Gasfilter DF50 - 3

Table of contents Application, characteristics, technical data Application 4 Characteristics 4 Types of models / Options Technical data Installation example Sectional view Dimensions, connection and weight Types of models / Options Volume flow diagram Design 10 Order data Observe the following publications in relation to ATTENTION installation, start-up and maintenance: DVGW - work sheets G 491 and G 600 Operating and Maintenance Instructions DF50 List of abbreviations and formula symbols AC Accuracy class AGo Upper response pressure group AGu Lower response pressure group BV Breather valve...

Open the catalog to page 3
Gasfilter DF50 - 4

Application, characteristics, technical data Application Type DF 50 filters are intended to separate gas impurities such as dust, rust, and other solids in gas-carrying line at a defined point. They are mainly used in gas systems and in front of such devices whose function is impaired by contamination. These filters can be used for gases according to DVGW worksheet G 260/G 262 and for neutral non-aggressive gases. (other gases on request) Easily replaceable filter cartridge High separation efficiency thanks to optimized flow guidance (30 µm standard, 5 µm optional) Type of models / Options...

Open the catalog to page 4
Gasfilter DF50 - 5

Technical data Type For screw-in units with flange set Nominal width Connection type Gas thread ISO 7-1 from Rp½ to Rp2 or ANSI-ASME B1.20 from ½“NPT to 2“NPT Flange PN16 – ISO 7005 from DN65 to DN300 Material Housing - Die-cast aluminum (up to DN100) - Sand-cast aluminum (from DN125) Filter - Non-woven polypropylene fibbers with metal supporting frame Seals - NBR Temperature range (operating/ambient temperature) Filtering area Filtration efficiency Particle size > 30 µm (5 µm optional), filter class G4 to EN 779 Function, strength, and tightness DIN 3386, DVGW work sheet G 498 and DIN...

Open the catalog to page 5
Gasfilter DF50 - 6

Structure and function The gas flows through the inlet flange into the filter housing. The dust particles entrained in the gas are retained by the filter element. The cleaned gas flows off through the outlet flange. The filters mainly consist of the housing, the cover, and the filter cartridge. Taking off the cover for maintenance and replacement of the filter cartridge guarantees easy access. The filter cartridge is made of non-woven polypropylene fibers, is equipped with a metal support frame and is suitable for holding dust and other impurities with a size >= 30 µm (>=5 µm optional). If...

Open the catalog to page 6
Gasfilter DF50 - 7

Dimensions, connection, and weight

Open the catalog to page 7
Gasfilter DF50 - 8

Types of models / Options Black epoxy resin coating To protect the gas filters from influences in aggressive atmospheres. Biogas or coke oven gas version For screw-in filters with flange set DN25-DN50

Open the catalog to page 8
Gasfilter DF50 - 9

Volume flow diagram • • • • for natural gas (ρn = 0.83 kg/m³; t = 15°C) Δp = pressure difference from inlet pressure to outlet pressure Qn = max. possible volume flow f - natural gas L conversion factor Gas f Hs,n Gas f Hs,n [kWh/m³] [kWh/m³] Acetylene 0.84 16.25 Sewage gas 0.84 Ammonia 1.04 4.83 Carbon monoxide 0.81 3.51 Butane 0.55 37.23 Carbon dioxide 0.65 Chlorine 0.51 - Air 0.80 Landfill gas approx. 0.80 Methane 1.08 11.06 Natural gas L 1.00 9.77 Propane 0.64 28.03 Natural gas H 1.03 11.45 Oxygen 0.76 Ethane 0.78 19.55 Sulphur dioxide 0.53 Ethylene 0.97 16.516 Nitrogen 0.81 Mine gas...

Open the catalog to page 9
Gasfilter DF50 - 10

Design If the flow rate read from the diagram is based on the operating pressure instead of the pressure at standard conditions (p=1.01325 bar, t=15°C), the pressure drop read from the diagram must be multiplied by the following factor: (1+ relative pressure in bar) Example: With a filter of size Rp1½" and an operating natural gas flow of 80 Nm3/h, the pressure drop according to the diagram is ∆p = 2 mbar. If this 80 Nm3/h flow is at 2 bar, then the effective pressure drop must be calculated as follows: ∆p = 2 mbar*) x [(1 + 2)x1/bar] = 6 mbar *) Determined from the diagram The filter must...

Open the catalog to page 10
Gasfilter DF50 - 11

Order data Example: Order selection Type DF50 DN - Nominal width Max. operating pressure 2 bar 6 bar Acceptance test certificate to EN 10204/3.1 without acceptance test certificate with acceptance test certificate Special model - Black epoxy resin coating - Biogas or coke oven gas version - With flange set - 5 µm Filter type: Order code:

Open the catalog to page 11
Gasfilter DF50 - 12

The Medenus plus 10 reasons for good business relations 1. Consultancy expertise and quality standards developed over decades 2. Broad and proven standard range of feedback controllers 3. Modern, fast and efficient production for series products and for individual orders 4. Customer-specific design of pressure regulators and vacuum regulators and special designs 5. Guaranteed deadline compliance with a delivery deadline guarantee 6. Fast response time in all matters 7. Sufficiently large parts storage for production and spare parts 8. Customer-specific theory & practice training courses 9....

Open the catalog to page 12
Gasfilter DF50 - 13

Contact Management ALEXANDER CHRISTIANI Technical Inside Sales Department MINDAUGAS PECKAITIS Phone: Mail: Head of Sales & Marketing FRANZ FEICHTNER Inside Sales Department SEBASTIAN HUCKESTEIN Head of Inside Sales Department MANUEL SCHEPP Inside Sales Department STEFANIE MÜLLER If you want to know more about solutions from MEDENUS for the gas industry, please contact your local contact person or go to our internet site at www.medenus.de Trade representation worldwide medenus.de/de/kontakt.html Gas-Druckregeltechnik GmbH Im Langen Feld 3 D-57462 Olpe Phone: +49 (0)2761 82788-0 Fax: +49...

Open the catalog to page 13
Gasfilter DF50 - 15

In the download area of our homepage, this document is available in different languages. You can use the following QR codes and links to go directly to this document in your language.