Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 1

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches

Open the catalog to page 1
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 2

Molded Case Circuit Breakers/Switches NOARK Ex9 Series - M Features Molded Case Circuit Breakers (M1-M6) NOARK Electric offers a complete range of Molded Case Circuit Breakers in six frame sizes: M1 - 150 A, M2 - 250 A, M3 - 400 A, M4 - 600 A, M5 - 800 A, and M6 - 1,200 A. Each frame size offers a range of interrupting voltage ratings from 240-690 Vac and 250-600 Vdc. The M series conforms to global standards that include UL 489, CSA C22.2 No 5 and IEC 60947-2. • • • • • • High-breaking capacity and a new patented arc extinguishing design New patented technology reduces the manual operating...

Open the catalog to page 2
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 3

Molded Case Circuit Breakers/Switches NOARK Ex9 Series - M Accessories • • • • Alarm Switch Auxiliary Contact Shunt Trip Under-Voltage Trip Handle Lock Mechanical Interlock Motor Operator Rotary Handle DIN Rail Plate Extended Rotary Handle Flange Handle Terminal Lugs Plug-In Base Rear Connection Kit Draw-Out Base Certifications • UL 489 Listed, File No. E355392 For: Molded Case Circuit Breaker, Alarm Switch, Auxiliary Contact, Shunt Trip, Under-Voltage Trip, Handle Lock, Mechanical Interlock, Motor Operator, Rotary Handle, Extended Rotary Handle, Plug-In Base, Rear Connection Kit and...

Open the catalog to page 3
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 4

Molded Case Circuit Breakers/Switches Product Selection Guide and Packaging M1-M6 Product Selection Guide M Frame Size Interrupting Rating Trip Unit Terminal Option Rate Code Neutral Protection Code ThermalMagnetic Electronic (M6 only) Blank: Standard MCCB (80% Rated) Blank: Neutral Pole without protection C: Neutral Pole with 100% protection P*: Plug-In R*: Rear Connection D*: Draw-Out M1M-M6M Product Selection Guide F† Frame Size Interrupting Rating Trip Unit Terminal Option Blank: Standard MCCB (80% Rated) L: Lug Line/Load Side Connection (Standard configuration for M1: 1 hole, M2: 1...

Open the catalog to page 4
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 5

Molded Case Circuit Breakers/Switches M1-M3 Specifications M1 Rated Current (A) Breaker Type Rated Voltage 50/60 Hz Interrupting Capacity (kA rms) 240 Vac Circuit Breaker Ratings UL 489 CSA C22.2 (kA rms) Vac 50/60 Hz 600 Vdc 3 Poles 220 / 240 Vac Circuit Breaker Ratings IEC 60947-2 Ultimate Breaking Capacity (Icu = 100% Ics) (kA rms) Current Rating (A) @ 104 ºF (40 ºC) A = Adjustable Thermal-Magnetic T = Thermal Trip Units (Fixed) F = Fixed M = Magnetic Accessories Alarm Switch Auxiliary Contact Shunt Trip Under-Voltage Trip Handle Lock Flange Handle Mechanical Interlock Motor Operator...

Open the catalog to page 5
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 6

Molded Case Circuit Breakers/Switches M4-M6 Specifications M4 Breaker Type Rated Voltage 50/60 Hz Circuit Breaker Ratings IEC 60947-2 Ultimate Breaking Capacity (Icu = 100% Ics) (kA rms) Circuit Breaker Ratings UL 489 CSA C22.2 (kA rms) Vac 50/60 Hz Current Rating (A) @ 104 ºF (40 ºC) A = Adjustable Thermal-Magnetic T = Thermal Trip Units (Fixed) F = Fixed M = Magnetic Accessories Alarm Switch Auxiliary Contact Shunt Trip Handle Lock Flange Handle Mechanical Interlock Motor Operator Handle Operators Terminal Cover and Kits Connection Bus Bar Connection Lug Line/Load Side Connection Plug-In...

