HTD series UPS

HTD series UPS

HTD series UPS

Product catalog summary
Overview
The HTD series UPS by Necron is designed with advanced high-frequency double conversion technology, enhancing component performance and reducing raw material usage and semiconductor count. This results in lower servicing time and cost of ownership. The UPS boasts high efficiency (>93%), a high input power factor (>0.99), and includes a built-in output isolation transformer to protect against power supply disturbances.
Technical Specifications
  • Input: Rated voltage options are 380V, 400V, or 415VAC with a voltage range of ±15% starting and ±20% working. The frequency is 50/60Hz with a range of ±5Hz and a power factor of ≥0.99.
  • Output: Voltage regulation is ±1%, with a pure sine wave waveform and a crest factor of 3:1. Total harmonic distortion is ≤1% for linear loads and ≤5% for non-linear loads.
  • Battery System: DC voltage is 600V (12V x 50pcs) with charger currents ranging from 16A to 50A depending on the model.
  • Efficiency: Operating efficiency is ≥93% in working mode and ≥98% in ECO mode.
  • Environmental: Operates in 0~95% RH at 0~40°C (non-condensing) with noise levels between 65dB and 75dB.
  • Physical: Dimensions and weight vary by model, with the largest model weighing up to 2380 kg and measuring 2380x860x1950 mm.
  • Management: Communication options include RS232, RS485, and dry contact, supporting various Windows operating systems. Optional SNMP for power management via web browser.
Standards and Compliance
The HTD series complies with IEC60664-1 for insulation resistance, EN62040-2 for EMI, and various IEC61000 standards for EMS, ensuring robust protection against electrical disturbances.
See more

Catalog excerpts

HTD series UPS-1

There is only one term to say “Powerful” HTD series UPS is equipped with advanced design criteria by using high frequency double conversion technology. It improves the performance of components, and minimizes the quantity of raw material and the number of semiconductors, thus HTD series reduces servicing time and cost of ownership. This UPS has high efficiency (>93%), input power factor (>0.99), and built-in output isolation transformer. The inverter transformer prevents the direct feed from the battery potential into the critical load, and provides a very high rejection ratio of the power supply disturbances (such as spike, surge, etc.). Uninterruptable Power Supply & Data Center Infrastructure Solutions www.necron.com.tr/en | [email protected]

 Open the catalog to page 1
HTD series UPS-2

Technical specifications Rated Voltage Rated Frequency Frequency Range Power Factor Total Harmonic Distortion (THDI) Bypass Voltage Range Voltage Regulation Synchronized with utility on AC mode; 50/60Hz ± 0.1% on battery mode Wavefrom OUTPUT Voltage Range Pure sine wave Crest Factor Total Harmonic Distortion (THDV) ≤ 1% (Linear load); ≤ 5% (Non-linear load) Transfer Time AC mode to battery mode 0ms, Inverter mode to bypass mode: 0ms, Inverter mode to ECO mode: 5-10ms Inverter Overload Capability 105%-110%: Transfer to bypass after 60mins; 111%-125%: Transfer to bypass after 10mins; 125%-150%:...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.