Introduction
The RD-30 is a versatile three-phase reference standard with a typical accuracy of ±0.02% at power factor (PF) of 1, and a worst-case accuracy of ±0.04% for PF ≥ 0.5. It is designed to measure real-world waveforms accurately, using advanced analog to digital conversion and electronically compensated transformers.

Characteristics
The RD-30 includes a Harmonic Analysis option for analyzing up to the 64th harmonic order and a built-in Comparator for automatic test result calculations. It can test revenue meters and reference standards using a controlled current source and perform three-phase meter accuracy tests in the field.

Technical Data
  • Current Range: 3 × 1mA to 120 (200)A, auto-ranging
  • Voltage Range: 3 x 30 to 630V at 60Hz, 3 x 30 to 525V at 50Hz, auto-ranging
  • Auxiliary Power Range: 3 × 60 to 630V, auto-ranging
  • Frequency: 40 to 70Hz
  • Power Factor Range: Any
  • Operating Temperature: -20°C to +70°C
  • Humidity: 0 to 95%, non-condensing

Measurement Modes
The RD-30 supports various measurement modes including 2-wire, 3-wire, and 4-wire configurations for active, reactive, and apparent power.

Accuracy and Drift
  • Power/Energy Accuracy: Typical ±0.02% at PF=1, Worst Case ±0.04% at PF≥0.5
  • Current Accuracy: ±0.028%
  • Voltage Accuracy: ±0.02%
  • Long Term Drift: Power/Energy: ±0.0055% first year, ±0.0175% over ten years; Current: ±0.0042% first year; Voltage: ±0.0028% first year
  • Temperature Drift: None between +20°C and +30°C, ±0.0005%/°C outside this range

Additional Features
The RD-30 offers optional features such as a built-in comparator and harmonic analysis. It is suitable for testing high-end energy meters in various settings including power plants and substations.
See more

Catalog excerpts

RD-30 THREE-PHASE REFERENCE STANDARD-1

■^1 THREE-PHASE REFERENCE STANDARD RD-30THREE-PHASE REFERENCE STANDARD r Typical Accuracy: ±0.02% @ PF=1 r Worst Case Accuracy: ±0.04% @ PF>0.5

 Open the catalog to page 1
RD-30 THREE-PHASE REFERENCE STANDARD-2

INTRODUCTION The RD-30 three-phase reference standard is one of the most versatile reference instruments ever. The RD-30 has a typical accuracy of ±0.02% @ PF=1 for all measurement functions across its entire operating range, with a maximum worst case accuracy of ±0.04%. This worst case accuracy specification includes the variables of stability, power factor, traceability uncertainty and test system errors. A unique design makes the RD-30 unsurpassed in its ability to accurately measure "real world" waveforms. The RD-30 reference meter includes an exclusive analog to digital signal converter...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.