Open the catalog to page 6
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 7

Molded Case Circuit Breakers/Switches M1-M6 Specifications M1-M6 Specifications M1 Impulse Withstand Voltage (Vimp) Operational Voltage (Ve) Utilization Category Mechanical Operating Cycles Electrical Operating Cycles Cable Connection Wire 167 ºF (75 ºC) Cu Wire Only AWG (mm2) M1-M5 Interrupting Polarity for DC Application 1 Pole * 2 pole in a 3 pole case

Open the catalog to page 7
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 8

Molded Case Circuit Breakers/Switches M1 Trip Unit M1 Adjustable Thermal, Fixed Magnetic M1 1 Pole • Fixed Magnetic: 150~1,500 A tripping current • Fixed Thermal: 15~150 A rated current M1 3 Poles • Fixed Thermal: 15-45A rated current • Adjustable Thermal: 50-150A rated current Adjustable: 0.8~1×In • Fixed Magnetic: 150~1,000 A tripping current • Adjustable Magnetic: 125~150 A rated current Adjustable:8860M142410514 5~10 x In M1 2 Poles • Fixed Thermal: 15~45 A rated current • Adjustable Thermal: 50~150 A rated current Adjustable: 0.8~1 x In • Fixed Magnetic: 150~1,500 A tripping current M1...

Open the catalog to page 8
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 9

Molded Case Circuit Breakers/Switches M2-M5 Trip Unit M2-M5 Adjustable Thermal, Adjustable Magnetic M2 1 Pole • Fixed Magnetic: 1,000~2,500 A tripping current • Fixed Thermal: 100~250 A rated current M2 2 Poles/3 Poles - M5 • Adjustable Thermal: 100~800 A rated current Adjustable: 0.8~1 x In • Adjustable Magnetic: 700~8,000 A tripping current Adjustable: M2 - 2 Poles/3 Poles 100~150 = 7~12 x In M2 - 2 Poles/3 Poles 175~250 = 5~10 x In M3/M4 225~600 = 5~10 x In M5 600~800=5~10 x In M2 - 1 Pole Fixed Thermal Overload Protection Fixed Magnetic Short Circuit Protection M2 - 2 Poles/3 Pole...

Open the catalog to page 9
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 10

Molded Case Circuit Breakers/Switches M6 Trip Unit Electronic Trip Unit These trip functions are available: L=Long-time Delay: Long-time Delay Protection Current; Long-time Delay Protection Time S=Short-time Delay: Short-time Delay Protection Current: Short-time Delay Protection Time I=Instantaneous Trip G=Ground Fault Protection Current: Short-time Delay Protection Time Neutral Protection: Long-time Delay, Short-time Delay, Instantaneous protection Frequency Selection available: 50 or 60 Hz Long-time delay protection current (IR): 8 specific setting (IR): OFF, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9,...

Open the catalog to page 10
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 11

Molded Case Circuit Breakers/Switches M1M-M6M Specifications MCP M1M Breaker Type Rated Voltage 50/60 Hz Vac Interrupting Capacity (kA rms) Circuit Breaker Ratings UL 489 CSA C22.2 (kA rms) Vac 50/60 Hz Circuit Breaker Ratings IEC 60947-2 Ultimate Breaking Capacity (Icu = 100% Ics) (kA rms) Magnetic Trip Units 220 / 240 Vac 380 / 415 Vac 660 / 690 Vac A = Adjustable T = Thermal F = Fixed M = Magnetic Accessories Alarm Switch Auxiliary Contact Shunt Trip Under-Voltage Trip Handle Lock Flange Handle Mechanical Interlock Motor Operator Handle Operators Terminal Cover and Kits Connection Bus...

Open the catalog to page 11
Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M - 12

Molded Case Circuit Protectors M1M-M3M Trip Unit Adjustable Magnetic • • • • Adjustable Magnetic Short Circuit Protection Adjustable Magnetic Short Circuit Protection Adjustable Magnetic Short Circuit Protec

Open the catalog to page 12

All NOARK Electric catalogs and technical brochures

  1. CCT51

    3 Pages

  2. Ex9SN

    4 Pages

  3. Ex9S32

    3 Pages

  4. Ex9M6M

    2 Pages

  5. Ex9M5M

    2 Pages

  6. Ex9M4M

    2 Pages

  7. Ex9M3M

    2 Pages

  8. Ex9M2M

    2 Pages

  9. Ex9M1M 3

    5 Pages

  10. Ex9CK Series

    5 Pages

  11. Ex9RD

    2 Pages

  12. Ex9C1222V7

    3 Pages

  13. Ex9M3

    5 Pages

  14. Ex9S32 Series

    16 Pages