video corpo

M2AS

M2AS

M2AS

Product catalog summary
Overview: The M2AS Super-mini Signal Conditioners Mini-M Series is a DC alarm device featuring a DPDT relay output, adjustable via thumbwheel switches. It is designed for various alarm applications, providing latching or non-latching outputs and adjustable deadbands.
Specifications:
  • Input Options: Current (4-20 mA DC) and Voltage (0-10 V DC, 0-5 V DC, 1-5 V DC) with specified input resistances.
  • Alarm Output: Configurable for high or low alarms with options for coil energized or de-energized at alarm.
  • Delay Times: On delay time options range from 0.05 to 10 seconds; power on delay time options range from 1 to 4 seconds.
  • Relay Type: Standard or enclosed type.
  • Power Input: Options for AC (100-240 V) and DC (24 V, 11-27 V, 110 V) with specified operational voltage ranges.
  • Options: CE marking, various coatings, and terminal screw materials.
General Specifications:
  • Construction: Plug-in with M3 screw terminals.
  • Housing: Flame-resistant resin.
  • Isolation: Input to output to power.
  • Setpoint Adjustments: 0-99% via thumbwheel switches.
  • Deadband: 1-99% adjustable.
  • LED Indicators: Red LED for coil energized status.
Input and Output Specifications:
  • DC Current: Shunt resistor attached.
  • Relay Contact Ratings: 120 V AC @5 A, 240 V AC @2.5 A, 30 V DC @5 A.
  • Maximum Switching Power: 600 VA or 150 W.
Installation and Performance:
  • Power Consumption: Approx. 3-5 VA for AC, 3 W for DC.
  • Operating Conditions: Temperature -5 to +55°C, Humidity 30 to 90% RH.
  • Mounting: Surface or DIN rail.
  • Setpoint Accuracy: ±0.5%.
  • Trip Point Repeatability: ±0.05%.
Standards and Approvals:
  • EU Conformity: EMC Directive, Low Voltage Directive, RoHS Directive.
  • Insulation: Reinforced and basic insulation for input/output to power.
Functions:
  • High and Low Alarms: Relay trips when input exceeds or falls below setpoint.
  • Delay Times: Configurable ON and Power ON delay times.
  • Latching Output: Requires reset control to return to untripped condition.
See more

Catalog excerpts

M2AS-1

Functions & Features • Provides a DPDT relay output at a preset DC input level • Thumbwheel switch setpoint adjustments • Adjustable deadband • Latching or non-latching output • Relays energized or de-energized at tripped condition Typical Applications • Various alarm applications Super-mini Signal Conditioners Mini-M SeriesDC ALARM (thumbwheel switch adjustment; DPDT output)MODEL: M2AS-[1][2][3][4][5]-[6][7]ORDERING INFORMATION • Code number: M2AS-[1][2][3][4][5]-[6][7] Specify a code from below for each of [1] through [7]. • Specify the specification for option code /Q (e.g. /C01/S01) Note: Must be used with its socket. NOT installable to a multi-unit installation base. (e.g. model: M2BS-16) 1: Hi (coil energized at alarm) 2: Hi (coil de-energized at alarm) 3: Lo (coil energized at alarm) 4: Lo (coil de-energized at alarm) N: Standard type S: Enclosed type M2: 100 - 240 V AC (Operational voltage range 85 - 264 V, 47 - 66 Hz) (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) R2: 11 - 27 V DC (Operational voltage range 11 - 27 V, ripple 10 %p-p max.) (Select '/N' for 'Standards & Approvals' code.) (Operational voltage range 85 - 150 V, ripple 10 %p-p max.) Standards & Approvals (must be specified) /N: Without CE /CE: CE marking Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to our web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating /C04: Polyolefin coating TERMINAL SCREW MATERIAL /S01: Stainless steel

 Open the catalog to page 1
M2AS-2

MODEL: M2AS GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3 screw terminals (torque 0.8 N·m) Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: Input to output to power Overrange input: -14 to +113.5 % When the relay’s untripped point relative to the preset alarm setpoint and deadband is out of this range, the relay remains latched. Setpoint adjustments: Thumbwheel switches (front); 0 – 99 % independently; 1 % increments Deadband (hysteresis) : Thumbwheel switches (front); 1 – 99 % independently; 1 % increments...

 Open the catalog to page 2
M2AS-3

MODEL: M2AS EXTERNAL VIEW Output Setpoint Adj. Deadband Adj. Output Monitor LED Reset Control EXTERNAL DIMENSIONS unit: mm [inch] 6 [.23] DIN RAIL 35mm wide • When mounting, no extra space is needed between units. TERMINAL ASSIGNMENTS unit: mm [inch] INPUT RESISTOR (model: REM2) Input shunt resistor attached for current input.

 Open the catalog to page 3
M2AS-4

MODEL: M2AS SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM ■ Relay Protection • AC Powered THUMBWHEEL SWITCHES Inductive Load (Coil) RESET CONTROL • DC Powered Inductive Load (Coil) Diode, Varistor or CR Circuit *Input shunt resistor attached for current input. FUNCTIONS ■ HIGH ALARM: When the signal input exceeds the preset setpoint, the relay provides a tripped condition. • Hi Alarm ■ POWER ON DELAY TIME: The relay does not provide a tripped condition for a duration of the preset Power ON Delay Time (TDP) after the power supply is turned on, even when the signal input is in an alarm range. Input...

 Open the catalog to page 4
M2AS-5

MODEL: M2AS Specifications are subject to change without notice.

 Open the catalog to page 5

All MG Co., Ltd. catalogs and technical brochures

  1. M2DNY

    3  Pages

  2. M2CDS

    4  Pages

  3. M2CA

    3  Pages

  4. M2BW

    2  Pages

  5. M2BS-16

    5  Pages

  6. M2BS2

    5  Pages

  7. M2BS-16

    5  Pages

  8. M2BD

    7  Pages

  9. M2BC

    8  Pages

  10. M2AVS

    4  Pages

  11. M2AP

    4  Pages

  12. M2AMS

    4  Pages

  13. M2ADS

    4  Pages

  14. M2AC

    3  Pages

  15. CNT

    2  Pages

  16. CLSE

    2  Pages

  17. CLSB

    3  Pages

  18. MCN-CON

    1  Page

  19. COP-US

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.