Overview: The MPI-C series is a multichannel electronic recorder designed for versatile data logging and control applications. It features 16 universal analog inputs, 4 digital inputs, 16 math channels, and 8 relay outputs. The device supports advanced data logging with a 2 GB internal flash memory and offers multiple communication options including Ethernet and RS-485.
Specifications:
  • Analog Inputs: 16 universal inputs compatible with RTD sensors (Pt-100, Ni-100), thermocouples (J, K, T, etc.), and transmitters with 4-20mA or 0-20mA outputs. Inputs are galvanically isolated.
  • Digital Inputs: 4 inputs with a measurement frequency range of 0.001 Hz to 10 kHz, capable of pulse counting and binary signal tracking.
  • Math Channels: 16 channels supporting operations like addition, subtraction, multiplication, division, and square roots.
  • Relay Outputs: 8 solid-state relays for alarm or control functions, each supporting up to 4 alarm thresholds.
  • Display: Graphic LCD TFT color display with dimensions of 43.8 mm x 77.4 mm and a resolution of 272 x 480 px.
  • Communication: Ethernet port with Modbus TCP and Web Server capabilities, RS-485 port with ASCII and Modbus RTU protocols, optional GSM module for SMS notifications.
  • Data Logging: Internal 2 GB memory with encrypted checksum protection, recording frequency adjustable from 5 seconds to 24 hours.
Technical Data:
  • Front Panel: Features a membrane keyboard with 7 or 19 buttons depending on the model.
  • Input Types: Supports a wide range of sensor types with specific measurement accuracies and characteristics.
  • Binary Inputs: Configurable for OC/contact or voltage input with specific thresholds and resistances.
  • Outputs: Solid-state relays with a maximum load current of 100 mA and voltage of 60 V.
  • RS-485 Port: Supports multiple transmission rates and protocols with short-circuit and thermal protection.
  • USB Port: Front panel USB 1.1 port with IP54 protection for data transfer.
  • Ethernet Port: Supports Modbus TCP and other protocols with RJ-45 connection.
  • Power Supply: Different supply voltages for MPI-C, MPI-CL, and MPI-CN models with specific power consumption details.
  • Mechanical Dimensions: Varies by model (MPI-C, MPI-CL, MPI-CN) with specific dimensions and protection classes.
Additional Features:
  • Advanced user and password management system.
  • Event log and register of authorized activities.
  • Dedicated software for visualization of measurement results.
See more

Catalog excerpts

MPI-CN-1

MPI-C MPI-CL MPI-CN MULTICHANNEL ELECTRONIC RECORDER 16 analog channels, 4 digital channels, 16 math channels 16 universal analog inputs 4 digital inputs 16 math channels 8 relay outputs for alarm or control functions 2 GB internal flash memory, advanced data logging Graphical color LCD TFT display USB port on the front panel with IP54 protection Ethernet port: Modbus TCP protocol, Web Server RS-485: ASCII and Modbus RTU protocol GSM module (option) 16 UNIVERSAL ANALOG INPUTS FOR TEMPERATURE SENSORS OR OTHER TRANSMITTERS:  RTD sensors type Pt-100 and Ni-100 and its multiples (such as Pt-200).  TC sensors J, L, M, T, U, E, N, B, R and S.  transmitters with output in the current loop 4-20mA or 0-20mA standard.  transmitters with an output resistance in the range 0 ... 5000 Ω.  converters with voltage output of -0.8 V ... 0.8 V. The inputs are galvanically isolated from each other. Digital filter with selectable time constant allows the measurement of noisy signals. 4 DIGITAL INPUT:  Measurement frequency range 0.001 Hz to 10 kHz.  Pulse counting.  Tracking and recording a binary signal (short or open circuit). 16 CALCULATED VALUES:  Available functions: addition, subtraction, multiplication, division, square roots on measured or calculated channels. ARCHIVING RESULTS:  Writing to internal 2GB memory.  Protected files with the encrypted checksum.  Recording frequency from 5 s to 24 h; possible to define two switched frequ

 Open the catalog to page 1
MPI-CN-2

8 RELAY OUTPUTS, THRESHOLD ALARM-CONTROL:  8 solid-state relay outputs rated at 0.1 A / 60 V.  Up to 4 alarm thresholds for each channel. COMMUNICATION WITH THE MASTER SYSTEM:  RS-485 port, ASCII and Modbus RTU protocol.  Ethernet port, Modbus TCP, Web Server.  GSM module (option), SMS notification about alarms, counters and current values. OTHER FEATURES:  USB port on the front panel for data and setting transfer.  Counters for each flow value channel (measured or calculated).  Tracking the value of minimum, maximum and average for each of the measured and calculated channel.  Advanced...

