1. Catalogs
  2. METREL
  3. Application note: Earth resistance measurement and 62 percent rule

Application note: Earth resistance measurement and 62 percent rule

Application note: Earth resistance measurement and 62 percent rule

Application note: Earth resistance measurement and 62 percent rule

Product catalog summary
Specifications and Preconditions:
The document outlines a rule from IEEE 81-2012 Annex C, which is based on a simplified model of rods with specific preconditions: the current through both rods (E and H) is the same, the soil is uniform, and the electrodes are hemispherical. If the distance between E and H is sufficient, they can be treated as hemispherical electrodes.

Earth Resistance Measurement and the 62% Rule:
The 62% rule is a well-known guideline in earth resistance measurements using the Fall of Potential (FoP) method. It states that the measurement S probe should be placed at 61.8% of the distance between the center E of the tested earthing system and the auxiliary test probe H.

Application Note:
For earth resistance measurements on objects with auxiliary grounding, such as transmission towers, the condition IE = IH is not met. In such cases, the earthing current IE must be measured separately using the method described in IEEE 81-2012 Ch. 8.2.2.6, implemented in the MI 3290 Earth Analyser.

Graphical Presentation and Measurement Adjustments:
During measurements, both probes E and H conduct current, causing a ground potential rise (GPR) around the electrodes, depicted as a funnel. The GPR of one probe affects the other, leading to measurement errors. The 62% method helps mitigate this by ensuring the voltage between E and S (62%) reflects the GPR of the E probe without H probe influence.

Correction Formula and Coefficient:
The formula for distance between E and S must be adjusted with a coefficient ki, resulting in shorter distances. The document provides a table of typical ki values and corresponding distances as a percentage of D. For example, if ki = 0.4, the S probe should be positioned at 46% of the distance between E and H.

Conclusion:
The document provides detailed guidelines and adjustments for accurate earth resistance measurements, emphasizing the importance of the 62% rule and the need for corrections based on specific conditions.
See more

Catalog excerpts

Application note: Earth resistance measurement and 62 percent rule-1

Application Note Earth resistance measurement and the 62% rule Everybody, who is familiar with the earth resistance measurements knows the 62 % rule: The rule (recommendation) is defined in IEEE 81-2012 in Annex C. It is based on simplified model of rods and some additional preconditions: - Current trough both rods (E and H) is the same: IE = IH - Uniform soil - Hemispherical electrodes If the distance between E and H rode is big enough, then the rods can be treated as hemispherical electrodes. If the soil can be treated as uniform soil then the following equations are valid: The distance between the E and S is calculated out of the following equation (C.9 in IEEE 81): 1 1 (D-x) D When performing the earth resistance measurement with the Fall of Potential (FoP) method you have to put the measurement S probe on a distance of 61,8% of the distance between the centre E of the tested earthing system and the auxiliary test probe H. The positive root of equation is the location of the S probe x0 = dE_S=0.618 D The S probe must be located on the straight line between E and H probe.

 Open the catalog to page 1
Application note: Earth resistance measurement and 62 percent rule-2

During the measurement both probes E and H conduct a current therefore the potential around the electrodes raises (GPR – ground potential raise). The graphical presentation of this potential raise around the probe has a form of a funnel (Figure 2). is influenced by the GPR of the other probe. When performing the measurements of the potential raise around the probe only the summary of both GRP can be measured. Therefore simple measurement of the voltage between E probe and zero ground results in an error and one of the possible solution is to use the 62% method. Within this method and the above...

 Open the catalog to page 2
Application note: Earth resistance measurement and 62 percent rule-3

Therefore the formula Eq.1 must be corrected with the coefficient ki: ki = This results in shorter distances between E and S probe: Figure 4: 4 flex clamp method Some typical values of ki and corresponding distances dE_S between E and S are listed in the table below: ki METREL D.D. Measuring and Regulation Equipment Manufacturer Ljubljanska 77, SI-1354 Horjul, Slovenia T +386 (0)1 75 58 200, F +386 (0)1 75 49 226 [email protected], www.metrel.si 46% 62% For example, if ki = 0,4 then the S probe must be positioned on 46% of the distance between E and H probe. The funnel around the auxiliary H probe...

 Open the catalog to page 3

All METREL catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.