Application Scope of Use
The HVT 300-DP Failsafe Busbar Symmetry Monitor is crucial for monitoring busbar symmetry in processes like hydrogen electrolysis and Chlorine-Alkali processes. It ensures efficient, safe, and reliable hydrogen production by maintaining even current distribution among electrolyzer cells, preventing efficiency loss and safety risks such as local overheating. It is also applicable in battery testing and high power supplies.

Safety Features
The device features comprehensive self-monitoring and diagnostic functions. It supports the creation of a safety loop using diagnostic relays REL3/REL4, with configurable safety outputs available through REL1/REL2 or a 4…20mA analog output.

Main Benefits
  • Failsafe voltage monitoring
  • Simple software configuration via USB or Modbus RTU
  • Measurement range of +/- 250V DC
  • Redundant architecture
  • Robust design with high dielectric strength
  • SIL2 certification according to IEC/EN 61508
  • Two individual safety outputs
  • LED status indicators for Power, Error, and Alarm
  • 10-year proof test interval

Safety Properties FMEDA
The device is categorized as SIL 2, Type B, with a Hardware Fault Tolerance (HFT) of 0, Safe Failure Fraction (SFF) of 95%, and Diagnostic Coverage (DC) of 89%. It has a safe failure rate of 331 FIT and a dangerous failure rate of 362 FIT.

Technical Data
  • Certificate: SIL 2 according to IEC 61508
  • Measurement range: +/- 250 VDC
  • Input Resistance: 12 MΩ each channel
  • Analog Output: 0/4…20 mA, Max 500 Ω at 22mA, Accuracy < 0.5%
  • Contact outputs: Normally Open, Max 62.5 VA / Max 30W, Max 125VAC/110VDC, Max. 1A
  • Status LEDs: Power (Green), Error/SIL Alarm (Red), REL1/REL2 (Yellow)
  • USB Interface: USB 2.0
  • RS485 Interface: Half duplex, 9600 bps, Device Address 1-248
  • Supply: 24VDC (20…30VDC), Max. 1.9W
  • Temperature: Operating -10°C to +60°C, Storage/Transport -20°C to +70°C
  • Humidity: 10% to 90% r.H no condensation
  • Max. operating altitude: <2000m above mean sea level
  • Temperature Coefficient: <0.01%/K (max), <0.005%/K (typical)
  • Galvanic isolation: 4.3 kV AC test voltage
  • Overvoltage category: CAT II: 1000V, Pollution Degree 2
  • PCB Material: FR4
  • Housing Material: Polyamide
  • Protection Class: IP20
  • Flammability: UL94 V0
  • Mounting type: 35mm DIN rail
See more

Catalog excerpts

Difference Voltage Transmitter HVT 300-DP-1

w Your safe choice HVT 300-DP Failsafe Busbar Symmetry Monitor for +/-250 V Application Monitoring the busbar symmetry is a safety-relevant task for different processes. For instance, in hydrogen electrolysis it is crucial for optimizing the efficiency, safety, and reliability of the process, as well as for ensuring consistent and high-quality hydrogen production. Busbars distribute electrical current to the electrolyzer cells, which are responsible for the hydrogen generation process. If the busbar symmetry is not maintained, it can lead to uneven distribution of current among the cells. This imbalance can result in reduced efficiency and performance of the electrolyzer, leading to suboptimal hydrogen production or even safety risks like local overheating. The HVT 300-DP is often used in Chlorine-Alkali processes to proactively detect cell ruptures, leakages or insulation faults. Scope of use Battery Testing High power supplies Chlorine Alkaline Electrolysis Safety Features Featuring a design approach that involves thorough self-monitoring, the HVT 300-DP provides a wide range of diagnostic functions. In order to create a safety loop, the desired output must be evaluated in conjunction with one of the two diagnostic relays REL3/REL4. This way, two individually configurable safety outputs can be created, for which either the relays REL1/REL2 or the 4...20mA analog output are available. HVT 300-DVl Shunt current Measurement HVT 300-DP Balance Voltage Measurement Voltage Monitor Voltage Monitor

 Open the catalog to page 1
Difference Voltage Transmitter HVT 300-DP-2

w Your safe choice Main Benefits - Failsafe voltage monitoring - Simple software configuration via USB or Modbus RTU - +/- 250V DC measurement range - Redundant architecture - Robust design with high dielectric strength - SIL2 according to IEC/EN 61508 - Two individual safety outputs - LED status: Power, Error, Alarm - 10-year proof test interval Technical Data Safety Properties HVT 300-DVj Shunt current Measurement HVT 300-DP Balance Voltage Measurement Voltage Monitor Voltage Monitor

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.