PFP The compact lightweight
88Pages

{{requestButtons}}

Catalog excerpts

PFP The compact lightweight - 1

PFP Catalogue Package: assembled 2021-10-21 PFP 1-Phase BL130 Catalogue Ed. 2.4 - 2018-07-18(Upd.2021) PFP 3-Phase BL130 Catalogue Ed. 1.3 - 2018-10-11(Upd.2021) Corrigendum 2021 to PFP Catalogues - 2021-06-25 PFP 3-Phase BL178 Catalogue Ed.2.0 - 2021-10-21

Open the catalog to page 1
PFP The compact lightweight - 2

Compact and Lightweight The compact plug-fan, driven by a built-in external rotor motor, has taken a leading position in the market for fans intended for integration in air conditioning and ventilation equipment. Most other plug fan ranges, driven by external-rotor permanent-magnet motors are, comfortably compliant with the curfor products intended for installation and use within the EU. Nicotra Gebhardt has led this market with its high-end airfoil RLE plug fan, featuring the revolutionary EVO impeller in combination with external-rotor EC motors. The PFP range, combining advanced...

Open the catalog to page 2
PFP The compact lightweight - 3

Advanced Motor Technology Although incorporating advanced technical solutions, the PFP is conceived to provide, in a simple package, a competitive perfor- The PFP drive system draws its technology from the advanced sys- Purchase cost: • the PFP fan is engineered for fast-rate and cost• the PFP fan already incorporates the motor and an advanced driver: no need for additional and separate supplies. Installation cost: • no manpower is needed to assemble fan, motor and driver. The compact external-rotor motors use high-intensity neodymium magnets, reducing the size of the motors while, at the...

Open the catalog to page 3
PFP The compact lightweight - 4

The currently available PFP range covers fan sizes from 280 mm up to 500mm, with one size of on-board single-phase driver, having nominal input power of 1.35 kW. The range is receiving a considerable extension in 2018, with the release of the first 3-Phase driver, a compact 2.4 kW unit, which will then be followed by a further step in power, to 4.0 kW, by the end of the year. PFP: Performance range with 1.35 kW Single-phase integrated drivers, in production. Performance data referring to: Standard air density r= 1.20 kg / m3 Installation type "A": free inlet, free outlet PFP: Performance...

Open the catalog to page 4
PFP The compact lightweight - 5

The PFP fans, whichever size or motor variant, are available in 1. of motorized impeller and matching inlet nozzle, loose, for installation in the customer’s supporting structure. 2. Fully-assembled unit with the motor and impeller sustained on a supporting bracket, which holds the inlet nozzle. In both cases, the assembly of motor and impeller is dynamically single pressure probe, to allow the measurement of the volume four anti-vibration mounts, with horizontal axis, is currently under deve development.

Open the catalog to page 5
PFP The compact lightweight - 6

Advanced Operating Modes PFP models, have a maximum electrical input power of 1.35 kW and incorporate an advanced active input stage, providing power factor control (power factor is continuously adjusted to unity). The smart drivers can provide advanced functions, extending way beyond the simple speed control and safety monitoring. the use of a dedicated software for PC and an USB-RS485 interface cable: no need for any additional, plug-in hardware. for harmonic distortion, like those which often apply to data centres. speed setting, which can normally be assigned in three The resulting...

Open the catalog to page 6
PFP The compact lightweight - 7

Pressure Transducer Another group of selectable operating modes is providing PID control, using one of the analogue input channels for the measurement of a status variable with an external sensor, e.g. a value of pressure or temperature, or a concentration of CO2 in the air, which can be kept to a desired value The PFP drivers are provided with two separate analovoltage from an external transducer, and the second for an input from a potentiometer or from another external 0-10Vdc voltage source, providing the target value. As an alternative, the target value for the PID may also be set via...

Open the catalog to page 7
PFP The compact lightweight - 8

Update: The 6-10 character part-numbering system, used to assign the part numbers to the products shown in this table, was superseded, in 2019, by a new, 16-character structured coding system, and some of the A3 fan models have also been replaced by new designs, with the same performance but having a larger base-plate, for ease of installation. Please consult the Corrigendum 2021, for additional information on these changes to the standard PFP product range.

Open the catalog to page 8
PFP The compact lightweight - 9

Update: Since 2020, the IP protection grade of the PFP fan models with BL 130 motors was upgraded to IP55, according to IEC 60529, both with the motor running or stationary, under condition that the cable glands and the cover lid are properly secured, and that any unused cable gland is closed with the sealing-plug provided.

Open the catalog to page 9
PFP The compact lightweight - 10

Type: PFP A3-0280 1.35kW 1Ph Motor: 1416F0 Power: Poles: Voltage: Supply: Frequency: Capacitor: Protection Cl.: Insulation Cl.: Thermal prot.: Temp. Min: Temp. Max: Current Max: Performance data referring to: Standard air density = 1.20 kg / m3 Installation type "B": free inlet, ducted outlet Sound Power Levels shown are Inlet-side LWA(B,in+cas), A-weighted, in dBA Integral speed-control by On-board Integral Driver 1500 1400 Performance referred to the best efficiency duty point Static Efficiency Compl. with Reg. 327/11/EC: Tier II (2015) Overall Efficiency ( x Cc) [%]: 56.8 A Measurement...

Open the catalog to page 10
PFP The compact lightweight - 11

NOISE DATA WIRING DIAGRAM Note: This fan model was re-numbered 6PA0015ZZ0000000 Note: This fan model was replaced by a new mechanical design, identified as 6PA0035ZZ0000000 . Please consult the Corrigendum 2021 for additional details.

Open the catalog to page 11
PFP The compact lightweight - 12

Type: PFP A3-0315 1.35kW 1Ph Motor: 1416F0 Power: Poles: Voltage: Supply: Frequency: Capacitor: Protection Cl.: Insulation Cl.: Thermal prot.: Temp. Min: Temp. Max: Current Max: Performance data referring to: Standard air density = 1.20 kg / m3 Installation type "B": free inlet, ducted outlet Sound Power Levels shown are Inlet-side LWA(B,in+cas), A-weighted, in dBA Integral speed-control by On-board Integral Driver ErP Data acc. to Reg. 327/11/CE Performance referred to the best efficiency duty point Static Efficiency Compl. with Reg. 327/11/EC: Tier II (2015) Overall Efficiency ( x Cc)...

Open the catalog to page 12

All Nicotra Gebhardt catalogs and technical brochures

  1. RDP

    56 Pages

  2. DDMP

    72 Pages

  3. RLMEVO