MFT-X
1 /9Pages

MFT-X

MFT-X
1 /9Pages

Catalog excerpts

MFT-X-1

MFT-X1 Multifunction tester True Loop™ test with patented Confidence Meter™ CertSuite™ compatible Bluetooth® result transfer Next generation 2-wire and 3-wire non-trip loop testing User upgradeable operating system High resolution 0.001Ω loop test Automatic volt-drop measurement Stabilised insulation test voltage Configurable RCD and EV auto-sequence tests Fast switch rechargeable plug-in battery pack Full colour TFT bonded display Re-designed lead set and carry case solution IP54 operational housing Patented Confidence meter technology The MFT-X1 new electrical installation testing platform MFT-X1 is the first of a new generation of firmware upgradeable, full functionality multi-function testers for low voltage electrical installations. All loop impedance ranges are now supported by the Megger patented Confidence meter technology, reducing typical test times for non-trip loop testing to around 7 seconds on quiet circuits, and providing optimised test times for loop impedance testing in difficult noisy supplies. The Confidence meter shows the progress of the loop measurement and indicates the presence of noise on the circuit, removing erroneous values to give a stable and consistent result. Intended for use on all low voltage electrical installations including EV charge points and domestic photo-voltaic systems, the range of test capabilities allow for general commissioning of installations and periodic maintenance as well as detailed fault diagnostics. MFT-X1 result downloading and CertSuite FEATURES True Loop™ True Loop™ impedance testing is now a standard feature on the MFT-X1. The latest 3-wire non-trip loop testing technology, incorporated with the patented Confidence Meter™, offers an unmatched, reliable, accurate, stable and repeatable loop test solution to the user, allowing testing in the most hostile high noise conditions or close to the source of supply. The technology also removes the risk of RCD uplift whilst reducing typical test times – even on circuits protected by 6 mA or 10 mA protective devices. Test results can be tagged with circuit data and transferred to CertSuite, the latest cloud base electrical certification software package from Megger. When paired to a mobile device using the low energy Bluetooth® mode, results can be sent directly from the MFT-X1 to an Android or IOS device running Megger CertSuite software. These results are also synchronised with the cloud-based application. With a wide range of certification options, CertSuite is available as a monthly or yearly subscription package for electrical certification of installations taking results directly from the MFT whilst testing. CertSuite is suitable for multiple concurrent users and is optimised for use with the MFT-X1. Results can be stored and reviewed remotely by users whilst on site from different locations, accessed by head office or other users with the relevant permission, with professional looking certification and

 Open the catalog to page 1
MFT-X-2

MFT-X1 Multifunction tester High resolution loop impedance testing The MFT-X1 has extended the low end of the loop impedance range from 0.01 ohms to 0.001 ohms resolution and 50 kA current calculation. The True Loop impedance measurement using the patented confidence meter makes these low impedance measurements a realistic option, with two wire test connections and high current testing. RCD custom testing RCD testing can now be optimised with the RCD test configurator. Select a whole suite of tests or only those elements of the RCD you require. You can even add ramp testing to the sequence, optimising...

 Open the catalog to page 2
MFT-X-3

MFT-X1 Multifunction tester FUNCTIONAL SUMMARY Voltage measurement Voltage range 0.001 V to 2 V (mV range) 2 V to 600 V (V range), 1000 V DC (on-CAT rated circuits) Voltage type: Phase sequence Automatic phase sequence testing on detection of valid three phase supplies Current measurement (non-contact) AC Trms Using optional accessories: MCC1010 current clamp Measurement Range Continuity/Resistance Measurement range Digital display Measurement Range Analogue arc Test voltage Test current (Nominal) >200 mA 0 Ω >< 2 Ω 10 mA Auto reduction on high resistance (actual current reported in display)...

 Open the catalog to page 3
MFT-X-4

MFT-X1 Multifunction tester 3 Phase testing Non-trip: Single phase only High current: Three phase High resolution: Three phase 3 wire - non-trip Test types RCD (non-trip) RCD EV (non-trip on 6mA EV RDCs) Voltage range Frequency range Single phase only Volt drop Volt drop calculation Requires Zref (Ze) and circuit current (I-vdrop) Dependent on loop impedance accuracy RCD testing RCD types supported 1/2x I∆n, 1x I∆n, 2x I∆n, 5x I∆n, Ramp, 0º/180º (customer configurable) Ramp testing Fault (Touch) voltage Earth testing 2 wire 2 wire earth resistance test

 Open the catalog to page 4
MFT-X-5

MFT-X1 Multifunction tester SPECIFICATIONS Voltage measurement Function Voltage AC/TRMS Millivolt measurement Live Earth detection Indicates if the PE terminal is live when selecting the Loop or RCD test ranges. The relevant Loop or RCD test is inhibited. Current Function Current AC/TRMS Frequency Bandwidth Resistance and Continuity Function Range Test Current 100 Ω – 999 kΩ Open circuit voltage

 Open the catalog to page 5
MFT-X-6

MFT-X1 Multifunction tester Insulation test Function Leakage current Output voltage -0% +2% +2 V at rated load or less Voltage display Short circuit current Test current on load 1 mA at min pass values of insulation Maximum capacitance 2 µF for a stable reading, 5 µF absolute limit Loop 2-Wire - No RCD (L-PE, L-N or L-L) Function Range 2-Wire HR Supply Voltage Supply Frequency Can be used to measure supply source resistance quickly and reliably between Line and PE or two Live conductors up to 550 V. EN61557-3 Measurement Range: 0.30 Ω to 1999 Ω Loop 2-Wire L-PE with RCD Function Range 0.01 Ω...

 Open the catalog to page 6
MFT-X-7

MFT-X1 Multifunction tester Loop 3-Wire L-PE with RCD Designation Test Current For circuits protected by an RCD rated <= 30 mA For EV charger circuits protected by a RDC and a Type A RCD rated <= 30 mA Supply Voltage Supply Frequency Note: Uses the Megger Confidence Meter to measure the supply source impedance of circuits protected with an RCD when three connections are possible. The L-N Loop resistance needs to be less than 12 Ω. The resistances of the L-PE, L-N and N-PE loops are all shown, and the accuracy of the L-PE resistance depends on the maximum resistance displayed. When the neutral...

 Open the catalog to page 7

All MEGGER catalogs and technical brochures

  1. digiPHONE+2

    8  Pages

  2. SPG 5-1000

    2  Pages

  3. PFL22M1500

    2  Pages

  4. digiPHONE+

    2  Pages

  5. Torkel 900

    6  Pages

  6. Easyloc

    3  Pages

  7. SMART THUMP

    3  Pages

  8. TRAX

    24  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.