1. Catalogs
  2. METREL
  3. MI 2891 Power Simulator EN

MI 2891 Power Simulator EN

MI 2891 Power Simulator EN

MI 2891 Power Simulator EN

Product catalog summary
Overview
The MI 2891 Power Simulator is a versatile three-phase power simulator designed for simulating typical scenarios in low voltage power supply systems. It serves as an effective tool for training, demonstrations, and educational purposes in electrical engineering.

Applications
  • Training purposes
  • Demonstration of Power Quality Analyzer (PQA) testing equipment
  • Education for students in electrical technical specialties

Standards
  • Safety: EN 61010-1: 2010
  • Electromagnetic compatibility (EMC): EN 61326-2-2: 2013

Measuring Functions
  • Voltage
  • Current
  • Frequency
  • Harmonics (Voltage and Current)
  • Phase angle (Voltage and Current)
  • Flicker
  • Phase sequence (Voltage and Current)

Key Features
  • Waveform generator with various settings
  • 4 voltage channels with a range up to 350 Vrms
  • 4 current channels with simulation up to 2kA
  • Simultaneous voltage and current simulation with 16-bit DA conversion
  • Simulation of dip, swell, interrupt, transient, and inrush events
  • Harmonics and unbalanced waveform simulation
  • Square flicker simulation
  • Comprehensive signal parameter settings
  • 4.3’’ TFT color display

Technical Specifications
  • Fundamental RMS voltage output: 50 ... 300 V, accuracy ± 0.1%
  • Event RMS voltage output: 0 ... 350 V, accuracy ± 0.1%
  • Fundamental RMS current: 100 A ... 2000 A, accuracy ±0.1%
  • Frequency range: 45 Hz ... 70 Hz, accuracy ± 10 mHz
  • Flicker type: Pst 0.5 ... 5.0, accuracy ± 1%
  • Voltage harmonics: 1% ... 100% of fundamental output, accuracy ± 5%
  • Current harmonics: 1% ... 100% of fundamental current, accuracy ± 5%
  • Unbalance range: 0.5% ... 5.0%, accuracy ± 0.15%
  • Event duration: 10 ms ... 7 days, error ± 1 cycle

General Information
  • Measuring category: CAT I / 300 V
  • Dimensions: 23 cm x 14 cm x 8 cm
  • Weight: 1.34 kg with batteries
  • Display: 4.3 TFT LCD with backlight
  • Battery: 6 x 1.2 V NiMH rechargeable batteries
  • Working temperature range: -20 °C ... +40 °C
See more

Catalog excerpts

MI 2891 Power Simulator EN-1

Equipment for laboratories and Schools Demonstration Board MI 2891 Power Simulator The MI 2891 Power Simulator is a multi-purpose three phase power simulator for simulating typical situations in low voltage power supply systems. It is an excellent tool for training, demonstration purposes, or as an electrical didactic tool. The simulator has some pre-programmed scenarios, and also the option of a complete manual mode. The user can decide between different Load character adjustments, adjustable current and voltage level with a simulation of varios different faulty conditions. MEASURING FUNCTIONS • Voltage • Current • Frequency • Harmonics (U,I) • Phase angle (U,I) • Flicker • Phase sequence (U,I) • Simple and powerful waveform generator with various settings, • 4 voltage channels with wide simulation range: up to 350 Vrms, • 4 current channels with current clamps simulation up to 2kA, • Simultaneous voltage and current (8 channels) simulation, 16 bit DA conversion for accurate signal generation, • Dip, swell, interrupt, signalling, transient and inrush events simulation, • Voltage and current harmonics waveform simulation. • Unbalanced voltage and current waveform simulation. • Square flicker simulation. • Various character load/character type combination simulation. • Thorough signal parameters settings. • Saving current system settings on power off. • 4.3’’ TFT colour display. • Training purposes • Demonstration of PQA testing equipment by sales personnel • Education of students of electro technical specialities STANDARDS Safety: • EN 61010-1: 2010 Electromag

 Open the catalog to page 1
MI 2891 Power Simulator EN-2

TECHNICAL SPECIFICATION ORDERING INFORMATION Fundamental RMS voltage output Output voltage AC 50 ... 300 V Event RMS voltage output Output voltage AC 0 ... 350 V Fundamental RMS current Range A 1033 (100 A ... 2000 A) Overall current accuracy ±0.1 % Inrush RMS current output Inrush current Range 1: 2.0 mVRMS ... 200.0 mVRMS Range 2: 20.0 mVRMS ... 2.0000 VRMS Accuracy ± 0.5 % · URMS ± 0.5 % · URMS Frequency Output range 45 Hz ... 70 Hz Flickers Flicker type Pst Voltage harmonics Measuring range UhN 1 % ... 100 % of fundamental output voltage UhN: N: Current harmonics and THD Measuring range IhN...

 Open the catalog to page 2

All METREL catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.