Catalog excerpts
USER'S MANUAL
Open the catalog to page 11.0 GENERAL POINTS The instruments of the family "MPT90" represent a series of " Single Loop" microprocessor temperature regulators in the standard 48x48 dimensions (96 mm. depth.) The complete version of the MPT90 instrument has the following technical characteristics: 1- Input from Thermoresistance PT100 ( scale -40.0 ÷ 200.0°C or -40 ÷ 800°C), or from thermocoupling Fe/CO (0÷600°C) and Cr/Al (0÷1200°C) and Pt-Pt/Rh (0 ÷ 1710°C), or from voltage ( 0÷ 10 V ) and current (0/4 ÷ 20 mA) selectable from the keyboard. 2- Two display to see Set-Point and Process Value and 4 keys for an easy...
Open the catalog to page 4MPT90 M1 cutback const.: 0 ÷ F.S. °C/°F of min. or max in the range: 0 ÷ F.S. °C/°F Alarms relay contact 220V /5A Main Outputs relay contact 220V /5A Alarm output Power supply 25Vac or 115Vac or 230Vac or 12÷30 Vdc Analogue outputs 0 ÷ 10 V – 0 ÷ 20 mA – 4 ÷ 20 mA Max load for current 300 Ω output Min load for voltage 1 KΩ output 10 V Max voltage given 20 mA Max current given 12 bits Resolution 1.2 DISPLAY MESSAGES The following table shows a summary of all the messages that the instrument can show on the display. Some are operating signals, others are indications of anomalies or non...
Open the catalog to page 5MPT90 M1 1.3 MPT INSTRUMENT CONNECTION OVERVIEW DESCRIPTION OF THE FRONT COMMANDS PV-Upper Display: temperature as read by sensor SP-Lower Display: set-point (power percentage on manual control) Led AL: alarm status indication or cooling action or servomotor control drive (if requested ) Led R: ramp function indication Led ON: load control indication : access to the programming functions : increase set-point. Used for programming function : decrease set-point. Used for programming function : enter the enable Ramp programs (disabled of the menu) : START/STOP functions. Only ramp functions...
Open the catalog to page 6MPT90 M1 DESCRIPTION OF THE TERMINAL BOARD inputs for sensor transducer power supply ( see configurations ) analogue outputs (OAP option) or serial output (if requested) enable second set-point (if RSP option is requested) instrument power supply. Between terminals 7 and 8 power from 90V to 260V , or from 10V to 30V if requested. Terminals 9, 10: contact NO of main relay ( A option ) or static output (C option) or alarm 2 conctat (OAP option) and analogue output control. Terminals 11, 12: contact NO of alarm relay (if requested: 03 option) For thermoresistance connection pay attention to...
Open the catalog to page 7VOLTAGE OR CURRENT INPUT CONNECTIONS CURRENT/VOLTAGE INPUT CONNECTIONS WITH TRANSDUCER POWER SUPPLY This connection can be used if the transducer power supply is configured ( see TERMINAL 3 CONFIGURATION). STATIC OUTPUTS CONNECTIONS V+ Be careful: this output is not isolated and may be used for an external solid state relay with double isolation between instrument and power line. ALARM CONCTACT (not available with “F” or “G” option) ME4020_08 10/11
Open the catalog to page 8SERVOMOTOR CONNECTIONS valve closing valve supply valve opening TERMINAL 3 CONFIGURATION ( TRANSDUCER POWER SUPPLY ) Open the instrument and set the jumper JP2 for a PT100 input (standard) or for a transducer power supply connection. ANALOGUE OUTPUTS CONNECTIONS
Open the catalog to page 92.0 INSTALLATION NOTES 1. Copy the connection schemes on pages 5, 6 and 7 taking into account the following points: a- the instrument can operate with analogue inputs or temperature sensors of both thermoresistance and thermocoupling types. Only one of this sensors can be connected (attach the connection only for the chosen sensor, leaving free the other connections.). b- the connector diagram shows all the possible options that the instrument may have; if certain options are not required then the relative connections are not necessary. 2. Follow the instructions of the paragraph: 2.1: for...
