1. Catalogs
  2. NOARK Electric, North America
  3. DC Molded Case Circuit Breakers Ex9 Series - M1PVS

DC Molded Case Circuit Breakers Ex9 Series - M1PVS

DC Molded Case Circuit Breakers Ex9 Series - M1PVS
1 / 13 PagesView full catalog

DC Molded Case Circuit Breakers Ex9 Series - M1PVS

Product catalog summary
Overview: The NOARK Electric M1PVS is a UL489B compliant DC Molded Case Circuit Breaker designed for photovoltaic systems. It offers current ratings from 15A to 80A with a breaking capacity of 10kA at 1000 Vdc. The breaker features thermal magnetic trip units for overload and short circuit protection and includes pre-installed jumpers for various system configurations.
Specifications: The M1PVS supports a working voltage of up to 1000Vdc and operates within an ambient temperature range of -20ºC to 50ºC. It has a mechanical life of 10,000 operations and an electrical life of 1,000 operations at 1000 VDC. The breaker is available in 3-pole configurations and is suitable for reverse-feed applications.
Features: Key features include factory-installed jumpers, compatibility with grounded and ungrounded systems, and a full line of internal and external accessories. The product is backed by a 5-year limited warranty.
Accessories: Available accessories include alarm switches, auxiliary contacts, shunt trips, under-voltage trips, handle locks, mechanical interlocks, motor operators, flange handles, and rotary handles. These accessories enhance the functionality and adaptability of the circuit breaker in various applications.
Certifications: The M1PVS is UL 489B listed (File No. E513573) and complies with CSA C22.2 NO. 305 standards.
Product Selection Guide: The guide provides details on jumper connection types, terminal options, and trip units. It emphasizes the importance of not altering factory-installed jumper configurations.
Dimensions and Weight: The dimensions vary slightly between models M1PVS-A/B and M1PVS-C/D, with weights of 1.50 kg and 1.659 kg respectively.
Trip Unit Details: The M1PVS features adjustable thermal overload protection for currents between 50A and 80A, and fixed magnetic short circuit protection with tripping currents ranging from 150A to 800A.
Mounting and Installation: The document provides detailed dimensions for mounting and installation, ensuring proper setup and integration into electrical systems.
Note: NOARK Electric reserves the right to make technical changes without prior notice. The document emphasizes the importance of adhering to the agreed particulars in purchase orders.
See more

Catalog excerpts

DC Molded Case Circuit Breakers Ex9 Series - M1PVS-1

Data Sheet DC Molded Case Circuit Breakers

 Open the catalog to page 1
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-2

Molded Case Circuit Breakers NOARK Ex9 Series - M1PVS Features The NOARK Electric M1PVS is a UL489B DC Molded Case Circuit Breaker available in current ratings of 15A to 80A with a breaking capacity of 10kA @ 1000 Vdc. Each unit is equipped with thermal magnetic trip units for protection of overload and short circuit in photovoltaic system. The M1PVS features a poles-in-series design and is equipped with preinstalled jumpers. Four jumper connection configurations are offered for grounded and ungrounded systems. Like all NOARK Electric products, the M1PVS is backed by a 5-year limited warranty....

 Open the catalog to page 2
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-3

Molded Case Circuit Breakers Product Selection Guide and Packaging M1PVS Product Selection Guide M Frame Size Photovoltaic Code Interrupting Rating Trip Unit Terminal Option Jumper Connection Type 1000VDC type in compliance with UL 4898 *Product equipped with factory installed jumpers NOARK takes no responsibility if the customer changes the jumper configuration in the field. Packaging Unit (LxWxH) L: Lug Line/Load Side Connection B: Jumper Connection B C: Jumper Connection C D: Jumper Connection D

 Open the catalog to page 3
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-4

Molded Case Circuit Breakers M1PVS Specifications M1PVS Rated Service Current Rated Service Voltage Short-circuit Interrupting rating @1000Vdc Trip Unit Ambient temperature Mechanical life Electrical life (operations @ 1000 VDC Dimensions (mm/in) Weight (with jumper) Suitable for Reverse-feed Applications Accessories Alarm Switch Auxiliary Contact Shunt Trip Under-Voltage Trip Handle Lock Flange Handle Rotary Handle Mechanical Interlock Motor Operator Terminations Connections Cable Selection Jumper Connection Type Connection A LOAD LOAD ungrounded system wiring ungrounded system wiring For both...

 Open the catalog to page 4
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-5

Molded Case Circuit Breakers Trip Unit M1PVS Adjustable Thermal, Fixed Magnetic 8860M142410511 • Fixed Thermal: 15~45 A rated current ℃ • Adjustable Thermal: 50~80 A rated current Adjustable: 0.8~1 x In • Fixed Magnetic: 150~800 A tripping current M1PVS Trip Unit lR Adjustable Thermal Overload Protection Trip Curves Fixed Magnetic Short Circuit Protection

 Open the catalog to page 5
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-7

Molded Case Circuit Breakers Dimensions Connection A Insulation board Jumper Circuit Breaker Phase barrier Phase barrier Insulation board Insulation board Jumper Insulation board Jumper Phase barrier Circuit Breaker Phase barrier Circuit Breaker

 Open the catalog to page 7
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-8

Molded Case Circuit Breakers Mounting Positions M1PVS Reverse Feed Allowed

 Open the catalog to page 8
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-9

Molded Case Circuit Breakers Accessories: Product Selection Guide Accessory Product Selection Guide AL Device Category Alarm Switch Auxiliary Contact Device Category Control Voltage Shunt Trip Under-Voltage Trip Device Category Handle Lock Mechanical Interlock Device Category Control Voltage

 Open the catalog to page 9
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-10

Molded Case Circuit Breakers Accessories: Product Selection Guide Accessory Product Selection Guide FH Flexible Shaft 4XA: NEMA 4,4X/ Standard Version 4XB: NEMA Type 4,4X/ Short Version Flange Handle Operating Mechanism for Flange Handle Device Category NEMA Degree NEMA Extended Rotary Handle (Through the Door) Shaft Cross-Section Shaft Cross-Section HOM: Handle Operating Mechanism Extended Handle Shaft

 Open the catalog to page 10
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-11

Molded Case Circuit Breakers Accessories: Dimensions AL21N/AX21N Alarm Switch/Auxiliary Contact Unit: in [mm] Mechanical Interlock Unit: in [mm] C Mechanical Interlock Shunt Trip/Under-Voltage Trip Unit: in [mm] Flange Handle Mechanism for M1PVS Unit: in [mm] Drilling Plate for Operating Mechanism Handle Lock Handle Lock Unit: in [mm] Motor Operator Unit: in [mm]

 Open the catalog to page 11
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-12

Molded Case Circuit Breakers Accessories: Dimensions EH External Rotary Handle for M1-M6 Unit: in [mm] (1) Rear screw mounting: Ø1.42 to Ø1.46(Ø31 to Ø37). Front clip mounting: Ø1.46(Ø37).

 Open the catalog to page 12
DC Molded Case Circuit Breakers Ex9 Series - M1PVS-13

NOARK Electric North America 2188 Pomona Blvd, Pomona Ca 91768 (626) 330-7007 na.noark-electric.com • [email protected] Note: NOARK Electric reserves the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. NOARK Electric nor any of its affiliates or subsidiaries shall be responsible or liable for potential errors or possible lack of information in this document. NOARK Electric reserves all rights in this document and in the subject matter and illustrations contained therein....

 Open the catalog to page 13
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.