1. Catalogs
  2. ndb Technologies
  3. XDP-II Offline Partial Discharge Measuring Kit

XDP-II Offline Partial Discharge Measuring Kit

XDP-II Offline Partial Discharge Measuring Kit

XDP-II Offline Partial Discharge Measuring Kit

Product catalog summary
Overview
The XDP-II Offline Partial Discharge (PD) Test Kit by ndb Technologies is designed for measuring PD in medium and high voltage (MV/HV) equipment such as transformers, cables, and arrestors. PD diagnosis is crucial for assessing insulation quality and identifying design or handling issues, thereby enhancing network reliability and reducing operational costs.

Complementary Accessories
The kit includes a newly designed Capacitive Coupler with an embedded integrator module, a 200pC calibrator module, an AC line filter, high voltage cables, connectors, and other necessary tools. The design emphasizes durability and high-quality materials.

Advantages
  • Lightweight, portable, and user-friendly
  • Data analysis via XDP-Soft
  • Cost-effective solution
  • Graphic display of PD readings
  • Storage capacity for over 380 recordings
  • Simultaneous display in decibels (dB) and picocoulombs (pC)

XDP-II Instrument
The XDP-II system is central to the kit, offering quick measurements and ease of use. It features a unique picocoulomb mode for displaying dB and pC readings, and an embedded speaker for detecting PD presence. The instrument's versatility is enhanced by a wide range of accessories.

Technical Specifications
  • Operating temperature: -20 to 50°C (-4 to 122°F)
  • Maximal voltage: 50 kV AC / 50-60Hz
  • Bandwidth: 150kHz to 550kHz (-3dB), 140kHz to 980kHz (-6dB)
  • Sensitivity: <1.5 pC
  • Capacitance: 1 nF
  • Power supply: 12V / 50mA
  • Output impedance: 50 Ohms
  • Phase output: <1V for 50kV
  • Phase output impedance: 500 Ohm at 1mA

XDP-053 Capacitive Coupler Specifications
  • Dynamic Range: 60 dB
  • Sampling Frequency: 30 MHz
  • Data Storage: Over 380 recordings
  • Bandwidth: 300 kHz to 70 MHz
  • Operating Phase Signal Range: 50 to 700mVrms
  • Operating RF Signal Input Range: 380uV to 380mV
  • Sensitivity: 5pC, depending on DUT capacitance
  • Reference Signal Output: 3.4V
  • Clock: Real-time internal clock
  • Operating Temperature: -20 to 50°C (-4 to 122°F)
  • Storage Temperature: -20 to 50°C (-4 to 122°F)
  • Humidity: 0 to 95% non-condensing
  • Liquid Protection: Splashproof
  • Display: Backlit LCD screen
  • Autonomy: 7.5 hours
  • Batteries: NiMH, rechargeable
  • Charging: 3 hours
  • Dimensions: 203 x 114 x 51 mm (8 x 4.5 x 2 inches)
  • Weight: 860g
See more

Catalog excerpts

XDP-II Offline Partial Discharge Measuring Kit-1

Offline Partial Discharge Measuring Kit This Partial Discharge measuring kit provides you with the easiest way to measure PD in a variety of MV/HV equipment such as transformers, cables, arrestors, couplers, etc... Partial Discharge diagnosis has been established as the most convincing technique for the evaluation of the insulation quality of MV/HV apparatus. Design, manufacturing or handling problems can be quickly identified using Partial Discharge testing and then improve design, network reliability and reduce operation cost by installing reliable components. XDP-II INSTRUMENT ADVANTAGES Light, portable and easy to use Data analysis with XDP-Soft Cost effective Graphic display of the PD readings Can store over 380 recordings Simultaneous display in dB and pC The well-established XDP-II PD measuring system is the heart of this cutting edge diagnosis kit. It allows quick measuring, simplicity of use, graphic display of the signal while staying portable. The XDP-II is used with its unique picocoulomb mode that displays the dB level as well as the pC reading. The embedded speaker allows the user to quickly determine the presence of Partial Discharge in the equipment under test. A great variety of accessories makes the XDP-II a versatile instrument that allows many more applications. COMPLEMENTARY ACCESSORIES Also included in the kit is our new design of the Capacitive Coupler where the integrator module is now embedded. Its refreshed design is not only good looking, it is also well made with high quality materials for years and years of service. Also included are a 200pC calibrator module, an AC line filter, high voltage cables and connectors and all other necessary tools. XDP-II Offline PD test kit ndb Technologies inc. • 1405 St-Jean-Baptiste, office 111 • Quebec (QC) G2E 5K2 - Canada • Tel: 1(418)877-7701 Fax: 1(418)877-7787 Email: [email protected]

 Open the catalog to page 1
XDP-II Offline Partial Discharge Measuring Kit-2

XDP-II TECHNICAL SPECIFICATIONS Dynamic Range Sampling Frequency Data Storage Operating Phase Signal Range (50 to 60Hz) Operating RF Signal Input Range Reference Signal Output (REF) Real-time internal clock Operating Temperature Storage Temperature Liquid Protection NiMH, rechargeable XDP-II instrument XDP-053 CAPACITIVE COUPLER TECHNICAL SPECIFICATIONS Operation temperature Power supply Output impedance Phase output Phase output impedance Maximal voltage ndb Technologies inc. • 1405 St-Jean-Baptiste, office 111 • Quebec (QC) G2E 5K2 - Canada • Tel: 1(418)877-7701 Fax: 1(418)877-7787 Email: [email protected]...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.