IAC-I-03

IAC-I-03

IAC-I-03

Product catalog summary
Overview: The IAC-I-03 is a robust accelerometer designed for industrial applications, providing a 4-20 mA output suitable for direct connection to standard control and measurement equipment such as PLCs and panel meters. It features a compact and rugged design with IP67 protection grade, ensuring durability in harsh environments.
Properties:
  • 3-axis measurement capability.
  • Embedded 4-20 mA signal conditioning.
  • Galvanically isolated to prevent electrical interference.
  • Protected against false polarization.
Specifications:
  • Output/Channel: 4-20 mA output range, supply voltage of 12-30 VDC, measuring range of ±2g or ±6g, sensitivity of 3.20 mA/g (±2g range) or 1.07 mA/g (±6g range).
  • Frequency Limits: Lower frequency limit at 0 Hz (DC), upper 3 dB frequency limit options of 100, 250, 500, or 1000 Hz.
  • Accuracy: Non-linearity of ±0.5% F.S., residual noise < 50 µg/√Hz, transverse sensitivity < 5%.
  • Environmental Characteristics: Operating temperature range from -20 to 85°C (-4 to 185°F), non-operating range below -40 or above 85°C, temperature coefficient of sensitivity ±0.01%/°C, temperature drift of zero point ±0.05 mg/°C.
  • Mechanical Data: Weight varies by model, case material options include stainless steel or aluminum, mounting via 3.2 mm diameter holes.
Electrical Connections:
  • Cable Gland Model: Uses a 5 x 0.25² cable for X, Y, Z axis outputs and sensor supply inputs.
  • M12 Connector Model: Provides 4-20 mA current outputs for X, Y, Z axes, with +24VDC and 0VDC sensor supply inputs.
Ordering Information: The product can be customized based on low pass filter frequency, cable length, casing material (aluminum or stainless steel), and measuring range (±2g or ±6g).
See more

Catalog excerpts

IAC-I-03-1

BLOCK DIAGRAM 3 axes Suited for direct connection to standard control and measurement equipment, e.g. PLCs or panel meters Embedded 4..20mA signal conditioning Galvanically Isolated Protected against false polarization Compact and rugged design Protection

 Open the catalog to page 1
IAC-I-03-2

DIMENSIONS – Cable Gland Model DIMENSIONS – M12 Connector Model MOUNTING ACCESSORIES See “ IAC – Accelerometer Accessories data sh

 Open the catalog to page 2
IAC-I-03-3

SPECIFICATIONS – ALL MODELS Output Range Supply Voltage Measuring Range Lower frequency limit Upper 3 dB freguency limit Residual noise Transverse Sensitivity Destruction limit Operationg temperature Range ENVIRONMENTAL CHARACTERISTICS Temperature coefficient of sensitivity  0.01 % /°C Temperature drift of zero point Protection grade Case Material Stainless Steel or Aluminium Weight Without Cable (g) MECHANICAL DATA Stainless Steel Casing AISI316 Grade (e.g. for offshore/marine environment) Aluminum (MIL-A-8625 Type II coating) ELECTRICAL CONNECTIONS - Cable Gland Model Signal X sensing Sensor...

 Open the catalog to page 3
IAC-I-03-4

Cable Gland Cable Connection Stainless Steel Cable Length

 Open the catalog to page 4

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.