1. Catalogs
  2. Mersen - Electrical Power
  3. DIN HIGH VOLTAGE FUSE-LINKS

DIN HIGH VOLTAGE FUSE-LINKS

DIN HIGH VOLTAGE FUSE-LINKS
1 / 20 PagesView full catalog

DIN HIGH VOLTAGE FUSE-LINKS

Product catalog summary
Mersen and the HV Fuse-Links Market
Mersen offers a wide range of high voltage (HV) DIN fuse-links for use in HV substations, switchgear, controlgear, and systems. These fuse-links provide reliable protection by interrupting fault currents before they peak. Key features include high breaking capacity, current limitation, low switching voltage, quick breaking, and non-ageing properties. The Limitor® brand is dedicated to HV fuse-links, ensuring expertise, reliability, and safety.

Standards and Certifications
Mersen's HV fuse-links comply with standards such as IEC 60282-1, VDE 0670 T4, VDE 0670 T402, and DIN 43625. The equipment and accessories meet standards like IEC 60787, IEC 62271-105, DIN 43624, and VDE 0670 T303. Mersen's quality and environmental management systems are ISO 9001 and ISO 14001 certified, respectively.

Types of HV Fuse-Links
According to IEC standards, there are three types of fuse-links: Back-up, General purpose, and Full range. Mersen provides Back-up and General purpose fuse-links. Back-up fuse-links handle currents from the rated maximum to the rated minimum breaking current, while General purpose fuse-links manage currents from the rated maximum to the melting current within one hour.

Innovations
Mersen has introduced innovations such as a new cap design, low power dissipation, and a patented thermal striker. The striker is a mechanical device that releases energy to operate another device. Options for striker operation include regular, Controlled Power Dissipation (CPD), and Thermal Striker (TS), which monitors fuse-link temperature to prevent overheating.

Low Power Dissipation and Compatibility
The latest fuse-element design reduces power dissipation, suitable for compact enclosed substations. PTD and PTS fuse-links are designed for low power losses and compatibility with air and SF6 insulated compact switchgear. The new cap design enhances compatibility with various fuse clips.

Product Descriptions and Cataloging
Mersen's catalog number system includes information on type, voltage rating, current rating, and features like the striker and thermal striker. Dimensions of HV DIN fuse-links are defined by DIN 43625, with diameter and length related to current and voltage ratings.

Technical Data and Specifications
The document provides detailed technical data for various fuse-links, including voltage, length, current rating, reference number, catalog number, standards compliance, thermal striker, CPD, diameter, breaking currents, resistance, power dissipation, and weight. For more technical data, curves, and references, Mersen's website is recommended.
See more

Catalog excerpts

DIN HIGH VOLTAGE FUSE-LINKS-1

Expertise, our source of energy W PRODUCT GUIDE

 Open the catalog to page 1
DIN HIGH VOLTAGE FUSE-LINKS-2

MERSEN AND THE HV FUSE-LINKS MARKET Mersen offers a wide range of HV DIN fuse-links to be used in HV substations, HV switchgear, HV controlgear and HV systems for reliable protection of HV/LV power distribution transformers and HV distribution networks. Designed to be combined with other equipment, these current-limiting fuse-links interrupt fault currents before they reach their peak. Mersen is offering current limiting fuses with high breaking capacity, offering the best protection against short circuit current. Mersen is also a key player in innovative solutions to increase safety and efficiency:...

 Open the catalog to page 2
DIN HIGH VOLTAGE FUSE-LINKS-3

Fuse description FR vs DIN Aluminium caps • DIN standard: German standard • FR standard: French standard Copper caps Silver coating • BS standard: British standard • UL standard E or R rated: American standard • Special HV fuses links Mersen is offering a very large range of fuses in accordance with UL, DIN and FR standards. Fuse element in pure silver Different types of high voltage fuse-links IEC standard defines 3 types of fuse-links: Back-up, General purpose and Full range. Mersen offers Back-up and General purpose fuse-links. Back-up fuse-links range Current-limiting fuse capable of breaking...

 Open the catalog to page 3
DIN HIGH VOLTAGE FUSE-LINKS-4

Striker The striker is a mechanical device forming a part of a fuse-link which releases the energy required to cause operation of another switching device or signalling device. The Mersen striker is a “medium” type with an effective length of 30mm and initial force of 80N. Mersen HV fuse-links have all a striker function Mersen offers 3 different options to operate the striker in HV fuses: • First one (regular) is driven by the fuse element when it is melting • Second one (CPD) is driven by the control of the power dissipation of the fuse-link according to Ohm's law. As the back-up fuse-link...

 Open the catalog to page 4
DIN HIGH VOLTAGE FUSE-LINKS-5

Outdoor type Mersen offers several technologies for fuse-elements to propose a compromise between cost and performance / efficiency depending on the application. All Mersen DIN HV fuse-links are for outdoor and indoor use. The latest innovation with a new fuse-element design in cast-in-one-piece structure to reduce power dissipation. They are brown and all are tested at the end of production. PTD fuse-links were specifically developed to be installed in compact-sized enclosed substations because they have a limited thermal power acceptance. PTS fuse-links were specifically designed with low power...

