1. Catalogs
  2. MJK
  3. Pumpestyring_701P_Datasheet_1211

Pumpestyring_701P_Datasheet_1211

Pumpestyring_701P_Datasheet_1211

Pumpestyring_701P_Datasheet_1211

Product catalog summary

Overview

The Pump Control Unit 701P is a compact device designed for level control of either one pump with one level alarm or two pumps operating alternately. It is housed in an M36 enclosure suitable for DIN rail mounting and can be supplied either as a standalone unit or complete with sensor and cable strain relief.

Functionality and Features

  • Controls pump operation based on liquid level measurements.
  • Supports one pump with one alarm or two pumps with adjustable levels.
  • Signal amplification from connected pressure transmitters to a level-proportional output.
  • Calibration performed from the front panel using a voltmeter connected to test terminals, where 1 meter corresponds to 1 Volt.

Sensors (Pressure Transmitters)

Two types of hydrostatic pressure transmitters are available for use with the 701P:

  • Type 7060: Polypropylene housing, suitable for wastewater and sludge measurement.
  • Type 7070: Acid-resistant stainless steel housing with small diameter, intended for clean liquids such as water boreholes.

Measurement ranges available: 0–3 m, 0–10 m, and 0–30 m.

Technical Specifications

ParameterSpecification
Measurement Range4–20 mA corresponding to 0–3 m, 0–10 m, or 0–30 m
Power Supply220–240 V AC or 110–130 V AC
Operating Temperature-20 to 60 °C
Input SignalFrom pressure transmitter (4–20 mA)
Accuracy±1.5%
Outputs2 relays with potential-free changeover contacts, 250 V, 4 A resistive, max 100 VA inductive
OperationFront panel control
Dimensions (HxWxD)86 x 69 x 58 mm
Enclosure RatingIP 22

Pressure Transmitter Specifications

ParameterType 7060Type 7070
Measurement Range0–3 m, 0–10 m, 0–30 m0–3 m, 0–10 m, 0–30 m
Output2-wire, 4–20 mA2-wire, 4–20 mA
Accuracy±0.5% of range±0.5% of range
Operating Temperature-10 to +60 °C-10 to +60 °C
DimensionsØ 60 x 140 mmØ 22 x 150 mm
MaterialHousing in polypropylene, membrane in acid-resistant stainless steel (AISI 316L)Housing and membrane in acid-resistant stainless steel (AISI 316L)
Cable2 x 0.5 mm², length 12 m (35 m for 0–30 m version), extendable2 x 0.5 mm², length 12 m (35 m for 0–30 m version), extendable
MountingSuspended with supplied cable strain reliefSuspended with supplied cable strain relief
Enclosure RatingIP 68, waterproof, max 3 barIP 68, waterproof, max 3 bar

Applications

The 701P pump control unit is used for level measurement and control in tanks, containers, and boreholes. Typical applications include pump stations, wastewater treatment plants, waterworks, and process and food industries.

Ordering Information

  • 201950: Pump Control 701 without transmitter
  • 201955: Pump Control 701 0–3 m with type 7060 transmitter
  • 201956: Pump Control 701 0–10 m with type 7060 transmitter
  • 201957: Pump Control 701 0–30 m with type 7060 transmitter
  • 202071: Pump Control 701 0–3 m with type 7070 transmitter
  • 202072: Pump Control 701 0–10 m with type 7070 transmitter
  • 202073: Pump Control 701 0–30 m with type 7070 transmitter

Manufacturer Contact

MJK Automation A/S
Byageren 7
DK-2850 Nærum, Denmark
Tel: (+45) 45 56 06 56
Fax: (+45) 45 56 06 46
Email: [email protected]
Website: www.mjk.com

See more

Catalog excerpts

Pumpestyring_701P_Datasheet_1211-1

Pumpestyring 701P Pumpestyring 701P er en kompakt enhed for niveaustyring af 1 pumpe og 1 niveaualarm eller 2 pumper i alternerende drift. Pumpestyring 701P leveres i M36 hus for DIN-skinne montage. Pumpestyring 701P leveres enten separat eller komplet med sensor og kabela­ ast­ ing. fl n Som sensor til Pumpestyring 701P leveres tryktransmit­er type 7060 eller type 7070. t • Pum­ estyring 701P le­ eres med hy­ rosta­ p v d tisk tryktran­ mitter med må­e­ m­ åde på 3, s l o r 10 eller 30 m. • Pum­ estyring 701P kali­ reres fra for­ la­ p b p den. Ind­ til­ings­ ær­ ierne af­læses på et s l v d voltme­er, som tilsluttes test-bøs­ ingerne. t n På test­ øs­ in­ er­ e svarer 1 m til 1 Volt. b n g n • Tryktra­ smitter 7060 frem­ tilles i po­ypro­ n s l pylen og er vel­ gnet til må­ing i spilde­ and e l v og slam. • Tryktransmitter 7070 er af syre­ast stål med f lille udvendig diame­er og anvendes til rene t væsker, f.eks. i vand­ orin­ er. b g Pumpestyring 701P finder anvendelse til måling og styring af niveauer i tan­ e, beholdere k og boringer. Pum­ esty­ ing 701P an­ endes til p r v styring af pumper i pum­ estationer, rensean­ p læg, vand­ ærker og proces- og føde­ are­ndu­ v v i strier. Generelt anvendes pum­ estyring 701P til styp ring af 1 pumpe med 1 alarm eller 2 pumper mellem ju­ térbare ni­ eau­ r. s v e I 701P elektronikenheden forstærkes signalet fra den tilsluttede tryktrans­ itter til et signal m pro­ ortionalt med niveauet. Det ni­ eau­ ro­ p v p portionale sig­ al anvendes til ind­ tilling af n s værdi­ r for start og stop af pumpen og e niveaualarmen. Pumpestyring 701P Måleområde: 4 - 20 mA (0 - 3 m / 0-10 m / 0 - 30 m) Forsyning: 220 - 240 V AC eller 110 - 130 V AC Temperatur: - 20 … 60 °C Indgangssignal: Fra tryktransmitter (4 - 20 mA) Nøjagtighed: ± 1,5 % Udgange: 2 relæer med potentialfri skiftekontakt. 250 V, 4 A ohmsk., maks. 100 VA induktiv Betjening: Fra forplade Dimension: 86 x 69 x 58 mm (h x b x d) Kapsling: IP 22 Da vores produkter løbende udvikles, forbeholder vi os ret til ændringer i mål og specifikationer.

 Open the catalog to page 1
Pumpestyring_701P_Datasheet_1211-2

Tryktransmitter 7060 eller 7070 M ­ åleområder: 0 - 3 m med tryktransmitter 7060 - 1413 eller 7070 - 1413 0 - 10 m med tryktransmitter 7060 - 1423 eller 7070 - 1423 0 - 30 m med tryktransmitter 7060 - 1433 eller 7070 - 1433 Udgang: 2-tråds, 4 - 20 mA Nøjagtighed: ±0,5 % af måleområde Temperatur: -10 … +60 °C Dimension: Type 7060: ∅ 60 x 140 mm Type 7070: ∅ 22 x 150 mm Materiale: Type 7060: Hus i PP, membran i syrefast stål (AISI 316L) Type 7070: Hus og membran i syrefast stål (AISI 316L) Kabel: 2 x 0,5 mm2, længde 12 m (7060 / 7070-1433 dog 35 m), kan for­æn­ es. l g Montering: Hænges i medfølgende...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.