Overview: The Nova Model 436 Tri-Gas Analyzer is designed for monitoring hydrogen (H2) purity and purging in hydrogen-cooled power generators. It provides continuous analysis of H2 purity and purge monitoring for generators and synchronous converters.
Applications: The analyzer is used for continuous analysis of H2 purity and purge monitoring in hydrogen-cooled generators.
Features: The analyzer includes isolated 4-20mA output, low H2 purity alarms, automatic calibration, serial output with data-logging, and an oil vapor filter assembly. It offers a bright digital readout and fast response time (T90 - 10 to 15 seconds).
Calibration: The analyzer uses three channels for calibration: Channel 1 uses air for zero and 100% H2 for span; Channel 2 uses 100% CO2 for zero and 100% H2 for span; Channel 3 uses 100% CO2 for zero and air for span.
Specifications: The detection method is a temperature-controlled thermal conductivity cell. It offers three ranges: 0-100% H2 in Air, 0-100% H2 in CO2, and 0-100% Air in CO2. The resolution is ±0.1% of gas measured, with accuracy and repeatability within ±1% F.S. The response time is 10-15 seconds to 90% step change. The ambient temperature range is 32-120°F (0-50°C).
Models: The analyzer is available in different configurations: 436N4N7, 436RMN7, and 436N7MC, with options for explosion-proof cabinets and general-purpose enclosures.
Output and Alarms: Standard output is 4-20 mA for 85-100% H2 in Air range, with optional isolated outputs for other ranges. Alarms for low H2 purity and detector failure are available, with adjustable set points.
Contact Information: Nova Analytical Systems is located in Niagara Falls, NY, USA, and Hamilton, ON, Canada. Contact details include phone numbers and email addresses for sales inquiries.
See more

Catalog excerpts

436 Series-1

436 SERIES TRI-GAS ANALYZER FOR MONITORING PURITY AND PURGING OF HYDROGEN COOLED POWER GENERATORS APPLICATIONS For continuous analysis of hydrogen (H2) purity and for purge monitoring of hydrogen-cooled generators and synchronous converters. FEATURES • One analyzer monitors all 3 gases for purity (Range 1) or purging (Ranges 2 and 3): • Range 1: 0-100% H2 in Air • Range 2: 0-100% H2 in CO2 • Range 3: 0-100% Air in CO2 • Bright digital readout • 4-20 mA isolated output for 85-100% of H2 in Air • Thermal-conductivity cell with high accuracy and repeatability, cannot be burned out. • Explosion-proof gas detector enclosure suitable for Class 1 Division 1 Group BCD rated areas • Fast response (T90 -10 to 15 secs) • Built in pressure regulator OPTIONS • Isolated 4-20mA output for any range selected • 2 levels of low H2 purity alarms & detector fail alarm • Automatic Calibration by microprocessor control available on N7MC configuration • Serial output with data-logging software • Oil vapor filter assembly NEMA 7 Gas Detector Cabinet Choice of Control Cabinet as follows: NEMA 4 Control Cabinet 19" Rack Mount Control Cabinet NEMA 7 Control Cabinet CALIBRATION • Channel 1 - Air for Zero, 100% H2 for Span • Channel 2 - 100% CO2 for Zero, 100% H2 for Span • Channel 3 - 100% CO2 for Zero, Air for Span NOVA ANALYTICAL SYSTEMS www.nova-gas.com Oil Vapor Filter Assembly - protects analyzer from sensor fouling caused by oil-vapors from power generator

 Open the catalog to page 1
436 Series-2

DESCRIPTION The Nova Model 436RMN7 Tri-gas analyzer is designed specifically for monitoring H2 purity in a power generator and to monitor the purging procedure during shut down. The analyzer can measure the following gases by switch selection: Range 1: 0-100.0% H2 in Air; Range 2: 0-100.0% H2 in CO2; Range 3: 0-100.0% Air in CO2. An isolated 4-20 mA recorder output is provided for the range of 85-100% H2 in Air. The Model 436 analyzer is typically divided into 2 sections which are electrically connected. The control section contains the main microprocessor board as well as the digital readout...