 Open the catalog to page 5
DIN HIGH VOLTAGE FUSE-LINKS-6

S for VDE0670T402 and dedicated switch-fuse combination D for VDE0670T402 45 mm diameter D for B for Voltage rating in V/100 Current rating P for of contact caps DIN Back-up in A striker Catalog Number T for Thermal Striker or Controlled Power Dissipation D for VDE0670T402 Fuse-link description 1 - Cap 2 - Body 3 - Rod 4 - Fuse element 5 - Sand 6 - Striker LEARN] MORE

 Open the catalog to page 6
DIN HIGH VOLTAGE FUSE-LINKS-7

LIMITOR®-B BACK-UP FUSE LINKS ACCORDING TO IEC 60282-1 HV fuse-links standard: DIN 43625 DIN 43625 defines the dimensions of HV DIN fuse-links. All Mersen HV DIN fuse-links are in compliance with this standard. The diameter "d” is mainly related to the current rating (50 to 88mm) and the length "e” is mainly related to the voltage rating (192 to 537mm). DIN 43625 defines lengths in accordance with voltage rated like shown in the table below:

 Open the catalog to page 7
DIN HIGH VOLTAGE FUSE-LINKS-8

LIMITOR®-B BACK-UP FUSE LINKS ACCORDING TO IEC 60282-1 * For more technical data, curves, references, etc, visit our website.

 Open the catalog to page 8
DIN HIGH VOLTAGE FUSE-LINKS-9

* For more technical data, curves, references, etc, visit our website.

 Open the catalog to page 9
DIN HIGH VOLTAGE FUSE-LINKS-10

LIMITOR®-B BACK-UP FUSE LINKS ACCORDING TO IEC 60282-1 * For more technical data, curves, references, etc, visit our website.

 Open the catalog to page 10
DIN HIGH VOLTAGE FUSE-LINKS-11

* For more technical data, curves, references, etc, visit our website.

 Open the catalog to page 11
DIN HIGH VOLTAGE FUSE-LINKS-12

* For more technical data, curves, references, etc, visit our website.

 Open the catalog to page 12
DIN HIGH VOLTAGE FUSE-LINKS-13

LIM ITOR®-G GENERAL PURPOSE FUSE-LINKS ACCORDING TO IEC 60282-1 RATED VOLTAGE RANGE OF FUSE-LINK [kV] * For more technical data, curves, references, etc, visit our website.

 Open the catalog to page 13
DIN HIGH VOLTAGE FUSE-LINKS-14

Bases with optional indicator

 Open the catalog to page 14
DIN HIGH VOLTAGE FUSE-LINKS-15

INDICATING DEVICES The indicating device enables electrical actuating of the opening mechanism for a circuit or triggering of an indicator during the melting of a fuse equipped with a trip-indicator. This very robust and original device means freedom for any mechanical system and offers the advantage of being able to incorporate a microswitch unit or units according to the equipment configuration. TUBE DE NEUTRE NEUTRAL CONDUCTOR External adaptor 292/442mm REF. NUMBER

 Open the catalog to page 15
DIN HIGH VOLTAGE FUSE-LINKS-16

HV fuses standard: IEC 60282-1 High-voltage fuses - Part 1: current-limiting fuses This part of IEC 60282 applies to all types of high-voltage current-limiting fuses designed for use outdoors or indoors on alternating current systems of 50 Hz and 60 Hz and of rated voltages exceeding 1000V. This standard defines test set-up, fuse characteristics and normal service conditions (without derating) like: • Operating temperature: -25°C to 40°C • Altitude: 1000m maximum It is advisable to replace all three fuse-links when the fuse-link on one or two phases of a three-phase circuit has operated, unless...

 Open the catalog to page 16
DIN HIGH VOLTAGE FUSE-LINKS-17

Rated voltage range It is important for HV fuse-links that they must be operated at the voltage for which they have been rated. Accordingly, the operating voltage corresponds to the maximum rated voltage of the fuse-link. Owing to the switching voltage occurring during arcing, the fuse-link cannot be used at lower voltages without limitation. A lower operating voltage at which the fuse-link can still be used without exceeding the system insulation level during extinction must therefore be taken into account. From these two values results the permissible voltage range of the fuse-link, which is...

 Open the catalog to page 17
DIN HIGH VOLTAGE FUSE-LINKS-20

MeRseivI Expertise, our source of energy W GLOBAL EXPERT IN ELECTRICAL POWER AND ADVANCED MATERIALS EUROPE ASIA AMERICAS FRANCE MERSEN France SB S.A.S. 15 rue Jacques de Vaucanson F-69720 Saint-Bonnet-de-Mure + 33 4 72 22 66 11 [email protected] CHINA MERSEN Shanghai Co. Ltd. No.55-A6. Shu Shan Road, Songjiang 201611 Shanghai + 8621 67602388 USA MERSEN USA Newburyport-MA L.L.C. 374 Merrimac Street Newburyport, MA 01950 +1 978-462-6662

 Open the catalog to page 20

Archived catalogs