresponding to slave stations 1-247and keep 248-256 bit number. When the error...

Open the catalog to page 14
ODOT-S4E2 - 16

The second part :Address 0x2010-0x2106 Word ,total 247 words, as "from the station status indicator" area. Reading the area could obtain the salve stations’ current working status, the data encoding format is as shown in Table 7.

Open the catalog to page 16
ODOT-S4E2 - 19

3.3.1 Communicate between Modbus TCP client and Modbus RTU/ASCII slave station 3.3.1.1. Application topology m (5PPLC)

Open the catalog to page 19
ODOT-S4E2 - 20

3.3.1.2.Transparent transmission mode configuration 1. Open configuration software "odot MGCC Config”, Right click the slave configuration page and select "Add Device",Add "ODOT-S4 E2”. 2.Double-click "ODOT-S4E2" or right-click "ODOT-S4E2", Select “common device attributes”, Set the gateway working mode to Transparent in the popup page.

Open the catalog to page 20
ODOT-S4E2 - 21

3. Double-click "COM1" , "COM2" ,"COM3" , "COM4"or right-click "COM1" , "COM2" ,"COM3" , "COM4" and click "Serial Properties", the "Serial Settings" window pops up. After setting the communication parameters, click the "OK" button to save and return. Take COM1 as an example. The meaning of each parameter is as follows: Operating mode: It is used to set up gateway as master station or slave station in the network. Default is master mode. Modbus protocol type: it's used to set up the gateway's protocol type of the network between the communication of the serial port and other connected...

Open the catalog to page 21

All ODOT Automation catalogs and technical brochures

  1. BOXIO 64

    4 Pages

  2. PLC

    59 Pages

  3. CN-8034

    2 Pages

  4. CN-8033

    2 Pages

  5. CN-8032

    2 Pages

  6. CN-8012

    2 Pages

  7. CN-8011

    2 Pages

  8. CN-8031

    2 Pages

  9. CT-7221

    17 Pages

  10. CT5800

    15 Pages

  11. CT4234

    20 Pages

  12. CT3804

    21 Pages

  13. CT-3713

    19 Pages

  14. CT3238

    19 Pages

  15. CT-3158

    19 Pages

  16. CT2718

    18 Pages

  17. CT2228

    18 Pages

  18. CT623F

    23 Pages

  19. CT-222F

    19 Pages

  20. CT-121F

    21 Pages

  21. ODOT-IOT02

    44 Pages

  22. ODOT-S7PPIV2.0

    31 Pages

  23. ODOT-PNM02

    31 Pages

  24. ODOT-IOT01

    79 Pages