The I-MUS Series is an Intelligent Modular UPS System designed to prevent single point failures through full redundancy of all units. It supports various configurations including 3Ph/3Ph, 3Ph/1Ph, 1Ph/3Ph, and 1Ph/1Ph, and can continue operation even if one or two input phases fail due to its AC Back-up technology.
Technical Specifications
  • Input/Output Power: Ranges from 20 KVA / 20 KW to 640 KVA / 640 KW.
  • Power Factor: Greater than 0.99.
  • Dimensions: Vary by model, with the largest being 3 x 600x2100x800 mm.
  • Weight: Starts at 24 Kg.
  • Operating Temperature: -10 to +40 °C.
  • Nominal Input Voltage: Options include 3 x 380 V / 220 V + N, 3 x 400 V / 230 V + N, 3 x 415 V / 240 V + N.
  • Voltage Tolerance: 70% Load 3 x 260 VAC / 150 V + N to 3 x 457 VAC + N Derating.
  • Frequency: 47 Hz to 63 Hz.
  • Voltage Stability: Static: ≤ ±1%; Dynamic: ±3%.
  • Efficiency: AC-AC efficiency ranges from 93% to 96% depending on load.
  • Battery: 204 Cells with a total of 408 VDC, VRLA type, with temperature compensation available.
  • Safety and Standards: Complies with EN62040-1-1-2003, EN60950-1:2001/A11:2004, and other relevant standards.
  • Protection Degree: IP20.
  • EMC Compatibility: Meets EN50091_2:1995 and other standards.
  • Operating Conditions: Recommended battery operating temperature is 15°C to 25°C, with a storage range of -30 °C to +70 °C and a maximum altitude of 1500m without derating.
See more

Catalog excerpts

I-MUS Series (Intelligent Modular UPS System)-1

I-MUS SERIES Introducing with Modular UPS system I-MUS Serisi (Intelligent Modular UPS System) is very different from current modular UPS systems with it’s specifications. New Intelligent modular UPS system prevents single point failure by having full redundancy of all units. i-mus modular UPS system is able to operate as 3Ph/3Ph, 3Ph/1Ph, 1Ph/3Ph and 1Ph/1Ph according to your requirements. When operating as 3Ph/3Ph; it can keep running normally whilst one or two input phases down due to it’s AC Back-up technology. Uninterruptable Power Supply & Data Center Infrastructure Solutions www.necron.com.tr/en | [email protected]

 Open the catalog to page 1
I-MUS Series (Intelligent Modular UPS System)-2

Technical specifications I-MUS SERIES Input/Output Power Power Factor Dimensions (WxHxD) Maximum Power Nominal Input Voltage Power Factor Maximum Power Voltage Stability Static : < = ± %1; Dynamic (load impact %0 - %100 and %100 - %0) : ± %3 Voltage Distortion Linear Load : < ± %2 / Non Linear Load : < ± %4 (EN62040-3-2001) Frequency OUTPUT Voltage Tolerance Number of Module Installed Frequency Tolerance Permissible unbalance Load Overload Capacity Free Running: ± 0,1% Synchronised With AC Input From 47 to 63Hz. Free Running Outside This Range For 3 Phase Operation 100% Each Phase Regulated Independently...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.