Open the catalog to page 102.1.1 DIAGRAM MENU WITH HEATING OR COOLING CONTROL I 3 = number relevant to used table Search for the item to change, shown in the upper display using key The value to change is shown on the lower display. If you must change a number, use the key to increment the blinking digit, and thel_key to shift the blinking digit, and if you must select an item, use the To exit the menu, press the modified parameters will be stored.
Open the catalog to page 11OuAn OuAn if requested analogue outputs tCOn = In for heating control tCOn = dlr for cooling control
Open the catalog to page 12MPT90 M1 Table 3 NOTES See ref. touch appears on appears on key PV display SP display page In this phase the instrument asks for Pp enter PASS 0 000 1 the Password in order to save the data 44 already programmed. The number memorized by the factory is 0, but any number between 0 and 9999 can be memorized by writing where CPAS appears (next displayed item). PASS 0 0 00 Set Up Procedure. 2 SP-4 To digit the desired number touch the key " SP-4" to move the flashing number to the right. PASS 0 1 00 3 SP+5 Touch the key " SP+5" to increase the flashing number enter CPAS 0 000 Number of the...
Open the catalog to page 13MPT90 M1 ref. touch appears on appears on key PV display SP display NOTES decimal point and confirm with "enter" Set the requested reading with the beginning of the analogue input. To digit the number see 2 and 3 paragraphs. Set the requested reading with the full scale of the analogue input. To digit the number see 2 and 3 paragraphs. Choose rISC for heating regulation with the main relay. Set the requested regulation by “SP+5” and confirm with “enter“. Lower limit set-point. To digit the number follow the procedure described in points 2 and 3 Upper limit set-point. To digit the number...
Open the catalog to page 14MPT90 M1 ref. touch appears on appears on key PV display SP display Ramp/ Exit NOTES OFF: Minimum alarm relay is enabled after the first time the temperature reaches the alarm value To change this item use the “SP+5“ key and confirm by “enter” Alarm value set up (if requested). To digit the value see steps 2 and 3. An alarm can work as minimum alarm (if < set-point) or maximum alarm (if > set-point). Alarm 1 hysteresis set up Possibility of inverting the relay function nA = normally open nC = normally closed Set the requested regulation by “SP+5” and confirm with “enter“. If analogue...
Open the catalog to page 15All MECT SRL catalogs and technical brochures
-
TPAC1008
22 Pages
-
TPAC1007
14 Pages
-
TPAC1006
22 Pages
-
MPA-MPV M6
42 Pages
-
MPA386 M6
39 Pages
-
MPP P6
19 Pages
-
MPA-MPV P6
18 Pages
-
MP40 P6 Simple imput
16 Pages
-
MP40 P6 Multi input
17 Pages
-
MPX28
8 Pages
-
MPSN20
2 Pages
-
MPCV015
20 Pages
-
MPT390 M6
61 Pages
-
MPT91 M1
66 Pages
-
MPT60 M1
45 Pages
-
MPT100 M1
35 Pages
-
MPCIB396 P6
41 Pages
-
MPCIB20 M1
25 Pages
-
MPCT301 P6
53 Pages
-
MPCT300 P6
37 Pages
-
MPCT30 P6
36 Pages
-
MPCT20 M1
35 Pages
-
MP2200 M6
44 Pages
-
MP1200 P6
36 Pages
-
MPPV340 M6
40 Pages
-
MPO347 M6
40 Pages
-
MPP323 M6
42 Pages
-
MPPV010 P6
40 Pages
-
MP45 P6
18 Pages
-
MPM P6
34 Pages
-
MP30 P2
15 Pages
-
MP20 M1
35 Pages
-
MPNC030
12 Pages
-
TPLC005
28 Pages
-
MPNC020
13 Pages
-
MPNC010
25 Pages
-
TP1070
15 Pages
-
TP1057
15 Pages