 Open the catalog to page 2
MPI-CN-3

TECHNICAL DATA Type of display: Reading field size: LED signal diodes : Keyboard: Number of inputs: Galvanic separation between channels: Galvanic separation from supply voltage: FRONT PANEL Graphic LCD TFT 272 x 480 points. 43,8 mm x 77,4 mm 3 two-colour, green-red Membrane, 7 or 19 buttons (MPI-CN and MPI-CL) ANALOG INPUTS 16 multiplexed with signal relays Yes, 100 VDC or 100 Vp-p Yes, 500 VDC or 500 Vp-p RTD inputs Sensor type : Current: Connection: Wire resistance compensation in the 3-wire connection: Wire resistance compensation in the 2-wire connection: Maximum resistance of wires (to...

 Open the catalog to page 3
MPI-CN-4

Number of inputs: Maximum input voltage: Measurement range: Minimum pulse width: BINARY INPUTS 4 30 VDC or 30 Vp-p 0.001 Hz - 10 kHz. (0.001 Hz - 1 kHz if the filtrating capacitor is connected) 20 μs (0.5 ms if the filtrating capacitor is connected) Configuration: OC / contact Voltage (OC): Current (contact): Switch on / off threshold: Configuration: input voltage Input resistance: Switch on / off threshold: Voltage (OC): Namur configuration: High impedance: Low impedance: Signal connections: Number of outputs: Type of outputs: Maximum load current: Maximum voltage: Wire connection: MPI-C, MPI-CL:...

 Open the catalog to page 4
MPI-CN-5

Green – red LED on the face plate. Recording indication: Transmission protocol: Interface: Data buffer: Number of connections opened simultaneously: Connection: Indication LEDs: ETHERNET PORT Modbus TCP, ICMP (ping), DHCP server, http server 10BaseT Ethernet 300 B 4 RJ-45 2, in RJ45 socket INTERNAL DATA MEMORY Capacity: 2 GB Estimated recording time for recording speed every 3 s for 16 ca. 400 days measuring channels: Recording indication: Green – red LED on the face plate. Supply voltage: Power consumption: Wire connection: Supply voltage: Power consumption: Wire connection: Type of housing:...

 Open the catalog to page 5
MPI-CN-6

INPUT TYPE MEASUREMENT ACCURACY Pt100 *K (K=1..11) Ni100 *K (K=1..11) J (Fe - CuNi) K (NiCr - Ni) T (Cu - CuNi) E (NiCr - CuNi) N (NiCrSi - NiSi) B (Pt30Rh -Pt6Rh) R (Pt13Rh - Pt) S (Pt10Rh - Pt) Linear / root-shaped (2) / userdefined – real measurement pitch, the pitch range can be set within the range of 0.0001 - 1. – the resistance sensor can be set within a sub-range ( 200 - 600 Ohm), but it limits the signal processing performance. (3) – the voltage can be set within a sub-range ( 0 mV - 50 mV), but it limits the signal processing performance. (4) – root-shaped characteristics within the...

 Open the catalog to page 6

All Metronic AKP catalogs and technical brochures

  1. KK DL7

    11  Pages

  2. MLOG

    2  Pages

  3. CONV 485USB-I

    2  Pages

  4. BC-3N

    5  Pages

  5. MPI-8E

    5  Pages

  6. FP-3021

    5  Pages

  7. FP-3021N

    5  Pages

  8. FP-3031

    5  Pages

  9. FP-3031N

    5  Pages

  10. FP-3011

    5  Pages

  11. FP-3011N

    5  Pages

  12. MPI-C

    6  Pages

  13. MPI-CL

    6  Pages

  14. MPI-D

    5  Pages

  15. MPI-DN

    5  Pages

  16. CONV 485E

    3  Pages

  17. BC-3

    5  Pages

  18. DL-7

    8  Pages

  19. CONV 485USB

    2  Pages

  20. CONV485E

    3  Pages

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.